background image

FLUID COMPONENTS INTERNATIONAL LLC

                             FLT93 Flow Switch Series

This page is subject to proprietary rights statement on last page

8

 

 

 

Doc. No. 06EN003312 Rev. D

Detecting Decreasing Flow (low flow alarm)

1. Stop the process flow and allow the signal to stabilize.

2. Record the no-flow signal.  (The no-flow signal should be greater than the normal flow signal.)

No-Flow Signal = ________ volts DC

3. Determine the set point by calculating the average of the normal and no-flow output signals.   (i.e.; If the normal

signal is 2.000 volts and the no-flow signal is 5.000 volts, then the calculated set point would be 3.500 volts.)

4. Record this value.

Calculated Set Point = ________ volts DC

Note:

The calculated set point must be at least 0.020 volts greater than the normal signal to ensure that the alarm
will reset.

5. Slide the mode switch to the CALIBRATE position.

6. Adjust the calibrate potentiometer (R24) until the voltmeter equals the calculated set point.

7. For the appropriate alarm, determine whether the status LED is on or off (red for No. 1 or green for No. 2).

If the LED is off, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm No.2) slowly
clockwise just until the LED turns on .

OR

If the LED is on, turn the set point adjustment potentiometer (R26 for alarm No. 1 or R25 for alarm No. 2)
counterclockwise until the LED turns off and then slowly clockwise just until the LED turns on.

8. If this is the only flow application alarm to be setup, then skip to the Continue With the Air/Gas Flow Procedure.

Detecting Increasing Flow (high flow alarm)

1. Establish the excessive process flow condition and allow the signal to stabilize.

2. Record the high flow signal.  (The high flow signal should be less than the normal flow signal.)

High Flow Signal = ________ volts DC

3. Determine the set point by calculating the average of the normal and high flow output signals.  (i.e., If the normal

signal is 2.000 volts and the high flow signal is 1.000 volts, then the calculated set point would be 1.500 volts.)

4. Record this value.

Calculated Set Point = ________ volts DC

Note:

The calculated set point must be at least 0.020 volts less than the normal signal to ensure that the alarm will
reset.

5. Slide the mode switch to the CALIBRATE position.

6. Adjust the calibrate potentiometer (R24) until the voltmeter equals the calculated set point.

7. For the appropriate alarm, determine whether the status LED is on or off (red for No. 1 or green for No. 2).

If the LED is on, turn the set point adjustment potentiometer ( R26 for alarm No. 1 or R25 for alarm No. 2) slowly
counterclockwise just until the LED turns off.

OR

If the LED is off, turn the set point adjustment potentiometer ( R26 for alarm No. 1 or R25 for alarm No. 2)
clockwise until the LED turns on and then slowly counterclockwise just until the LED turns off.

Summary of Contents for FLT93 Series

Page 1: ...lement Serial Number Also Showing FlowArrow Located near the FE enclosure It is also on the enclosure tag Electronics Serial Number It is also on the transmitter s FT enclosure tag C Recommended insta...

Page 2: ...1 megohm resistor connected to ground Connect the instrument to ground Apply antistatic agents such as Static Free made by Chemtronics or equivalent to hand tools to be used on the instrument Keep hi...

Page 3: ...Remote Wiring Pictorial FLT93 Integral Wiring Diagram Maximum Distance for AWG Connection 10 ft 50 ft 100 ft 250 ft 500 ft 1000 ft 3m 15m 31m 76m 152m 305m AC Power 22 22 22 20 18 16 Relay 6A 22 16 12...

Page 4: ...OR FLT S AND J14 IS STANDARD FOR FLT93 F 0 75 WATTS 0 21 WATTS OFF OFF 0 49 WATTS 0 25 WATTS JUMPER ALARM NO 1 RELAY DE ENERGIZED WITH LOW FLOW LOW LEVEL DRY OR HIGH TEMPERATURE RELAY DE ENERGIZED WIT...

Page 5: ...h alarm can be setup for one of three applications flow level interface or temperature The following application specific adjustment procedures are generic and can be used for setting either or both a...

Page 6: ...turn the set point adjustment potentiometer clockwise until the LED turns on With the LED on slowly turn the potentiometer counterclockwise one turn past the point at which the LED just turns off The...

Page 7: ...kwise until the LED turns off With the LED off slowly turn the potentiometer clockwise one half turn past the point at which the LED just turns on The potentiometer may have up to one quarter turn of...

Page 8: ...No 2 counterclockwise until the LED turns off and then slowly clockwise just until the LED turns on 8 If this is the only flow application alarm to be setup then skip to the Continue With the Air Gas...

Page 9: ...ontinue With the Air Gas Flow Procedure 1 Slide the mode switch to the RUN position 2 Establish the normal process flow condition For low flow alarm setups the status LED should be off For high flow a...

Page 10: ...etecting Wet Condition high level alarm If the status LED is on turn the set point adjustment potentiometer R26 for alarm No 1 or R25 for alarm No 2 slowly counterclockwise just until the LED turns of...

Page 11: ...ge is out of tolerance NOT OK The serial numbers on the control board and the sensing element must match If the serial numbers are OK then contact FCI Field Service c The Voltage is between 1 and 6 vo...

Page 12: ...secrets and proprietary information which is the property of Fluid Components International LLC FCI Disclosure of this data to you is expressly conditioned upon your assent that its use is limited to...

Reviews: