background image

   

 

 

 

 

 

 

     

    

Orion-M

 

 

3.2     FDC Orion-M 

 

 

 

 

 

 

 

 

 

 

 

 

                CONFIGURING THE UDC2500/3200 CONTROLLER 

3.2  Input Type Assignments 

The  Honeywell  UDC2500/3200  controls  provide  universal  input  types  for  input  1.    An  optional  analog  input 
(voltage/current)  for  input  2  is  available  on  the  UDC2500  while  the  UDC3200  can  provide  an  optional 
universal input for input 2.  The Loop Input # for the corresponding control in the Orion-M Configurator is set 
to match the selected input type for input 1 of the UDC control while the second input can be configured as a 
monitor point in the Orion-M. 
 

IMPORTANT:

  The  Orion-M  is  unable  to  detect  sensor  break  or  input  failure  conditions  on  the  Honeywell 

UDC2500 or UDC3200 controller.  Therefore, a problem may exist with a controller input, but 
the Orion-M will be unable to report the alarm condition. 

 
 

If  the  failure  of  an  input  is  a  critical  alarm  condition  that  requires  monitoring,  the  orion-M 
provides 30 alarms that can be configured to any loop or monitor input.  A process alarm can 
be  configured  with  alarm  set  points  outside  of  the  normal  operating  range  for  the  input.    A 
failure  of  the  input  on  the  UDC2500/3200  would  result  in  a  high  scale  or  low  scale  break, 
which could then be detected and reported by the alarm set in the Orion-M.    

 
 

3.2.1 

Input 1 Operation 

When input 1 of the UDC2500/3200 is a temperature input, i.e., RTD or thermocouple, the temperature units 
of  the  input  on  the  UDC2500/3200  must  be  set  to  match  the  selection  in  the  Orion-M  on  the  Degrees  C/F 
screen.  The Orion-M can not change the temperature units on the UDC controller.  Thus, when  you set up 
the UDC controller, its temperature units must match that of the selection in the Orion-M.   If the selections do 
not match, the Orion-M may show units of degrees Centigrade while the actual value from the UDC control is 
in degrees Fahrenheit. 
 
In addition, if %RH (wetbulb) is selected for a Loop Input in the Orion-M Configurator, the temperature units in 
the Orion-M must match the UDC controllers for the drybulb/wetbulb calculation to be performed correctly.  If 
the temperature units do not match, the relative humidity reading on the Orion-M will not be correct. 
 

NOTE:

 

It is recommended that the Degrees C/F selection screen  be disabled in the Orion-M Configurator 
once the proper temperature units selection has been made to prevent it from being accessed.  This 
will prevent the temperature units from being accidentally changed and causing operator confusion 
when  the  units  do  not  match  between  the  UDC  control  and  the  Orion-M.    See  section  3.6  Orion 
Functions/Startup  View,  in  the  Orion-M  Configuration  Manual  for  information  on  enabling  and 
disabling this item. 

 
For  either  temperature  or  process  (voltage/current/carbon)  input  types,  the  Orion-M  will  set  the  lower  and 
upper  set  point  limits  for  the  input  to  match  the  settings  in  the  Orion-M  Configurator.    The  decimal  point 
selection for the Loop Input in the Orion-M and the UDC controller do not have to be set to match; however, if 
the loop controls are visible to the operator, it is recommended that the decimal point resolution of the Orion-
M and UDC controller match. 
 
Loop Inputs set as temperature in the Orion-M Configurator allow a decimal point selection of 0 or 1.  Process 
type loop inputs can be displayed on the Orion-M with a resolution of 0 to 3 decimal points.  The Orion-M has 
a  display  range  of  -32768  to  32767,  -3276.8  to  3276.7,  -327.68  to  327.67  or  -32.768  to  32.767  depending 
upon decimal point selection.  When selecting the decimal point resolution for the Loop Input in the Orion-M 
Configurator, make sure that range of the UDC2500/3200 does not exceed the range selected in the Orion-M 
or the value may not be displayed correctly.   
 

IMPORTANT:

  The lower and upper set point limits are set once, each time the Orion-M enters the runtime 

application.  Do not alter the values in the UDC2500/3200 control once they have been set or 
the Orion-M may not be able to set the correct set point to the controller.      

 

Summary of Contents for Orion-M

Page 1: ...Orion M Honeywell UDC2500 3200 Series Controller System Guide Rev C February 7 2011 Supersedes Rev B March 25 2010 Orion M Honeywell UDC2500 3200 Controller System Guide...

Page 2: ...ion to verify that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the above you can get technical assistance by dialing 1...

Page 3: ...1 1 Communications Wiring 2 1 3 Configuring the Honeywell UDC2500 3200 Controller 3 1 3 1 Assigning the Proper Communications Settings 3 1 3 2 Input Type Assignments 3 2 3 2 1 Input 1 Operation 3 2 3...

Page 4: ......

Page 5: ...No other control system on the market provides the flexibility functionality and configurability of the Orion M 1 1 Features The digital inputs of the Orion M can be configured as alarm inputs with a...

Page 6: ...includes the following interface features Overview screen that displays all runtime information Profile run and monitor views Profile entry open save and download interface screens Current alarm and a...

Page 7: ...ring to and form the UDC controllers be routed away from all high voltage and or output control wiring This will minimize the chances of electrical transients or spikes in the power control wiring fro...

Page 8: ...UDC2500 or UDC3200 Product Manual for all other connections including power sensor and control wiring Since no two applications are the same it is up to the system designer to insure that the control...

Page 9: ...munications link beginning with 1 up to the total number of controllers As control loops are enabled in the Orion M Configurator the Orion M will automatically use the Loop Input as the corresponding...

Page 10: ...he Orion M Configurator the temperature units in the Orion M must match the UDC controllers for the drybulb wetbulb calculation to be performed correctly If the temperature units do not match the rela...

Page 11: ...f the loop control is visible to the operator it is recommended that the Monitor Input Offset screen be hidden see Section 3 6 Orion Functions Startup View in the Orion M Configuration Manual or even...

Page 12: ...M is designed to send the shed timer reset command to the UDC controller to take it out of computer set point control when the set point permission is enabled This allows control via the keypad of the...

Page 13: ...Orion M APPENDIX FDC Orion M A 1 Appendix...

Page 14: ...ter delivery to the first purchaser for use There are no expressed or implied Warranties extending beyond the Warranties herein and above set forth Limitations Future Design Controls provides no warra...

Reviews: