IMPORTANT
Do not install and store the UPS in the following places:
Outdoor location
Exposed to the wind and rain
Extremely humid and dusty
With corrosive gas or salt
Direct sunlight
Near sparks or heating element
Extremely hot or cold, where the temperature fluctuates greatly
With vibration and shock
Do not perform the battery check in succession.
When the battery check is performed, the internal battery actually
discharges to check the voltage.
Consecutive battery checks may cause battery degradation and shorten
the battery replacement cycle.
If the UPS is not used for a long time, charge the battery every two
months.
Charge the battery by operating the UPS for 12 hours or more
every two months
. A
fter charging the battery, perform the battery check.
If the UPS is not used for a long period of time, the battery may become
over-discharged due to self-discharge, rendering the UPS unusable.
Disposal of used battery has legal restrictions
Please follow any local, county, regional or state guidelines for the disposal
of batteries.
Do not block the vent hole and cooling fan, Do not use UPS where the
air is not well ventilated.
The UPS is equipped with vents and cooling fans to cool the inside of the
UPS; the internal and ambient temperatures of the UPS may deviate from
the rated specifications.
Replace the cooling fan periodically.
Continued use after the fan has reached the end of its service life may
cause the internal temperature of the UPS to exceed its rating.