6.2 Operation Mode List
33
LED
No
.
RUN
(green)
AL ARM
(orange)
OVER
LOAD
(orange)
BYPASS
(orange)
BATTERY
CONDITION
(green/
orange)
Warning
beep
Operational
status
Remarks
9
Lighting
(b)
Slow
blink
(1)
Output
overload
during the
bypass
operation
During the bypass operation, the
capacity of the connection device
exceeds the rated value. Reduce the
capacity of the connection device to
less than the rated value of the UPS.
In this state, even if pressing the
bypass switch (pressing the RESET
switch and the BATT CHECK
switch for approximately 3 seconds
simultaneously), the UPS will not
return to the normal operation
(No.1).
10
Lighting
Lighting
Indication of
the amount
of battery
charge
(green)
(1)
Output
overload
during the
battery
operation
During the battery operation, the
capacity of the connection device
exceeds the rated value. Reduce the
capacity of the connection device to
less than the rated value of the UPS.
If this state continues for 100
seconds, the UPS will stop. Evacuate
important connection device from
the UPS.
11
Lighting
Indication of
the amount
of battery
charge
(green)
(2)
Battery
operation
Since the abnormalities occurred at
an input power supply, the UPS
started to supply the electric power
to the connection device from the
battery. It is not necessary to deal
with it especially.
If an input power supply returns, the
UPS will return to the normal
operation (No.1) automatically.
12
Lighting
Indication of
the amount
of battery
charge
(green)
(1)
Battery
voltage drop
due to
continuing
the battery
operation
The battery voltage dropped since
the battery operation has continued.
In the rated load, the battery
operation will be completed
approximately 2 minutes later.
Evacuate important connection
device from the UPS.
If an input power supply returns, the
UPS will return to the normal
operation (No.1) automatically.
13
Lighting
(b)
Slow blink
(orange)
(4)
(at the
manual
check)
Battery
checking
The battery check is performed. At
the manual battery check, a buzzer
sounds at the start and end of the
battery check. After the battery check
is performed for approximately 5
seconds, the UPS will return to the
normal operation (No.1) if there is
no problem.
14
Lighting
(a)
Fast blink
(orange)
(1)
Battery check
error
There is possibility that the battery is
not fully charged. Perform the
battery check manually after
operating the UPS 12 hours or more
to charge the battery. Since an
adequate backup time cannot be
assured, evacuate important
connection device from the UPS.
If the UPS becomes this state again,
the battery is out of order. Since it is
necessary to replace the battery,
contact an agent from which you
purchased the UPS, or a maintenance
company.