Page 75 of 91
Rev. 4.20
15.3.1
Input and output description
INPUT
: The input is of the type of balanced resistance of the 27K• value. The input signal is given opening the
circuit between the two clips and the resistance; but, if it is short circuited, a fault in the input line is indicated. The
maximum length of the input line is 8m.
OUTPUT
: The output is made by a relay at clean contact from 1A with the clips C, NO and NC.
The input and output can be programmed with different types of meaning (Example: Alarm fire, technological...).
15.3.2
Module addressing
For the addressing you must act on the button of the device. For the procedures, refer to the manual of the
Control Panel.
15.3.3
Manual zero setting of the address
Normally the factory address is to 0 (zero). If you have the necessity to take the address to value zero manually,
you must give the module a tension of 24V (L- and L+ near the jumper) and, after about ten seconds, press the
button and wait that the led makes a longer flash.
15.3.4
Point setting
In the “
Point setting
” menu (submenu of “
POINT
” item) there are different parameters for this detector. For
the output setting, see chapter
PART 9).
ADDRESS
:
the point and loop addresses (no mod.).
ZONE
:
the zone address of the point loop (mod., range value
1-63
).
NAME
:
the name of the point (mod.).
TYPE
:
point type (no mod.).
SECTION
:
the section where the point is (no mod.).
O.OF SERVICE
:
it indicates if the point is in out of service (mod.
YES
or
NO
).
FAULT
:
it indicates if the point is fault (no mod.).
LED ON
:
if
YES
the led flash (mod.
YES
or
NO
).
INPUT
:
the input is activeable like:
TECHNOLOGICAL
,
FIRE
ALARM
and
BATH
; (mod.).
SING.CONSEN.
:
it is used when the control panel is supervisory mode
and the zone of the point is enabled the "double
consent". If
YES
, when the module go to alarm status,
the control panel go to fire alarm too. The possibility to
modify this function is given provided that there are at
least 2 points on the specific zone. If after deleting of a
point, the assigned zone at double consent has only
one installed point, this parameter value will read
No
and the zone must be at single consent (mod.
YES
or
NO
).
SERIAL NUM
:
the serial number of the module (no mod.).
SW VERSION
:
the software version of the module (it is changed
through PC).
Point setting
•ADDRESS: 001-1
ZONE: 01
NAME: ROOM1
TYPE: I/O MODULE
SECTION: A-B
OUT OF SERVICE: NO
FAULT: NO
LED ON: NO
INPUT: DISABLED
SINGLE CONSENSE: NO
SERIAL NUM:002-00001
SW VERSION: 2.00
Esc. Pre. Next Mod.