Page 71 of 91
Rev. 4.20
15.1.4
Heat detector
The heat rate-of rise detector has been designed to activate itself when the heat exceeds a previously fixed level
or when the speed with which this increment is produced is high, even though the scheduled level has not been
exceeded.
ADDRESS
:
the point and loop addresses (no mod.).
ZONE
:
the zone address of the point loop (mod., range value
1-63
).
NAME
:
the name of the point (mod.).
TYPE
:
point type (no mod.).
SECTION
:
the section where the point is (no mod.).
O.OF SERVICE
:
it indicates if the point is in out of service (mod.
YES
or
NO
).
FAULT
:
it indicates if the point is fault (no mod.).
LED ON
:
if
YES
the leds flash (mod.
YES
or
NO
).
INPUT
:
the input is activeable like only
TECHNOLOGICAL
type
(mod.).
SING.CONSEN.
:
it is used when the control panel is supervisory mode
and the zone of the point is enabled the "double
consent". If
YES
, when the detector go to alarm status,
the control panel go to fire alarm too. The possibility to
modify this function is given provided that there are at
least 2 points on the specific zone. If after deleting of a
point, the assigned zone at double consent has only
one installed point, this parameter value will read
No
(mod.
YES
or
NO
).
SERIAL NUM
:
the serial number of the detector (no mod.).
SW VERSION
:
the software version of the detector (it is changed
through PC).
RATE-OF-RISE
:
if value is
YES
, the heat detector has rate-of-rise
function too (no mod.).
SUP.TEMP LEV
:
the temperature level in supervisory mode. This level
refers at the
TEMP.
value (mod. Range:
40-70
).
Beyond this value, the alarm goes active.
NSUP.TEMP LEV
:
the smoke level in no supervisory mode. This level
refers at the
TEMP.
value (mod. Range:
40-70
).
Beyond this value, the alarm goes active.
TEMP. °C
:
it indicates the temperature measure from the detector
(no mod.).
Point setting
•ADDRESS: 001-1
ZONE: 01
NAME: ROOM1
TYPE: HEAT DETECTOR
SECTION: A-B
OUT OF SERVICE: NO
FAULT: NO
LED ON: NO
INPUT: DISABLED
SINGLE CONSENSE: NO
SERIAL NUM:002-00001
SW VERSION: 2.00
RATE-OF-RISE: NO
SUPERV.TEMP LEV: 058
NSUPER.TEMP LEV: 056
TEMP. °C: 25.32
Esc. Pre. Next Mod.