Output setting
•OUTPUT ADDRESS: 002
TYPE: SIREN
DEVICE: SUPERV.RELAY
OUT OF SERVICE: NO
FAULT: NO
STATUS: DISABLED
TEST RUN: NO
ACTIV. DELAY s: -
MAN.ALARM ACTIV:
NO
OUT ACTI.TIME s: -
INVERT: NO
Esc. Pre. Next Mod.
Output setting
•OUTPUT ADDRESS: 001
TYPE: 24 Vdc
DEVICE: PWR SUPPLY.
OUT OF SERVICE: NO
FAULT: NO
Esc. Pre. Next Mod.
9.2 CONTROL PANEL OUTPUT
9.2.1 Output description
Selecting “
CONTROL PANEL OUTPUT
” the outputs inside the control panel will be able to be programmed as
follows:
Ø
(out5) Clips RL1 (SEL4): relay 1 is a clean relay no supervised that can be programmed NO/NC;
Ø
(out4) Clips RL2 (SEL3): relay 1 is a clean relay no supervised that can be programmed NO/NC;
Ø
(out9) Clips OC4: open collector No 4 programmable for typology of alarm and zone;
Ø
(out8) Clips OC3: open collector No 3 programmable for typology of alarm and zone;
Ø
(out7) Clips OC2: open collector No 2 programmable for typology of alarm and zone;
Ø
(out6) Clips OC1: open collector No 1 programmable for typology of alarm and zone;
Ø
(out3) Clips FAULT (SEL1,2): supervised output of fault;
Ø
(out2) Clips –S +S: supervised siren;
Ø
(out1) Clips +24 –24: auxiliary power supply 24Vdc.
5 4 9 8 7 6 3 2 1
OUTPUTS ADDRESS
-2
4
+
24
S
H
I
+
S
-S
- +
FAULT
S
H
I
O
C
1
O
C
2
O
C
3
O
C
4
RL2
RL1
SEL4
SEL3
SEL1
SEL2
9.2.2 24Vdc output
It is a power supply output of 24Vdc.
For the information about the menu items, to see the chapter
9.1.4.
9.2.3 Siren output
It is a output of supervisory type siren.
For the information about the menu items, to see the chapter
9.1.4.