8.1 Rated Specification
Type
M-UPS050AD1S
M-UPS050AD2S
Rated capacity
5000 VA / 4000 W
Voltage
100 V 2%
200 V 2%
Frequency
50 Hz or 60 Hz (automatic switching in UPS)
During normal operation
Various by input frequency
Frequency accuracy
During backup
0.1% or better
Number of phases
Single phase, 2-wire system (with grounding terminal)
Load condition
Linear load or rectifying load of peak-to-rms ratio up to 3
Voltage waveform
distortion factor
At load resistance: 4% or less
At rectified load: 6% or less
Overcurrent
protection
RMS value: 100% or greater
Peak value: 300% or greater of rated RMS value
(Shall withstand the load of crest factor = 3.)
Grounding method Non-grounded or neutral grounded
AC
output
Commercial
electric power
switching method
Thyristor switching (switching time: uninterruptible)
Switching cannot be performed when the power is off.
Voltage
100 V 15%
200 V 15%
Frequency
50 Hz or 60 Hz 5%
Number of phases
Single phase, 2-wire system (with grounding terminal)
Capacity
5000 VA or less
Grounding method Single-line grounding
Power factor
0.97 or greater (during rated running)
AC input
Input higher
harmonics current
Conforms to IEC61000-3-12.
Type
Compact control valve lead-acid battery (long-life battery)
Backup time *1
[initial value]
About 10 minutes
[4000 W]
Storage
battery
Nominal voltage
216 V
Ambient temperature 0 to 40 C
Relative humidity
20 to 95% (no condensation)
Noise
50 dB (A) or less (at 1 m from the front of the UPS)
Others
Cooling method
Forced air cooling
External dimensions (W D H) 350 700 675 mm
Mass
180 kg (without batteries: 125 kg)
Applicable standard
Complies with VCCI CLASS A, UL1778-4th, IEC62040
Input
Input/output terminal block (L/R, N/S: M6 screw)
Grounding terminal Input/output terminal block (PE (G): M6 screw)
External
connection Output
Input/output terminal block
(l1/U1, l3/V1: M6 screw)
Input/output terminal block
(l1/U2, l2/V2: M6 screw)