FLUID COMPONENTS INTERNATIONAL LLC

                             FLT93 Flow Switch Series

This page is subject to proprietary rights statement on last page

4

 

 

 

Doc. No. 06EN003312 Rev. D

Jumper Placement

Input Power

Relay Energization

Selectable Heater Wattage Control

Jumper Locations  (Underlined Jumpers are default)

Relay Contact Configuration

Standard Default Jumper Configuration

J22 SINGLE SPDT (DISABLES ALARM NO. 2)
J23 DUAL DPDT (ONE RELAY PER A LARM)

100-130 V A C 200-260 V A C 21-30 V DC 18-26 V A C

J1

IN

OUT

OUT

OUT

J2

OUT

IN

OUT

OUT

J3

IN

OUT

OUT

OUT

J4

OUT

OUT

OUT

IN

J5

IN

IN

OUT

OUT

J6

OUT

IN

IN

IN

J7

OUT

OUT

IN

OUT

J8

OUT

OUT

IN

OUT

J9

OUT

OUT

OUT

IN

POWER SELECT

JUM PER

FLOW / LEVEL

TEMP

ALARM NO. 1

J20

J21

ALARM NO.2

J18

J19

JUM PER

J32

J12

J13*

J14*

J33

FLT93-F ELEMENT 
WA TTAGE (560 OHM HTR)

FLT93-S ELEMENT 
WA TTAGE (110 OHM HTR)

0.57 

WATTS

0.52 

WATTS

WATTS

1.75 

WATTS

*J13 IS STANDARD FOR FLT-S AND J14 IS STA NDA RD FOR FLT93-F.

0.75 

WATTS

0.21 

WA TTS

OFF

OFF

0.49 

WATTS

0.25 

WA TTS

JUM PER

ALARM NO. 1

RELAY DE-ENERGIZED WITH LOW FLOW,
LOW LEVEL (DRY) OR HIGH TEMPERATURE.
RELAY DE-ENERGIZED WITH HIGH FLOW,
HIGH LEVEL (WET) OR LOW TEMPERATURE.

ALARM NO. 2

RELAY DE-ENERGIZED WITH LOW FLOW,
LOW LEVEL (DRY) OR HIGH TEMPERATURE.
RELAY DE-ENERGIZED WITH HIGH FLOW,
HIGH LEVEL (WET) OR LOW TEMPERATURE.

J27

J26

J25

J24

INPUT POWER

FLT93-S 0.75 WATTS FOR AIR OR LIQUID APPLICATIONS (J13)

FLT93-F 0.25 WATTS FOR AIR OR LIQUID APPLICATIONS (J14) 

NUMBER OF ALARMS

230 VAC (J2, J5 AND J6), OR FM APPROVAL 120 VAC (J1, J3, J5)

SET TO MONITOR FLOW OR LEVEL SIGNALS (J20).                           
RELAY ENERGIZED BELOW TEMPERATURE (J25)                            
SET POINT AT APPROXIMATELY:                                                         
250°F (121°C) FOR STANDARD TEMPERATURE,                             
500°F (260°C) FOR MEDIUM TEMPERATURE,                                         
850°F (454°C) FOR HIGH TEMPERATURE (FLT93-S ONLY).

HEATER POWER

ALARM NO. 1 RED LED 
SET POINT POT R26

ALARM NO. 2 GREEN LED 
SET POINT POT R25

SET TO MONITOR FLOW OR LEVEL SIGNALS (J20).                           
RELAY ENERGIZED AT FLOW OR WET (J27)

TWO (J23).  EACH ALARM HAS ONE SET OF SPDT CONTACTS.

Alarm Application

Summary of Contents for FLT93 Series

Page 1: ...lement Serial Number Also Showing FlowArrow Located near the FE enclosure It is also on the enclosure tag Electronics Serial Number It is also on the transmitter s FT enclosure tag C Recommended insta...

Page 2: ...1 megohm resistor connected to ground Connect the instrument to ground Apply antistatic agents such as Static Free made by Chemtronics or equivalent to hand tools to be used on the instrument Keep hi...

Page 3: ...Remote Wiring Pictorial FLT93 Integral Wiring Diagram Maximum Distance for AWG Connection 10 ft 50 ft 100 ft 250 ft 500 ft 1000 ft 3m 15m 31m 76m 152m 305m AC Power 22 22 22 20 18 16 Relay 6A 22 16 12...

Page 4: ...OR FLT S AND J14 IS STANDARD FOR FLT93 F 0 75 WATTS 0 21 WATTS OFF OFF 0 49 WATTS 0 25 WATTS JUMPER ALARM NO 1 RELAY DE ENERGIZED WITH LOW FLOW LOW LEVEL DRY OR HIGH TEMPERATURE RELAY DE ENERGIZED WIT...

Page 5: ...h alarm can be setup for one of three applications flow level interface or temperature The following application specific adjustment procedures are generic and can be used for setting either or both a...

Page 6: ...turn the set point adjustment potentiometer clockwise until the LED turns on With the LED on slowly turn the potentiometer counterclockwise one turn past the point at which the LED just turns off The...

Page 7: ...kwise until the LED turns off With the LED off slowly turn the potentiometer clockwise one half turn past the point at which the LED just turns on The potentiometer may have up to one quarter turn of...

Page 8: ...No 2 counterclockwise until the LED turns off and then slowly clockwise just until the LED turns on 8 If this is the only flow application alarm to be setup then skip to the Continue With the Air Gas...

Page 9: ...ontinue With the Air Gas Flow Procedure 1 Slide the mode switch to the RUN position 2 Establish the normal process flow condition For low flow alarm setups the status LED should be off For high flow a...

Page 10: ...etecting Wet Condition high level alarm If the status LED is on turn the set point adjustment potentiometer R26 for alarm No 1 or R25 for alarm No 2 slowly counterclockwise just until the LED turns of...

Page 11: ...ge is out of tolerance NOT OK The serial numbers on the control board and the sensing element must match If the serial numbers are OK then contact FCI Field Service c The Voltage is between 1 and 6 vo...

Page 12: ...secrets and proprietary information which is the property of Fluid Components International LLC FCI Disclosure of this data to you is expressly conditioned upon your assent that its use is limited to...