5 Inspection
28
Charging the battery
4.
Put out the BATTERY CONDITION LED (orange) by pressing the RESET switch on
the front of the UPS for approximately 3 seconds, and operate the UPS 12 hours or
more to charge the battery.
When pressing the RESET switch, once the BATTERY CONDITION
LED (orange) on the front of the UPS goes out, and is switched to the
indication (green) of the amount of battery charge.
Remarks. In this state, even if a power failure occurs, the battery operation may not
be performed.
5.
Return to Procedure 2, and perform the battery check again manually.
When the UPS will be in the state of Procedure 3
“
If the battery is not
fully charged
”
again:
The battery is out of order (end of battery life). Replace the battery.
For details, refer to Chapter 7.1
“
Replacing the Battery
”
.
Press the RESET switch.