- 57 -
Table 2. M-UPSXXXAD1S/2S-W(provided UL489 breaker) Input ratings,
wire size and torque
INPUT & GROUND
MODEL
Vin
(V)
Iin
(A)
WIRE SIZE
AWG
Type of
Closed-loop
Terminal
TIGHTENING
TORQUE
(N m)
100
M-UPS050AD1S-W
M-UPS050AD2S-W
200
50
4
R22-6
4.1
100
M-UPS075AD1S-W
M-UPS075AD2S-W
200
75
2
R38-6
9.8
100
M-UPS100AD1S-W
M-UPS100AD2S-W
200
100
1/0
R60-8
9.8
Table 3. Output ratings, wire size, torque, external output breaker size
INPUT & GROUND
2 POLE
BREAKER
MODEL
Vout
(V)
Iout
(A)
WIRE
SIZE
AWG
Type of
Closed-loop
Terminal
TIGHTENING
TORQUE
(N m)
V
A
M-UPS050AD1S-U
100
50
4
R22-6
70
M-UPS050AD2S-U
200
25
8
R8-6
4.1
240 AC
35
M-UPS075AD1S-U
100
75
2
R38-8
100
M-UPS075AD2S-U
200
37.5
6
R14-8
9.8
240 AC
50
M-UPS100AD1S-U
100
100
1/0
R60-8
125
M-UPS100AD2S-U
200
50
4
R22-8
9.8
240 AC
70
Figure 1. Diagram of All Models
Dual
Converter
Boost
Chopper
L
N
PE(G)
S1
S2
AC Input/Output
terminal Block
AC Input/
Outpminal Block
l1
l2
l1-l3 : AC100V
l1-l2 : AC200V
Relay : Only 5kVA mount
External Battery Box
FG
l1
l3
8.2 Additional Description for UL Type