Page 44 of 91
Rev. 4.20
temperature level in no supervisory mode on this
reported value. Beyond this value, the alarm go active
(mod. Range:
40°-70°
).
NSUP.TEMP LEV
:
if set up, all the multi-criteria heat detectors acquire the
temperature level in no supervisory mode on this
reported value. Beyond this value, the alarm go active
(mod. Range:
40°-70°
).
SUP.SMOK LEV
:
if set up, all the multi-criteria smoke detectors acquire
the smoke level in supervisory mode on this reported
value. This level refers at the
SMOKE
value (mod.
Range:
80-150
). Beyond this value, the alarm goes
active.
NSUP.SMK LEV
:
if set up, all the multi-criteria smoke detectors acquire
the smoke level in no supervisory mode on this
reported value. This level refers at the
SMOKE
value
(mod. Range:
80-150
). Beyond this value, the alarm
goes active.