Page 91 of 91
Rev. 4.20
OUTPUTS
Alarm siren output:
Open circuit and short circuit check device;
resistance at end of power line: 5,6K• 1/4W;
maximum power output: 28.5Vdc 315mA.
Alarm siren output fuse:
F 315mA L 250V (fast).
Fault siren output:
Open circuit and short circuit check device;
resistance at end of power line: 5.6K• 1/4W;
maximum power output: 28.5Vdc 315mA.
Fault siren output fuse:
F 315mA 250V (fast).
Aux. relay:
2 programmable relay no supervised exits not directly in power in circuit (contact
C/NO/NC);
contacts: max. 1A, 40Vac/dc.
24V output:
Maximum power output: 28.5Vdc max 315mA.
24V output fuse:
F 315mA 250V.
Open collector output:
4 open collector outputs;
max. 27mA;
resistance in series of 1K•.
IN COMPLIANCE WITH THE FOLLOWING STANDARDS:
EN 54-2, EN 54-4 (Directive 89/106/EEC): Certificate: 1293-CPD-0221:2011
EN 55022, EN50130-4 (Directive EMC 2004/108/EC)
EN 61000-3-2, EN 61000-3-3 (Directive EMC 2004/108/EC)
EN60950-1 (Directive LVD 2006/95/EC)