Page 52 of 91
Rev. 4.20
2.4 If the control panel is not under supervised mode the output becomes active under forced delay 0 value.
2.5 If the conditions 2.2.,.2.4 are not running or “false” the following guidelines apply:
If the output is inactive the “manual alarm delay option to zero” is activated with a pre-defined delay which
cannot be “Zeroed”.
2.5.2
If for the output there is the active option “manual alarm delay at zero”:
2.5.2.1
If the <=1 manual buttons are pressed for the alarm output the pre-defined delay is
activated, which can be “Zeroed” by pressing the >=2 manual button or by the general
deleting command of delays on the control panel (from the evacuation menu).
2.5.2.2 If the manual button > =1 is pressed the alarm output is activated with forced “0” delay.
GROUP 3
For the group 3 outputs the following conditions apply:
3.1 The control panel must be in the state expected for the functions for it to be activated.
3.2 The output occurs with preset delay but it cannot be in any way forced to “0” value.
Note:
ü
An output can only be activated either on a fire alarm state or on a different status which occurs
simultaneously.
ü
Hence, depending on the state of the control panel, the output can be considered under the group 1 or
group 3.