Page 25 of 91
Rev. 4.20
ü
out of service;
ü
active outputs;
ü
pre-alarm (minimum priority).
All and any event which the Control Panel reveals, are automatically saved on the event list (see chapter
4.6).
The exclamation mark (
!
) or interrogation mark (
?
) indicate that the origin of the message has not been restored
yet and that the reset or restore function through the
RESET
button, will not have any effect. The difference
between the two marks lies in the priority state of verification by the Control Panel; (
!
) continuous control, but this
symbol (
?
) stands for periodical control.
The absence of (
!
) or (
?
) indicates that the origin of the event has been restored and the message can be
removed with the
RESET
button.
When the fire alarm is triggered, the Control Panel visualizes the areas in
alarm (not the points or other elements).
Menu
:
access to the Control Panel menu;
View
:
details of selected visualized message;
Ala.
:
allows access to other types of messages (fault, out of service, ...);
Poi.
:
visualize points of the selected area which have gone into alarm.
When the evacuation procedure is enabled, status check and related
extinguishing procedure.
Menu
:
access to the control panel menu;
View
:
details of selected visualized message;
Ala
.
:
allows access to other types of messages (fault, out of service, ...).
When the fault is identified, the control panel shows the associated list of
events.
Menu
:
access to the control panel menu;
View
:
details of selected visualized message;
Ala
.
:
allows access to other types of messages (fault, out of service, ...).
When the service alarm is triggered, the control panel shows the associated
“armed” points.
Menu
:
access to the control panel menu;
View
:
details of selected visualized message;
Ala
.
:
allows access to other types of messages (fault, out of service, ...).
FIRE ALARM: 002
001 ZONE ALARM 01-1
!OFFICE 1
002 ZONE ALARM 02-1
!OFFICE 2
Menu View Ala. Poi.
EVACUATION: 002
001 17/03/05 12:34:58
!MANUAL EVACUATION
002 17/03/05 12:35:48
!EXTINCTION ACTIVATED
Menu View Ala.
FAULT: 002
001 17/03/05 12:34:58
?OUT.INTERRUPTION 002
002 17/03/05 12:35:48
!TRADIT.LINE FA 003-1
Menu View Ala.
TECHNOLOG.ALARM: 002
001 17/03/05 12:34:58
!LOW TECHN. INP 001-2
002 17/03/05 12:35:48
!BATH TECH. INP 003-1
Menu View Ala.