3.3 Interface
P
ort
-16 -
CN2 (PC interface)
D-sub 9-pin female
(#4-40 inch
screw
)
Pin No. Signal type Signal name
Description
2-3
“Closes” on
action
Input power
supply error
signal
(See Note 1)
This is a no-voltage contact signal that is
output when a voltage error occurs in the
input power supply due to power supply
interruption, etc. (If the power failure lasts
up to 1.5 seconds, there is no operation.)
1-3
“Closes” on
action
Low battery
voltage signal
(See Note 1)
No-voltage contact signal that is output
about 2 minutes (during rated load)
before termination of battery discharge
during battery running.
8-7
AC output
stops upon
receipt of
“H” signal
UPS
automatic
shutdown
signal
(See Note 2)
Signal input to the Product for stopping
AC output from the Product.
(1)
AC output may be stopped only during
battery running.
(2)
This signal (5 to 25 V DC) should be
input for 0.6 second or longer.
6-7
Serial data
input (RX)
9-7
Serial data
output (TX)
7
RS-232C
serial signal
(See Note 3)
Signal ground
(SG)
<Communication method>
Baud rate:
2400 bps
8 bits
1 bit
Data length:
Stop bit:
Parity:
non
Character type: ASCII type
Note 1: See the graph on the previous page for contact capacity.
When using the UPS monitoring function (using the above contact signal) pre
installed in the following OS, contact your maintenance staff, since the dedicated
cable for contact signal which corresponds to each OS is needed separately. For
more detail on the UPS monitoring function pre installed in each OS, refer to an
instructions manual, an on-line manual, etc. of each OS.
Windows NT/2000/XP: FiFH/WS9 (dedicated contact signal cable)
Note 2: Windows 2000 and XP permit shutdown of the OS on occurrence of
interruption of power supply, and UPS automatic shutdown thereafter is not feasible.
Note 3: Dedicated RS-232C communication cable is required elsewhere for
execution of RS-232C serial communication. Please contact the in-charge
maintenance staff.
FiFA/WS9 (dedicated RS-232C communication cable)