background image

FLT93 Flow Switch Series

FLUID COMPONENTS INTERNATIONAL LLC

Doc. No. 06EN003312 Rev. D

9

This page is subject to proprietary rights statement on last page

Wet/Dry Liquid Level Applications

1. Remove the instrument's enclosure cover.

2. Ensure the configuration jumpers on the control circuit are correct for this application.  See the tables on page 4.

3. Check to make sure the input power jumpers match the power to be applied to the instrument.  See the power input

table on page 4.

4. Apply power to the instrument.  Verify the yellow LED is on and allow the instrument fifteen minutes to

warm-up.

5. Verify the mode switch is in the RUN position.

6. Attach a DC voltmeter to P1  with the positive (+) lead to position one and the negative (-) lead to position two.

Note:

The terminal block can be unplugged from the control circuit to facilitate easy connections.  The terminal
block is used in late production instruments.  Early production instruments used a mating cable and
connector. If a cable and connector are required use FCI part number 015664-01 to order.

7. Raise the process fluid level so the sensing element is wet.

8. Allow the output signal to stabilize and record the wet condition value.

Wet Condition Signal = ________ volts DC

Note:

The output signal at  P1 is relative to the type of process media detected.  See the figure on page 4.

9. Lower the process fluid level so the sensing element is dry.

10. Allow the output signal to stabilize and record the dry condition value.  (The dry signal should be greater than the

wet signal.)

Dry Condition Signal = ________ volts DC

Continue With the Air/Gas Flow Procedure

1. Slide the mode switch to the RUN position.

2. Establish the normal process flow condition.  For low-flow alarm setups, the status LED should be off.  For high flow

alarm setups, the status LED should be on.

3. Establish the process alarm condition and monitor the voltmeter display.

4. When the output signal passes through the calculated set point value, the status LED should turn on for low-flow

alarms, off for high flow alarms, and the relay contacts should change state.

5. Reestablish the normal process flow condition.  Both the LED and the relay contacts should reset.

6. Disconnect the voltmeter from P1.

7. Replace the enclosure cover.

Note:

The alarm can be set for a specific flow rate.  Follow the Air/Gas Flow Application procedure up to step 7
except establish the specific flow rate rather than the normal flow.  The output signal will be the set point
value.  Determine whether the alarm should actuate with decreasing or increasing flow and skip to the
appropriate step 4 in Detecting Decreasing Flow or Detecting Increasing Flow, respectfully.  Enter the
specific flow rate value as the set point.  Then follow the Continue With the Air /Gas Flow Procedure steps.

The relay logic default configuration is set for the relay coil to be de-energized when the flow signal voltage
is greater than the set point value.  (i.e., Assume that the normal process flow condition has been
established.  In this state, the relay coil will be energized if the alarm has been set for low-flow detection
and de-energized if the alarm has been set for high flow detection.)  A recommendation is to have the relay
coils energized when the process condition is normal.  This will enable the alarm to close or open the
contacts in case of a power failure.

Summary of Contents for FLT93 Series

Page 1: ...lement Serial Number Also Showing FlowArrow Located near the FE enclosure It is also on the enclosure tag Electronics Serial Number It is also on the transmitter s FT enclosure tag C Recommended insta...

Page 2: ...1 megohm resistor connected to ground Connect the instrument to ground Apply antistatic agents such as Static Free made by Chemtronics or equivalent to hand tools to be used on the instrument Keep hi...

Page 3: ...Remote Wiring Pictorial FLT93 Integral Wiring Diagram Maximum Distance for AWG Connection 10 ft 50 ft 100 ft 250 ft 500 ft 1000 ft 3m 15m 31m 76m 152m 305m AC Power 22 22 22 20 18 16 Relay 6A 22 16 12...

Page 4: ...OR FLT S AND J14 IS STANDARD FOR FLT93 F 0 75 WATTS 0 21 WATTS OFF OFF 0 49 WATTS 0 25 WATTS JUMPER ALARM NO 1 RELAY DE ENERGIZED WITH LOW FLOW LOW LEVEL DRY OR HIGH TEMPERATURE RELAY DE ENERGIZED WIT...

Page 5: ...h alarm can be setup for one of three applications flow level interface or temperature The following application specific adjustment procedures are generic and can be used for setting either or both a...

Page 6: ...turn the set point adjustment potentiometer clockwise until the LED turns on With the LED on slowly turn the potentiometer counterclockwise one turn past the point at which the LED just turns off The...

Page 7: ...kwise until the LED turns off With the LED off slowly turn the potentiometer clockwise one half turn past the point at which the LED just turns on The potentiometer may have up to one quarter turn of...

Page 8: ...No 2 counterclockwise until the LED turns off and then slowly clockwise just until the LED turns on 8 If this is the only flow application alarm to be setup then skip to the Continue With the Air Gas...

Page 9: ...ontinue With the Air Gas Flow Procedure 1 Slide the mode switch to the RUN position 2 Establish the normal process flow condition For low flow alarm setups the status LED should be off For high flow a...

Page 10: ...etecting Wet Condition high level alarm If the status LED is on turn the set point adjustment potentiometer R26 for alarm No 1 or R25 for alarm No 2 slowly counterclockwise just until the LED turns of...

Page 11: ...ge is out of tolerance NOT OK The serial numbers on the control board and the sensing element must match If the serial numbers are OK then contact FCI Field Service c The Voltage is between 1 and 6 vo...

Page 12: ...secrets and proprietary information which is the property of Fluid Components International LLC FCI Disclosure of this data to you is expressly conditioned upon your assent that its use is limited to...

Reviews: