Page 39 of 91
Rev. 4.20
ADDRESS
:
the point and loop addresses (no mod.).
ZONE
:
the zone address of the point loop (mod., range value
1-
63
).
NAME
:
the name of the point (mod.).
TYPE
:
point type (no mod.).
SECTION
:
the section where the point is (no mod.).
O.OF SERVICE
:
it indicates if the point is in out of service (mod.
YES
or
NO
).
FAULT
:
it indicates if the point is fault (no mod.).
LED ON
:
if
YES
the leds flash (mod.
YES
or
NO
).
INPUT
:
the input is active-able like only
TECHNOLOGICAL
type
(mod.).
SING.CONSEN.
:
it is used when the control panel is supervisory mode and
the zone of the point is enabled the "double consent". If
YES
, when the detector go to alarm status, the control
panel go to fire alarm too. The possibility to modify this
function is given provided that there are at least 2 points
on the specific zone. If after deleting of a point, the
assigned zone at double consent has only one installed
point, this parameter value will read
No
(mod.
YES
or
NO
)
and the zone must be at single consent.
SERIAL NUM
:
the serial number of the detector (no mod.).
SW VERSION
:
the software version of the detector (it is changed through
PC).
SUP.SMOK LEV
:
the smoke level in supervisory mode. This level refers at
the
SMOKE
value (mod. Range:
80-150
). Beyond this
value, the alarm goes active.
NSUP.SMK LEV
:
the smoke level in no supervisory mode. This level refers
at the
SMOKE
value (mod. Range:
80-150
). Beyond this
value, the alarm goes active.
SMOKE(0-255)
:
it indicates the smoke into the detector with a range of
0-
255
(no mod.).
DIRTY %
:
the dirty % of the detector. If the value exceeds
80%
, the
control panel send the problem with a message (no mod.).
EFFICIENCY %
:
the efficiency % of the detector. If the value goes under
25%
, the control panel send the problem with a message.
This value depends of the device sensor (no mod.).
RATE-OF-RISE
:
if value is
YES
, the heat detector has rate-of-rise function
too (no mod.).
SUP.TEMP LEV
:
the temperature level in supervisory mode. This level
refers at the
TEMP.
value (mod. Range:
40-70
). Beyond
this value, the alarm goes active.
NSUP.TEMP LEV
:
the smoke level in no supervisory mode. This level refers
at the
TEMP.
value (mod. Range:
40-70
). Beyond this
value, the alarm goes active.
TEMP. °C
:
it indicates the temperature measure from the detector (no
mod.).
Point setting
•ADDRESS: 001-1
ZONE: 01
NAME: ROOM1
TYPE: SMOKE+HEAT DE
SECTION: A-B
OUT OF SERVICE: NO
FAULT: NO
LED ON: NO
INPUT: DISABLED
SINGLE CONSENSE: NO
SERIAL NUM:002-00001
SW VERSION: 2.00
SUPERV.SMOK LEV: 130
NSUPER.SMOK LEV: 100
SMOKE (0-255): 003
DIRTY %: 000
EFFICIENCY %: 100
RATE-OF-RISE: NO
SUPERV.TEMP LEV: 058
NSUPER.TEMP LEV: 056
TEMP. °C: 25.32
Esc. Pre. Next Mod.