7 Maintenance
36
The method of battery replacement
Electric
shock
Only maintenance personnel must perform the battery
replacement.
There is fear of an electric shock.
Damage
Replace the battery with one specified by our company and a
new one.
If using the un-specified battery or mixing an old battery and a new
battery, it becomes the cause of failure and trouble of the UPS.
Important
The disposal of used battery has legal restrictions.
Commission industrial waste disposal contractor, or consult with an agent from which
you purchased the UPS, or a maintenance company.
The battery of this UPS can be replaced (hot-swap) without turning off the UPS and
connection device (Note). For details, consult with an agent from which you purchased
the UPS, or a maintenance company.
Note) The UPS performs the bypass operation during hot swapping. In the state of
the bypass operation, even if the abnormalities, such as a power failure, occur
at an input power supply, the battery operation cannot be performed.
Use the battery shown in the following list. For the method of purchasing the battery
unit, consult with an agent from which you purchased the UPS, or a maintenance
company.
Battery unit
UPS
model
Arrangement
model
Type of
battery unit
Number of
units (Note)
(per UPS)
Mass
(a unit)
Battery
capacity
M-UPS050
AD1C
M-UPS050
AD1B
Battery for
M-UPS
050AD1B
RRABU-GX14
4 units
Approximately
9kg
12V, 9Ah 3
Note) It is necessary to replace the battery by the unit.