6 Troubleshooting
- 36 -
Operation mode list
Symbols of LED:
···· Lighting
········· Not lighting ········ Blinking
The BATTERY CONDITION LED (green) indicates the amount of battery charge
according to the sort of lighting as follows
:
(Not lighting)········· 0 to 50%
: The battery is not fully charged. Even if a
power failure occurs, the UPS may not be
able to back up.
(Blinking) ·············· 50 to 80% : The battery is charged to some extent,
however, an adequate backup time cannot be
assured.
(Lighting) ·············· 80 to 100% : The battery is fully charged. There is
backup
time at full.
LED
No.
RUN
(green)
AL ARM
(orange)
OVER
LOAD
(orange)
BYPASS
(orange)
BATTERY
CONDITION
(green/
orange)
Warning
beep
Operational
status
Remarks
1
Lighting
Indication
of the
amount of
battery
charge
(green)
-
Normal
operation
The UPS is operating normally.
2
-
Stopping
(without an
input power
supply)
The output of the UPS is stopping.
If an input power supply returns,
the UPS will become the stopping
(No.3). If the UPS does not become
the stopping (No.3) even if an input
power supply returns, check
whether or not the input breaker
has tripped. If the breaker has
tripped, reset it. If the UPS still
does not become the stopping
(No.3), contact an agent from
which you purchased the UPS or a
maintenance company.
When the UPS stopped since the
input power failure continued and
electric discharge of a battery was
completed, the UPS will return to
the normal operation (No.1)
automatically if an input power
supply returns.
3
(b)
Slow
blink
-
Stopping
(with an input
power supply)
The output of the UPS is stopping.
The UPS will return to the normal
operation (No.1) by pressing the
RUN/STOP switch for
approximately 1 second.
Summary of Contents for M-UPS050AD2B