background image

20

WARM AIR FURNACE

WARNING

DISCONNECT THE ELECTRICAL POWER SUPPLY TO THE
FURNACE BEFORE ATTEMPTING ANY MAINTENANCE.
FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK
RESULTING IN PERSONAL INJURY OR LOSS OF LIFE.

CAUTION

Do not operate the furnace without an air filter. 

WARNING

HOLES IN THE EXHAUST PIPING OR FURNACE HEAT
EXCHANGER CAN ALLOW TOXIC FUMES TO ENTER THE
HOME AND CIRCULATE THROUGH THE DUCT SYSTEM
RESULTING IN CARBON MONOXIDE POISONING OR
DEATH. IF LEAKS ARE FOUND IN THE FURNACE HEAT
EXCHANGER, IT MUST BE REPLACED.

CAUTION

Be careful when working on the burner assembly. The hot
surface igniter is fragile and can break easily.

MAINTENANCE

AIR FILTER

The filter should be inspected frequently and cleaned as
necessary. We recommend a monthly inspection at first,
perhaps coinciding with the arrival of the monthly fuel bill as
a reminder. The frequency may be increased or decreased
depending on experience and conditions.

LUBRICATION

Both the induced draft blower motor and circulating fan
motor are ball bearing type motors. Neither requires routine
lubrication.

IMPORTANT: The motor bearings were prelubricated by the
motor manufacturer. Do not attempt to lubricate them.
Excess lubrication will void the warranty, shorten the service
life of the motors, and will attract the buildup of dust and
dirt.

The induced blower motor and circulating fan motor must be
cleaned on a periodic basis by a qualified service technician.
Dust buildup in the ventilation ports of the motor will cause
the motor to not dissipate heat properly resulting in reduced
service life.

VENT CONNECTOR

The exhaust venting between the furnace vent box and
chimney should be inspected periodically for sags, pitting,
evidence of leakage etc. If any of these conditions exist,
contact your installation contractor, service agency or fuel
supplier.

OPERATING TIPS

1.  Clean air filters maximize efficiency and reduce heating

costs.

2.  During the heating season, keep windows and doors

closed to reduce the heating load on the system.

3.  Avoid excessive use of kitchen exhaust hoods and other

exhaust fans to reduce the heating load on the system.

4.  Arrange the furniture and drapes so that the supply air

registers and return air grilles are unobstructed.

5.  If you have a perimeter duct system, ideally, the warm air

should bathe the cold exterior walls. Avoid the use of
plastic deflectors on the supply air registers that tend to
short circuit the warm air straight into the return air
grilles. These deflectors are often the cause of cool
draughts across the floor.

6.  Avoid placing heat producing appliances such as

televisions, radios, lamps, etc. in a location to influence
the thermostat.

7.  Keep combustible articles at least 3 feet away from the

furnace. Do not block access for servicing the furnace.
Do not use the vent connector as a hanger for clothes or
anything else.

8.

Never attempt to operate the furnace without the
blower door in place.

ANNUAL INSPECTION / SERVICE

A qualified installation contractor, service agency or fuel
supplier must inspect the furnace annually.

Your annual inspection will normally cover the following:

HEAT EXCHANGER

The heat exchanger should be inspected for corrosion. The
flue passages (heat exchanger tubes) should be free of scale
or excessive corrosion. Observe the burner flames. If there
appears to be flame distortion, check venting for blockage.
Also check for signs of inadequate combustion air supply. If
flame distortion continues after eliminating the blockage in
the venting as the cause, it may be necessary to replace the
tubular heat exchanger. The tubular heat exchanger cannot
be field cleaned. If the tubular heat exchanger is blocked by
soot or excess scale, replace it. Check NOX baffles (installed in
heat exchanger tubes) for any distortion. If distorted, replace
NOX baffles.

BURNERS

The burners should be inspected to ensure that they are free
of deterioration, dust and debris, and properly aligned with
the heat exchanger. In most cases, a simple vacuuming with a
brush attachment will adequately clean the burner assembly
and burner compartment.

The flame sensor should be inspected and cleaned with fine
steel wool or Scotch-Brite™ scrubbing pad. The wiring
connection should be checked to ensure that it is tight and
corrosion free.

NOTE: This is a critical connection. Small amounts of corrosion
can significantly increase the internal resistance of the
connection. A relatively small increase in resistance can result
in a large decrease in flame signal.

Summary of Contents for F80A

Page 1: ...DIMENSIONS 5 DUCTWORK 6 DETERMING COMBUSTION AIR 7 FURNACE VENTING 8 GAS SUPPLY 12 CONVERSIONS 13 HIGH ALTITUDE AIRFLOW SPECIFICATION TABLES 14 ELECTRICAL SPECIFICATIONS 15 START UP PROCEDURES SEQUEN...

Page 2: ...ated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furna...

Page 3: ...sociation 1515 Wilson Boulevard Arlington VA 22209 703 841 8400 National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 9101 617 770 3000 Canadian Gas Association Suite 1 243 Consumer...

Page 4: ...em An undersized return air system will prevent sufficient quantities of air from reaching the supply air system properly sized or otherwise and will consequently reduce the service life of the furnac...

Page 5: ...pports so as not to interfere with accessing the burner and blower compartments The opening in the floor must provide adequate clearances to the combustible material According to the Clearances to Com...

Page 6: ...E AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE...

Page 7: ...UCING DEVICE SUCH AS A FIREPLACE INSERT STOVE ETC DOING SO MAY RESULT IN FIRE CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY LOSS OF LIFE OR PROPERTY DAMAGE CAUTION DO NOT USE THE REAR PANEL AS A...

Page 8: ...gs one within 12 inches of the ceiling and the other within 12 inches of the floor The air openings must be sized based on whether the combustion and ventilation air is being taken from indoors or out...

Page 9: ...NFPA 54 National Fuel Gas Code in the United States or B149 Natural Gas and Propane Installation Code in Canada and within the requirements of the codes of the local authority having jurisdiction Refe...

Page 10: ...h joint to prevent sagging Horizontal segments must slope upward from the furnace to vent or chimney with a minimum 1 4 inch per foot When the vent tables from ANSI 223 1 NFPA 54 or B149 permit more t...

Page 11: ...connector segments together with a minimum of three sheet metal screws per joint Secure the vent connector to the furnace collar with a minimum of three sheet metal screws Type B vent connectors do n...

Page 12: ...EDICATED VENTING Figure 7 below shows a good method to permit dedicated venting making use of B Vent within a masonry chimney When using this method provide support for the B Vent IMPORTANT maintain a...

Page 13: ...there is no blockage restriction leakage corrosion collapsed materials such as fallen bricks or any other deficiency that could lead to an unsafe condition 3 Insofar as practical duplicate winter oper...

Page 14: ...ntity of dish detergent with water and daubing it onto the gas piping and connections PURGING GAS LINES NATURAL TO L P GAS This series furnace is manufactured as a natural gas sea level appliance It m...

Page 15: ...5 mm 1 20 mm 135 2000 4500 121 500 97 200 1 90 mm 1 15 mm 0 2000 135 000 108 000 1 95 mm 1 20 mm 2000 3000 118 800 95 040 1 83 mm 1 13 mm 3000 4000 113 400 90 720 1 79 mm 1 10 mm 4000 5000 108 000 86...

Page 16: ...ce requires a dedicated overcurrent device either a circuit breaker or a Type D time delay fuse It is permissible to connect furnace accessories such as humidifier transformers condensate pumps and el...

Page 17: ...to the right hand side The junction box contains a BLACK wire to be connected with L1 hot a WHITE wire to be connected with L2 the Neutral and a GREEN wire to be connected to the ground Use good qual...

Page 18: ...gin again at Step 4 above If the flame sensing signal is lost more than 5 times during a furnace cycle the gas valve will close and the ignition sequence goes into a 5 second postpurge the induced blo...

Page 19: ...and the air filter or filters are in place determine if the airflow is correct 1 Insert a duct thermometer in the supply air duct The thermometer should be placed as close as practical to the furnace...

Page 20: ...ower assembly to slide into blower rails Push blower assembly towards back of furnace ensuring blower assembly is correctly placed in blower rails Insert blower shroud on the front of the blower housi...

Page 21: ...ture and drapes so that the supply air registers and return air grilles are unobstructed 5 If you have a perimeter duct system ideally the warm air should bathe the cold exterior walls Avoid the use o...

Page 22: ...ft blue and not impinging on the heat exchanger CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Always verify proper ope...

Page 23: ...TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY FLAME SENSE LOST MAIN VALVE CLOSES THERMOSTAT CALL FOR HEAT ENDS MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN...

Page 24: ...23 MODEL F80A 50V51 250...

Page 25: ...ne voltage to L1terminal of must be 120 volts with reference to furnace chassis 2 Furnace must be reliably connected to earth ground 3 Induced blower moving main burner flame away from the flame senso...

Page 26: ...25 MODEL F80A R R 3 FACTORY SETTING...

Page 27: ...O IF YOU SMELL GAS DO NOT TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING LEAVE THE BUILDING IMMEDIATELY IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A P...

Page 28: ...nside air from outdoors from an attic or crawl space If renovations are done be sure that air supply openings are not inadvertently covered over with insulation vapor barrier or similar construction m...

Page 29: ...the next step 8 Gas valve Ensure that the Gas Valve Control is in the ON position see Figure 3 at right 9 Replace the burner access door ensuring that it is properly in place 10 Restore the electric...

Page 30: ...the furnace All ductwork should be secured to the furnace and all ductwork should be solidly supported throughout the heating system The furnace should be well supported on a level floor or by the me...

Page 31: ...operation points 5 and 9 will be ignored CAUTION THE FURNACE SHOULD BE OPERATED WITH ALL PANELS IN PLACE NEVER OPERATE THE FURNACE WITH THE BLOWER DOOR REMOVED EXCEPT FOR SERVICE PURPOSES WARNING ALWA...

Page 32: ...o Warm Air Furnace products Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any...

Reviews: