background image

Page 65 of 91

Rev. 4.20

13.1 DETAILS

The control panel allows to manage the functions of evacuation / extinguish which can be manually activated from 
the panel itself or directly when a fire alarm occurs.
The settings of the evacuation are run within the “

Evacuation setting

” (see chapter 

 

10.3).

The evacuation phase can be subdivided into 4 parts:

1)

FIRE ALARM

:

whenever the control panel detects an alarm, fire type; it will go into “

Fire alarm

” 

status.

2)

EVACUATION

:

following a pre-set delay given by the initial settings for a fire alarm detection, the 
evacuation procedure is initialized. The internal buzzer and all outputs/exits set up 
as evacuation are activated and a red led lights up “

evacuation

” is lit and 

signalled.

3)

EXTINGUISH

:

following a pre-set delay given from the initial settings of the evacuation procedure, 
the evacuation process comes to an end to make way for the extinguishing 
procedure. The internal buzzer and all outputs dedicated to the extinguishing 
become active, while the outputs with evacuation function are turned off.

4)

RESTORE

:

following a pre-set delay given by the initial settings of the extinguish procedure, 
the extinguishing process will terminate. All outputs dedicated to the extinguish with 
red led “

evacuation

” are turned off.

STATO CENTRALE

Fire outputs

Evacuation outputs

Extinguish outputs

FIRE ALARM

On

Off

Off

EVACUATION

On

On

Off

EXTINGUISH

On

Off

On

RESTORE

On

Off

Off

PART 13

EVACUATION

EVACUATION

EXTINGUISH

RESTORE

FIRE ALARM

Summary of Contents for EX-CP4L

Page 1: ...NUAL EX CPL FIRE CONTROL PANEL EXCELLENT FIRE SYSTEM FDP International Group S r l Via Pierobon 127 35010 LIMENA PD ITALY Tel 39 049 767249 fax 39 049 767898 E mail info fdpinternational com www fdpin...

Page 2: ...Sensor 17 PART 3 PRELIMINARY REMARKS FOR A CORRECT INSTALLATION 18 3 1 LINE CABLE TEST PROCEDURE BEFORE LOOP CONNECTION 18 3 1 1 Line continuity 18 3 1 2 Shielded 18 3 1 3 Isolation between positive a...

Page 3: ...3 5 Point address selection 41 7 3 6 Zone address selection 41 PART 8 ZONE PROGRAMMING 42 8 1 DETAILS 42 8 2 ZONE CREATION 42 8 3 ZONE SETTING 42 8 3 1 Main menu 42 8 3 2 Zone menu 42 8 3 3 Loop selec...

Page 4: ...ETTABLE BUTTON 73 15 2 1 Input and output description 73 15 2 2 Button addressing 73 15 2 3 Manual zero setting of the address 73 15 2 4 Point setting 73 15 2 5 Electrical scheme 74 15 3 INPUT OUTPUT...

Page 5: ...Page 5 of 91 Rev 4 20...

Page 6: ...st be used in each loop Connectible detectors Smoke detector EX SOD EX SD Heat detector EX TD Multi criteria detector EX MD Connectable modules Manual button EX P5 EX MP Input Output module EX MEIO Is...

Page 7: ...32 Report of detector check The control panel is preset for a further output PS2 to which it is possible to connect a keyboard for a quicker programming of points and zones All the programming of the...

Page 8: ...For a suitable selection of the acquisition procedure refer to the PRELIMINARY REMARKS FOR A CORRECT INSTALLATION Remember that The acquisition of points through the installation is preferred when it...

Page 9: ...nce every time 2 2 CONNECTING THE CONTROL PANEL TO THE MAIN POWER LINE 230VCA It is expected that the electrical wiring edifice building in which the Control Panel resides is adequately furnished with...

Page 10: ...net cables and loops cables Watching frontally box the metallic opened three rectangular openings on the bottom and three holes sluices pre cut on the top part can be viewed Use the holes in the follo...

Page 11: ...anual 6 close the front cover by re screwing all the screws provided In the case the electronic card should be completely removed and or re inserted into the metallic case pay extra attention to the g...

Page 12: ...nterfaces Don t forget use shielded and twisted cable to reduce the interferences The section will depend on the length of loop WARNING Installations with cable length superior to 2Km are not advised...

Page 13: ...nd included between the two modules isolator will be disconnected with the consequent loss of communication of a maximum of 32 elements maximum number of elements that the rule UNI 9795 allows to lose...

Page 14: ...le to always use a fire resistant double twisted and protected cable for the installation Depending on how the CONFIG parameters are set up see chapter 9 2 4 it is necessary to modify while the contro...

Page 15: ...connected between the open Collector output and the clip of the 24Vdc ausiliary output In this condition the maximum current available is of 24 27mA this value depends on a resistance of 1K that it co...

Page 16: ...or cable to the power supply the conductor cable endings should be pin type this to ensure and maintain the safety conditions 2 5 9 Battery connections On the control panel electronic circuit board th...

Page 17: ...ion too Any problem must be noted in the event register solving the probable problems as soon as possible 2 8 4 Yearly control The maintenance staff must have the duty to perform the following control...

Page 18: ...e between 20 and 25 Besides the resistance of the negative cable and the positive one must result similar 3 1 2 Shielded It must present treble the resistance of line cables at most Warning if shielde...

Page 19: ...between shielded clip and the clip R and the terminal R and common terminal common clip of base nr 2 or nr 3 FURTHER CHECK FOR SHORT CIRCUITS ON THE LOOP LINE AND POWERED UP SYSTEM Connect the negativ...

Page 20: ...sed the system will go back to level 1 automatically 4 1 1 Control panel controls Main control keys Silence Silence the internal buzzer Reset Delete all the alarm conditions and rearm the control pane...

Page 21: ...if the siren output is delayed In this case in the corner in top at right of the display to appear a siren icon Activated output Yellow Lit led at active outputs Fault Yellow The control panel has po...

Page 22: ...SELECT AN ITEM FROM THE MENU OF THE CONTROL PANEL Point menu view mod insert remove d b reset ACCESS LEVEL 1 Sel Back Esc Sel Select Back Preview Esc Escape Button for menu selection Item selected But...

Page 23: ...at level 1 it is necessary to insert the suitable codes to enter the superior levels The access levels are divided as described below Level 1 All the information is operative the control panel contro...

Page 24: ...o silence at once the buzzer inside the control panel pressing the key silence placed GENERAL SIREN SILENCE MODE If you need to silence the siren s output and or all the ones enabled to this command s...

Page 25: ...ected area which have gone into alarm When the evacuation procedure is enabled status check and related extinguishing procedure Menu access to the control panel menu View details of selected visualize...

Page 26: ...etail In order to visualize messages which differ from the ones listed on display press Ala and select the list of events you wish to visualize List of types of messages Only the assigned groups with...

Page 27: ...el of the system the control panel will log and list all the relevant conditions 4 6 1 Main menu Enter the Main menu with the provided arrow keys in display select EVENT To confirm with the Sel button...

Page 28: ...re three start up procedures loop reset LOOP RESTART to select when isolators are not zero address in loop RESTART INST ISOLAT to select when isolators are present along the loop with address zero Aft...

Page 29: ...e intense flashes indicate and sub divide the hundred count for the points for the tens you will see short sequence light flashes instead By correctly counting the brief light flash impulse you can de...

Page 30: ...on confirming the occurred identification with a beep In case of missing points these will not be acquired the control panel will continue to search for the missing point till the time out period ends...

Page 31: ...must be selected 6 1 3 Loop start restore loop selection When it is necessary to start or reset loop to enter the menu Loop start restore it is necessary to select o k reset from the menu It is now po...

Page 32: ...l scanning from point a control panel starting to the first possible isolator point 121 127 and in succession among isolators as far as point B control panel arrival Afterwards it will scan the loop i...

Page 33: ...s must have address 0 The acquisition of points through serial number provides for the acquisition of a point through the research of the series number of the same point The acquisition of points thro...

Page 34: ...n the line that shows the type of address assignment the user wants to select and confirm with Sel Type in Del to return to the Point menu 7 1 5 Type of point acquisition After the user has entered th...

Page 35: ...ing the acquisition step is comprised between the levels visualizes on the display Set yourself on the line and select Mod The data are modified with the numerical keyboard At the end of the possible...

Page 36: ...R NUM and press the Mod command to insert the initial serial number Press Ok to initialize the acquisition Press Canc to terminate the operation When the Point to Install is confirmed on the menu the...

Page 37: ...to modify some parameters as an example the zone of belonging or the element name 7 2 1 Main menu After the user has entered the Main menu select POINT and confirm with the key Sel to pass to Point m...

Page 38: ...are not modifiable Example the Type of point the SECTION of belonging the SW VERSION etc To view other information relative to the point that has been examining it is necessary to wait a few seconds...

Page 39: ...e mod Range 80 150 Beyond this value the alarm goes active NSUP SMK LEV the smoke level in no supervisory mode This level refers at the SMOKE value mod Range 80 150 Beyond this value the alarm goes ac...

Page 40: ...3 2 Point menu After the user has entered the Point menu select the item remove Select Back to return to the Main menu Select Esc to return to the Main menu and to go out completely Main menu POINT SE...

Page 41: ...ith Sel Type in Canc to return to the Point menu 7 3 5 Point address selection Should the user select to remove a single point type in the point address to remove Through the numerical keyboard it is...

Page 42: ...value of the zone in the Point setting menu see the chapter 7 2 5 8 3 ZONE SETTING 8 3 1 Main menu After the user has entered the Main menu select ZONE and confirm with the key Sel to pass to Zone me...

Page 43: ...after deleting of a point the assigned zone at double consent has only one installed point this parameter value will read No mod YES or NO DELAYED OUTPUT it is used when the control panel is supervis...

Page 44: ...value the alarm go active mod Range 40 70 SUP SMOK LEV if set up all the multi criteria smoke detectors acquire the smoke level in supervisory mode on this reported value This level refers at the SMOK...

Page 45: ...on with Sel 9 1 3 Output selection Inside the output menu there are two typologies 1 CONTROL PANEL OUTPUT 2 LOOP OUTPUT Use the four arrows to set oneself on the line which shows the type of selection...

Page 46: ...ssible to set some formulas for this modality OR OR OR AND AND AND ZONE REPETITION the output is activated if a zone of a loop goes to fire alarm FORMULA no available SILENT MODE it sets up the possib...

Page 47: ...ivated when all the zones have all the devices in fire alarm The possibility to do activate an output through a formula it is not available now Output setting OUTPUT ADDRESS 001 1 TYPE LOOP OUTPUT DEV...

Page 48: ...d that can be programmed NO NC out9 Clips OC4 open collector No 4 programmable for typology of alarm and zone out8 Clips OC3 open collector No 3 programmable for typology of alarm and zone out7 Clips...

Page 49: ...put is normally of supervisory type but it is possible to change the set up mode through the software CONFIG and the hardware through the bridge SEL1 see the picture in the chapter 9 2 1 CONFIG set up...

Page 50: ...ive load and that is to deactivate at the click of the relay example electromagnets Loads to activate at the click of the relay example sirens or optic panels For circuit examples see chapter PART 15...

Page 51: ...s inferior to ten seconds 9 4 2 Logic of activation There are 3 exit groups defined by their activation purpose 1 Outputs activated on fire alarm status 2 Outputs activated on zone repeater 3 Outputs...

Page 52: ...tivated which can be Zeroed by pressing the 2 manual button or by the general deleting command of delays on the control panel from the evacuation menu 2 5 2 2 If the manual button 1 is pressed the ala...

Page 53: ...re alarm given by the double consent is not enabled the user must pass to the alarm signal directly To have the pre alarm in the zones enabled to this property it will be necessary to be in supervised...

Page 54: ...restoration procedures NORMAL the control panel only restores the points which are no longer under alarm The fire alarm is restored only when all the armed points have been reset before the actual res...

Page 55: ...lay It is possible to customize the two initial messages which appear on the display Once the menu is entered go to Prompt modification and select the line you wish to modify and press the Mod button...

Page 56: ...serial cable connection interface Procedure 1 Connect through the RS232 RS485 cable the output of COM1 or COM2 see chapter 2 5 to a serial port COM of the PC 2 Launch a common platform program for the...

Page 57: ...ir original function in the Restore Fault situation it is not necessary to wait for the Loop re start 10 9RESTORING DEFAULT SETTINGS This procedure allows to reset the control panel s default settings...

Page 58: ...TWARE VERSION Inside the SW Version menu you find the micro processor versions for the control panel and loops uP CPU SW VER version of microprocessor of the control panel no mod uL CPU SW VER version...

Page 59: ...l 11 4LAMP TEST This function allows to verify the status of all led and the display of the control panel By selecting the voice lamp test from the Diagnostic menu the control panel will light up for...

Page 60: ...amme which once initiated downloads all the events including the ones previously eliminated with function remove CAUTION once the chronological reset is confirmed the Control Panel will re start with...

Page 61: ...ter 0 12 2EXTERNAL PS2 KEYPAD Within the Connection menu select the voice keyboard to enable the keyboard Once the correct password is inserted the control panel will confirm the external enabling fun...

Page 62: ...the modified power source NOTE even if the external power source is activated the control panel will signal the power loss of the primary source through a flashing led which corresponds to Power suppl...

Page 63: ...nnection Another connection can be the LAN net Ethernet for the connection of 64 control panels in net at a PC master disposal The connection takes place through MOXA TCP IP converter module which tur...

Page 64: ...Page 64 of 91 Rev 4 20 MOXA DE 211 module...

Page 65: ...evacuation are activated and a red led lights up evacuation is lit and signalled 3 EXTINGUISH following a pre set delay given from the initial settings of the evacuation procedure the evacuation proc...

Page 66: ...EVACUATION START manual start up of the evacuation procedure this voice is present if the manual start up function has been enabled DELAYS TO ZERO deleting of the pre set delays on the siren outputs...

Page 67: ...The control panel s outputs and loops I O modules can be programmed as evacuation or extinguish outputs see chapter 9 1 4 In this manner it is possible to command a extinguishing control unit or sign...

Page 68: ...panel setting For the repeater setting it is enough to install the RS232 serial port inside the control panel in the first connector on the left The control panel needs not be set being already progr...

Page 69: ...Negative output for outside door repeater 3 R 4 SCR 5 LOOP 6 LOOP 15 1 1 Detector addressing For the addressing it is necessary to use a magnet near the reed For the procedures refer to the manual of...

Page 70: ...of a point the assigned zone at single consent has only one installed point this parameter value will read No mod YES or NO SERIAL NUM the serial number of the detector no mod SW VERSION the software...

Page 71: ...alarm too The possibility to modify this function is given provided that there are at least 2 points on the specific zone If after deleting of a point the assigned zone at double consent has only one...

Page 72: ...the zone must be at single consent SERIAL NUM the serial number of the detector no mod SW VERSION the software version of the detector it is changed through PC SUP SMOK LEV the smoke level in supervi...

Page 73: ...s necessary to use a CMOS interface with a low current supply to control a relay The input and output can be programmed with different types of meaning Example Alarm fire technological 15 2 2 Button a...

Page 74: ...ead No and the zone must be at single consent The manual the button which gives an alarm signal that is not influenced from these setting mod YES or NO SERIAL NUM the serial number of the button no mo...

Page 75: ...he output setting see chapter PART 9 ADDRESS the point and loop addresses no mod ZONE the zone address of the point loop mod range value 1 63 NAME the name of the point mod TYPE point type no mod SECT...

Page 76: ...NO S RELAY LED JUM PER 27Kohm LOOP CONNECTION OUTPUT MODULE L L L L C NC S L L L L C NC S L L L L C NC NO S RELAY LED JU MPER 27K ohm POWER SUPPLY 24V LAMP ELECTROMAGNET MAX 1A on relay 15 3 6 Connec...

Page 77: ...nput the output module is rendered un accessible through its programming and becomes active whenever the module reveals an input alarm signal JUMPER RESTORATIONBUTTON 27K ohm POWER SUPPLY The bathroom...

Page 78: ...ong a loop B1 B2 AUX FAULT 30Vdc 2 3 1 6 5 4 L L 2 3 1 6 5 4 BUTTON 12 24Vdc Automatic 12 24Vdc Automatic POWER SUPPLY 24V 2A L L L L NO C NC S Rel LED I O MODULE 5 6Kohm RS485 RS232 RS485 SLAVE SLAVE...

Page 79: ...are controlled from a PC master The maximum length with RS485 is 1Km Into the PC must be installed the X Advisor software to manage all the control panels 16 2CONTROL PANEL CONNECTION ON LAN S WIT CH...

Page 80: ...ONTROL PANEL We remember that if the control panel has a 24Vdc output it is limited in current The user must use an external power supply B1 B2 AUX FAULT 30Vdc ELECTROMAGNET 1B 1B SHI 1A 1A 2B 2B SHI...

Page 81: ...CTION POINTS L L S out In L L S R E E D BUT T ON L L L NO C NC S LE D I O MODULE 24Vdc 2A Power Supply 12 24V 2 3 1 6 5 4 2 3 1 6 5 4 2 3 1 6 5 4 1B 1B S HI 1A 1A 2B 2B S HI 2A 2A 24 24 SHI S S FAULT...

Page 82: ...control panel is turn on restored it puts all loops to out of service 8 LOOP ACTIVATION As final control it is necessary to restart all loops 6 1 9 MENU Push the button relative at the Menu 10 LOOP S...

Page 83: ...re acquired them addresses are from 121 to 127 N STEP BY SETP DESCRIPTION CHAPTER 1 MENU Push the button relative at the Menu 7 1 1 2 POINT Select POINT item 7 1 2 3 insert Select insert item 7 1 3 4...

Page 84: ...NTROL PANEL OUTPUT LOOP OUTPUT Select the item where is the output to programme 9 1 3 5 OUTPUT SELECTION Select the loop if loop output and the output address to programme 6 OUTPUT SETTING Inside at t...

Page 85: ...bol on the second line of description reading Once the alarms have been restored it is possible to set up the reset mode according to the requirements of the user See charter 10 4 where all the differ...

Page 86: ...rs 7 2 5 7 OUT OF SERVICE NO Set up the field command of OUT OF SERVICE at YES 7 2 5 Repeat the same procedure for all the other Points which are in put of service if you want to put them back into se...

Page 87: ...matically to restore the restore of the System Fault it is not necessary to wait for the Loop to re start itself Reset data base Events N STEP DESCRIPTION CHAPTER 1 MENU Press the command in reference...

Page 88: ...CT S C x y L In the loop a short circuit is present between L and L in the section pointed out by the line isolators x and y The fault message points out the loop L 1 4 and the section where the short...

Page 89: ...equires a careful cleaning of its chamber It is necessary to disassemble it take it off the line and then re insert into the loop The external power supply fuse is faulty Check the fuse of the externa...

Page 90: ...ors buttons input output modules and isolators Maximum points number for loop 120 between detectors buttons and modules 7 addressable isolators 100 passive isolators Point types Into the loop it is po...

Page 91: ...ren output fuse F 315mA 250V fast Aux relay 2 programmable relay no supervised exits not directly in power in circuit contact C NO NC contacts max 1A 40Vac dc 24V output Maximum power output 28 5Vdc m...

Reviews: