6 Troubleshooting
34
LED
No
.
RUN
(green)
AL ARM
(orange)
OVER
LOAD
(orange)
BYPASS
(orange)
BATTERY
CONDITION
(green/
orange)
Warning
beep
Operational
status
Remarks
15
Lighting
Lighting
(orange)
(1)
End of
battery life
The recommendation time of battery
replacement has come. Since it is
necessary to replace the battery,
contact an agent from which you
purchased the UPS, or a maintenance
company. Although the alarm
(indication and warning beep) can be
stopped by pressing the RESET
switch for 3 seconds, the alarm
(warning beep) is issued again 24
hours later or at the restart. When
only the warning beep is stopped by
pressing the RESET switch 1 second
or more, the alarm (warning beep) of
the end of battery life will be issued
again at the automatic battery check
which is performed every two weeks.
16
(b)
Slow
blink
(a)
Fast
blink
(1)
Setting error
of rated
output
voltage
A setup of the switch of voltage
setting on the back of the UPS is
wrong. Use 0 to 4 of the switch of
voltage setting. For details on a
setup, refer to Chapter 3.4
“
Setting
up the Output Voltage
”
.
17
(b)
Slow
blink
(b)
Slow blink
(orange)
-
Waiting for a
restart
The output of the UPS has stopped
by setup of the RS-232C
communication using the connector
for RS-232C on the back of the UPS.
After a time specified at the setup
passes, the UPS will be started up
automatically, and return to the
normal operation (No.1). Also, the
UPS can be started up with the
RUN/STOP switch.