- 46 -
8
Appendix
8.1
Rated Specification
Model
M-UPS050AD2B
Rating capacity
5000VA/4000W
Voltage
200/208/220/230/240V ± 2%
Frequency
50/60Hz (automatic changeover inside the UPS)
At the normal operation Depend on input frequency
Frequency
accuracy
At the battery operation Within ±0.1%
Number of phase
Single-phase two-wire (with a ground terminal)
Load condition
Linear load or rectified load with a crest factor of up to three times
Voltage waveform
distortion factor
At the resistance load: 4% or less
At the rectified load: 6% or less
Overcurrent
protection
Effective value: 100% or more
Peak value: 300% or more of rated effective value (bearing the load
of the crest factor of three)
Grounding system
Un-grounding
A
C
o
u
tp
u
t
Straightforward
bypass circuit
Thyristor system
(changeover time : without instantaneous power interruption)
Changeover is impossible at the time of a power failure.
Voltage *1 *2
160 to 288V
Frequency
50/60Hz ±5%
Number of phase
Single-phase two-wire (with a ground terminal)
Capacity
5000VA or less
Grounding system
Un-grounding or Line to line on a center-earthed
Power factor
0.97 or more (at the rated operation)
A
C
i
n
p
u
t
Input harmonic
current
Based on the Guideline of harmonic restraint measures for
general-purpose UPS
Type
Small sealed lead storage battery (long-life battery)
Backup time *3
(initial value)
Approximately 5 minutes
(4000W)
B
a
tt
e
ry
Nominal voltage
192V
Ambient
temperature
0 to +40 C
Relative humidity
20 to 95% (no condensation)
Noise
50dB(A) max. (at 1m from the front of the UPS)
O
th
e
rs
Cooling method
Forced air cooling
Outside dimension
W D H
130 718 434mm
Mass
63
㎏
(without battery: 29
㎏
)
Standard
UL1778 (-U, -UC type)
Applicable standard
VCCI CLASS A,
Comply with IEC62040
Input
Terminal block (L1/R, L2/S : M5 screws)
Ground
Terminal block (PE(G) : M5 screw)
E
x
te
rn
a
l
c
o
n
n
e
c
ti
o
n
Output
Terminal block (l1/U, l2/V : M5 screws)