4.1 Turning on the UPS
- 18 -
3. AC voltage is output from the output terminal block.
The RUN LED (green) on the front of the UPS lights up.
The BATTERY CONDITION LED (green) on the front of the UPS
indicates the battery charge level by the lighting type.
4. Battery check is executed automatically.
The [BATTERY ALARM] LED (orange) on the front of the UPS flashes
slowly (in 1.6
second period).
5. If no error was found in batteries during battery check for 5 seconds,
and [BATTERY CAPACITY] LED on the front face of the Product shows
the extent of battery charge (green) again, and return to the normal
running status arises.
If the normal running does not start, refer to Chapter 7 "Troubleshooting”.
Turning on the connected device
6. Upon normal start-up of normal running, turn ON the power for the
connected device.
Type: M-UPS***ADS
Status: Running
Input: ***.*:V **.*Hz
Output: ***.*:V **.*Hz
[RUN] LED (green) lit
Indication of the extent of battery
charge (green)
Battery Checking
Lit: 80 to 100%
Flashing
:
50 to 80%
Out
:
0 to 50%