VHF Configuration
The VHF Configuration menu provides similar functions
as provided through the keypad menus.
The VHF frequency, activation threshold and
‘Click’
period can all be set.
Depending on customer demand, the capability to set
Sequential or Concurrent channel activation may also
be made available.
Winsock Alert
In some territories it is necessary to flash the windsock a
defined period before the main lighting circuit times-out. e.g.
CASA MoS Part 139 compliance (Australian Civil Aviation) requires:
9.3.1.5
Ten minutes before the aerodrome lighting system is due to turn
OFF, the PAL must cause the lights of at least the primary Illuminated
Wind Direction Indicator (IWDI), in accordance with Paragraph 9.6.1.10, to
commence to flash at approximately 50 cycles per minute (approximately
0.6 seconds ON and 0.6 seconds OFF), and continue to flash until either:
(a) the PAL system switches OFF, and all aerodrome lighting, including
the IWDI lights, is extinguished; or
(b) the PAL system has been reset for another ON period.
Select whether the Windsock Alert is on or off, the channel
which will trigger the alert and the period of the alert.
Note that in the current version of SMS only one channel can
trigger the windsock alert. In future versions of SMS, all and any channel will act as the trigger.
Cellular Numbers
For future product development and for units fitted with Cellular
Radios, cellular radio numbers can be stored in the RLC.