background image

  

 

5.3    Inspecting the Battery (Battery Check) 

 

27

 

3. 

As a result of the battery check, the UPS will be in the following state. 

 

If the battery is fully charged:

 

 

The  RUN  LED  (green)  on  the  front  of  the  UPS  lights  up, and  the  UPS 
returns to the normal operation. 

 

 

If the battery is not fully charged:

 

 

A warning beep sounds and the BATTERY CONDITION LED (orange) 
on the front of the UPS blinks. 
Proceed to Procedure 4.

 

 

The RUN LED

green

lights up.

 

The BATTERY   
CONDITION LED (orange) 
blinks.

 

Pip-pip- 
pip-pip

・・・

 

(continuous 
sound)

 

Summary of Contents for M-UPS050AD1B

Page 1: ...Fuji Electric Co Ltd USER S MANUAL Uninterruptible Power Supply GX 100 Series 5kVA Model M UPS050AD1C M UPS050AD1B INR HG5411...

Page 2: ...equired safety is not maintained such as atomic nuclear command aircraft flight control air traffic control mass transport control life supporting system and weapon control etc Do not use this product...

Page 3: ......

Page 4: ...box are described 2 Overview The name of each part and the operation mode of the UPS are described 3 Installation Installation of the UPS and connection of the cable are described 4 Running The method...

Page 5: ...ectly Caution indicates that slight or moderate injury may result or that the UPS or user s property may be damaged if the UPS is not used correctly Important Important indicates precautions for use o...

Page 6: ...maintenance other than daily inspection such as the replacement of battery or cooling fan must be performed by the specialist engineer There is the fear of an electric shock Connect a grounding wire t...

Page 7: ...an accident such as an overturn or a drop will not occur The mass of the UPS is as follows M UPS050AD1C 84kg without batteries 48kg M UPS050AD1B 78kg without batteries 42kg This UPS can be also insta...

Page 8: ...ut voltage cannot be changed Replace the battery periodically If continuing to use the battery that reached the end of battery life there is the fear of the leak of battery and a smoke For the replace...

Page 9: ...y every two months Charge the battery by operating the UPS 12 hours or more every two months and after charging the battery perform the battery check If leaving the UPS unused for a long time the batt...

Page 10: ...plying the voltage that exceeds the rated voltage range of the connection device the connection device may be damaged Do not apply the single line grounding at the output side It is not insulated betw...

Page 11: ...rmining an installation location Determining the installation method Installation method 3 2 Connecting the Cable 10 Caution about connecting the cable Preparation before connecting the cable Connecti...

Page 12: ...peration Mode List 30 Types of blink of LED Types of the warning beep Operation mode list 7 Maintenance 7 1 Replacing the Battery 35 Timing of the battery replacement The method of battery replacement...

Page 13: ...C 84kg without batteries 48kg M UPS050AD1B 78kg without batteries 42kg 1 Open the packing box and take out the UPS Confirming the contents of the packing 2 Confirm that there is no damage to the appea...

Page 14: ...2 2 Overview 2 1 Name and Main Function of Each Part This chapter describes the name and main function of each part of the UPS 1 2 3 4 5 6 7 8 9 10 11 14 13 12 15 16 18 17...

Page 15: ...witch for approximately 3 seconds after restoring the failure the ALARM LED goes out 8 BATT CHECK It is the switch for performing the battery check manually By pressing the switch for approximately 2...

Page 16: ...operation In the event of an input power failure When the voltage or the frequency of an AC input power source is abnormal the UPS starts the electric discharge from the battery and continues to supp...

Page 17: ...ithout instantaneous interruption It is also the same as when switching to the bypass operation manually with the switch on the front of the UPS At the bypass operation electric power is not supplied...

Page 18: ...sparks or heating element An extremely hot or cold place or place where the temperature fluctuates greatly A place where vibration and a shock are added Do not use the UPS in a residential area or it...

Page 19: ...quired in the front and rear of the UPS Confirm the environment of the installation location The recommended environment in consideration of the battery life etc is as follows Item Recommended environ...

Page 20: ...installing laying the UPS down tilt it only to the right side seeing from the front Never tilt the UPS to the left side Fire Damage There is fear of a fire or the UPS failure owing to a leak of batte...

Page 21: ...an accident such as an overturn or a drop The weight of the UPS is as follows M UPS050AD1C 84kg without battery 48kg M UPS050AD1B 78kg without battery 42kg When using the bracket standard attachment...

Page 22: ...ltage more than 5kV peak UC is 2kV peak is applied the filter circuit of the input part may be damaged The input voltage of the UPS is 85 to 138 VAC When input voltage is different from the rated spec...

Page 23: ...age zero cross condition Zero cross must not occur twice or more in 1 cycle 1 Confirm the input power supply The input power supply which can connect with this UPS is as follows UPS model Breaker capa...

Page 24: ...grounding side l U AC output un grounding side n V AC output grounding side Input and output terminal block PE G Ground protective grounding 5 pole screw terminal M6 Input power supply and output sys...

Page 25: ...t is the no voltage contact signal which is outputted when the abnormalities such as the power failure occur at an input power supply In the power failure for 1 5 seconds or less it does not operate 3...

Page 26: ...s or more 6 7 Serial data input RX 9 7 Serial data output TX 7 RS 232C serial signal 3 Signal ground SG Communication system Baud rate 2400 bps Data length 8 bits Stop bit 1 bit Parity non Character t...

Page 27: ...procedures of the rated output voltage 1 Turn off the connection device 2 Press the RUN STOP switch on the front of the UPS for approximately 1 second The buzzer will sound if the switch is received...

Page 28: ...ximately 1 second The buzzer will sound if the switch is received 8 AC voltage set up is outputted from the output terminal block The RUN LED green on the front of the UPS lights up 9 Turn on the conn...

Page 29: ...s fear of damaging the connection device Confirming cable connection 1 Confirm that the UPS is connected to an input power supply and the connection device Turn on the input breaker on the back of the...

Page 30: ...output terminal block The RUN LED green on the front of the UPS lights up The BATTERY CONDITION LED green on the front of the UPS indicates the amount of battery charge according to the sort of lighti...

Page 31: ...ck is performed for approximately 5 seconds Then if the battery is normal the BATTERY CONDITION LED green on the front of the UPS indicates the amount of battery charge again and the UPS returns to th...

Page 32: ...the distribution board is turned off or the input breaker on the back of the UPS is turned off without turning off the UPS the internal battery will be discharged since it will be in the same state as...

Page 33: ...output stops The RUN LED green on the front of the UPS blinks slowly in the cycles of approximately 1 6 sec If an output does not stop normally Refer to Chapter 6 Troubleshooting 4 Turn off the input...

Page 34: ...d cut off connection with AC input terminal R S There is fear of an electric shock Only maintenance personnel must perform the maintenance other than daily inspection such as the replacement of batter...

Page 35: ...he vent hole and the cooling fan When the dust is adhering Refer to How to care for the UPS Confirm that the surface of UPS and the electric cables are not heating unusually When they are heating Conf...

Page 36: ...the rolling blackouts are performed without turning off the UPS the UPS will be in the same state as an ordinary power failure Electric power is supplied to the connection device from the internal bat...

Page 37: ...rmalities in a battery When performing the battery check other than the automatic check Important Do not perform the battery check in succession When the battery check is performed the internal batter...

Page 38: ...A buzzer sounds and the BATTERY CONDITION LED orange blinks in the cycles of approximately 1 6 sec A buzzer sounds again approximately 5 seconds later and the battery check is completed Press the BATT...

Page 39: ...d The RUN LED green on the front of the UPS lights up and the UPS returns to the normal operation If the battery is not fully charged A warning beep sounds and the BATTERY CONDITION LED orange on the...

Page 40: ...ont of the UPS goes out and is switched to the indication green of the amount of battery charge Remarks In this state even if a power failure occurs the battery operation may not be performed 5 Return...

Page 41: ...y 1 second Note However if a warning beep does not stop even if pressing the RESET switch stop a warning beep by the following procedures For details refer to Chapter 4 2 Turning off the UPS 1 Turn of...

Page 42: ...blink in the cycles of approximately 0 4 sec OFF Approximately 0 4 sec ON b Slow blink in the cycles of approximately 1 6 sec OFF ON Approximately 1 6 sec Types of the warning beep The symbols corres...

Page 43: ...Normal operation The UPS is operating normally 2 Stopping without an input power supply The output of the UPS is stopping If an input power supply returns the UPS will become the stopping No 3 If the...

Page 44: ...the UPS will become the failure state of No 4 6 b Slow blink Manual bypass operation The UPS has been switched to the bypass operation manually In this state even if an input power failure occurs the...

Page 45: ...ce from the battery It is not necessary to deal with it especially If an input power supply returns the UPS will return to the normal operation No 1 automatically 12 Lighting Indication of the amount...

Page 46: ...sing the RESET switch 1 second or more the alarm warning beep of the end of battery life will be issued again at the automatic battery check which is performed every two weeks 16 b Slow blink a Fast b...

Page 47: ...en the backup time of the battery has been lowered to 3 minutes or less at the rated load Battery life is influenced greatly by ambient temperature and the conditions of connection device If using the...

Page 48: ...ut turning off the UPS and connection device Note For details consult with an agent from which you purchased the UPS or a maintenance company Note The UPS performs the bypass operation during hot swap...

Page 49: ...battery to prevent a short circuit This UPS uses the small sealed lead storage battery The small sealed lead storage battery uses expensive and rare resources However these precious resources are able...

Page 50: ...ALARM LED orange and the BYPASS LED orange light up after a warning beep sounded for 120 seconds At the second battery replacement at an ambient temperature of 25 degrees C and approx 6th year in cas...

Page 51: ...ails consult with an agent from which you purchased the UPS or a maintenance company Note The hot swap should be performed in a short time The UPS starts the bypass operation if the temperature inside...

Page 52: ...on the back of the UPS Remove all of the connections of input and output terminal For details refer to Chapter 4 2 Turning off the UPS 3 Put the UPS in a box the box etc which was packing the UPS and...

Page 53: ...the load of the crest factor of three Grounding system Un grounding AC output Straightforward bypass circuit Thyristor system changeover time without instantaneous power interruption Changeover is imp...

Page 54: ...standard VCCI CLASS A In conformity with EN62040 UC type Input Terminal block L R N S M6 screws Output Terminal block l U n V M6 screws External connection Ground Terminal block PE G M6 screws 1 Opera...

Page 55: ...readily accessible disconnect device shall be incorporated in the building installation wiring Circuit Breaker UL Listed Inverse time Circuit Breaker is not provided on the UPS at input side as shippe...

Page 56: ...EL Vin V Iin A WIRE SIZE AWG Type of Closed loop Terminal TIGHTENING TORQUE N m V A M UPS050AD1C U M UPS050AD1B U 100 105 110 115 120 50 47 6 45 5 43 5 417 4 R14 6 3 0 AC240 70 Figure 1 Circuit diagra...

Page 57: ...ized servicing personnel who were qualified technically Keep unauthorized personnel away from batteries and cooling fan The UPS has an internal energy source the battery The output may be energized wh...

Page 58: ...s or metal parts on top of batteries e Disconnect charging source prior to connecting or disconnection battery terminals f Determine if battery is inadvertently grounded If inadvertently grounded remo...

Reviews: