8.1 Rated Specification
- 47 -
Model
M-UPS075AD2B
M-UPS100AD2B
Rating capacity
7500VA/6000W
10000VA/8000W
Voltage
200/208/220/230/240V ± 2%
Frequency
50/60Hz (automatic changeover inside the UPS)
At the normal operation Depend on input frequency
Frequency
accuracy
At the battery operation Within ±0.1%
Number of phase
Single-phase two-wire (with a ground terminal)
Load condition
Linear load or rectified load with a crest factor of up to three times
Voltage waveform
distortion factor
At the resistance load: 4% or less
At the rectified load: 6% or less
Overcurrent
protection
Effective value: 100% or more
Peak value: 300% or more of rated effective value (bearing the load of
the crest factor of three)
Grounding system
Un-grounding
A
C
o
u
tp
u
t
Straightforward
bypass circuit
Thyristor system
(changeover time : without instantaneous power interruption)
Changeover is impossible at the time of a power failure.
Voltage *1 *2
160 to 288V
Frequency
50/60Hz ±5%
Number of phase
Single-phase two-wire (with a ground terminal)
Capacity
7500VA or less
10000VA or less
Grounding system
Un-grounding or Line to line on a center-earthed
Power factor
0.97 or more (at the rated operation)
A
C
i
n
p
u
t
Input harmonic
current
Based on IEC61000-3-12
Type
Small sealed lead storage battery (long-life battery)
Backup time *3
(initial value)
Approximately 8 minutes
(6000W)
Approximately 5 minutes
(8000W)
B
a
tt
e
ry
Nominal voltage
192V
Ambient
temperature
0 to +40 C
Relative humidity
20 to 95% (no condensation)
Noise
55dB(A) max. (at 1m from the front of the UPS)
O
th
e
rs
Cooling method
Forced air cooling
Outside dimension
W D H
130 718 434mm
Mass
127
㎏
(without battery: 59
㎏
)
Standard
UL1778 (-U, -UC type)
Applicable standard
VCCI CLASS A,
Comply with IEC62040
Input
Terminal block (L1/R, L2/S : M8 screws)
Ground
Terminal block (PE(G) : M8 screw)
E
x
te
rn
a
l
c
o
n
n
e
c
ti
o
n
Output
Terminal block (l1/U, l2/V : M8 screws)
*1 Operation of UPS according to an input voltage
Low voltage
detection : 144V
return : 154V
Overvoltage
detection : 300V
return : 290V
*2 Rated voltage of UL standard product is 200, 208, 220, 230, or 240V.
*3 The backup time is the test result and is not a guaranteed value.