background image

Guidelines

Venting may be vertical or horizontal. 

Horizontal piping must slope back towards the furnace
at a minimum rate of 1/4” to the foot, so that

Horizontal runs must be supported at least every 3
feet. Horizontal sections must not dip or sag

All vent runs through unconditioned space where
freezing might occur should be insulated with 1”
thick, medium density, foil-faced Fiberglass insulation.
An equivalent “arm-aflex” or “rub-a-tex” may also be
used as long as there is no heat tape applied to the
vent pipe. For horizontal runs where water may
collect, wrap the vent pipe with self regulating 3 or 5
watt heat tape. The heat tape must be CSA, UL, or ULC
listed and installed per the manufacturer’s instructions. 

DO NOT COMMON VENT WITH ANY OTHER
APPLIANCE. 

If venting vertically, do not vent up a chimney serving
another appliance or install in a chase with a metal or
high temperature plastic pipe from another gas or fuel
burning appliance unless the required clearances to
combustibles can be maintained between the PVC pipe
and other pipes.

All exhaust piping must be installed in accordance
with CAN/CGA-B149.in Canada; the latest edition of
National Fuel Gas Code, NFPA 54 / ANSI Z223.1 in the
United States, as well as in accordance with local
codes. 

Take the building orientation and the presence of
other buildings or other nearby structures into
consideration when planning the venting system
location. Certain external structures could create air
turbulence around the vent termination leading to
downdrafts and similar venting problems. In windy
and hill locations, roof venting may improve
operations. Maximum venting length is based on 30
mph winds, areas where higher gusts are dominant it
is suggest to shorten the horizontal vent length,
increase the diameter of the vent, or vent vertically. 

The exhaust vent and combustion air intake shall be
installed so that both are located in the same wind
pressure zone.

CAUTION

FAILURE TO FOLLOW ALL VENTING GUIDELINES MAY
RESULT IN ERRATIC FURNACE OPERATION, FREEZE-UP
OF THE VENTILATION AIR PIPING, OR SOOTING OF THE
FURNACE. 

DANGER

SOLVENT CEMENTS AND PRIMERS ARE HIGHLY FLAM-
MABLE. PROVIDE ADEQUATE VENTILATION AND DO
NOT ASSEMBLE NEAR HEAT SOURCE OR OPEN FLAME.
DO NOT SMOKE. AVOID SKIN OR EYE CONTACT.
OBSERVE ALL CAUTIONS AND WARNINGS PRINTED ON
MATERIAL CONTAINERS. FAILURE TO FOLLOW THESE
GUIDELINES MAY RESULT IN FIRE, EXPLOSION OR AS-
PHYXIATION CAUSING PERSONAL INJURY OR LOSS OF
LIFE. 

JOINING PIPE AND FITTINGS 

Acceptable Materials for  Combustion Air and
Exhaust Vent Pipe

The furnace products of combustion include both flue
gases and condensate. All venting and drain materials are
plastic.

The combustion air and vent piping and fittings may be
comprised of: 

• Schedule 40 PVC, ASTM D1785 or CSA B137.3 

• PVC-DWV, ASTM D2665 or CSA B181.2 

• ABS-DWV, ASTM D2661 or CSA B181.1 

• Schedule 40 CPVC, ASTM F441 or CSA B137.6 

In Canada, construct all combustion-air and vent pipes for
this unit of CSA or ULC S636 listed schedule-40 PVC, PVC-
DWV or ABS-DWV pipe and pipe cement. SDR pipe is not
approved in Canada. In addition, the first three feet of the
exhaust must be accessible for visual inspection.

Procedure for Cementing Joints (ASTM D2855):

It is preferable to use a single type of plastic throughout
the venting and combustion air piping; however, if
dissimilar piping or fitting materials are used, they must be
joined with an appropriate transition cement. Dissimilar
pipe segments may be joined together by mechanical
means (i.e., 2” rubber coupling).

WARNING

All pipe, fittings, solvent cement, primers and
procedures must conform to American National
Standards Institute and American Society for Testing
Materials (ANSI / ASTM) standards. 

PIPE AND FITTINGS: ASTM D1785, D2466 and D2564 

PVC PRIMER AND SOLVENT CEMENT: ASTM D2564 

ABS PIPE AND FITTINGS: Use ABS Primer and Solvent
Cement D2235 

CPVC SOLVENT CEMENT: F493 

For proper installation, DO NOT thin or use solvent
cement that has become curdled, lumpy or thickened.

IMPORTANT

16

condensate drains towards the furnace. 

Minimum vent length - 25 total equivalent feet.
(See page 18, Table 4 - Venting Table) 

Summary of Contents for FV95A054

Page 1: ...erence USER S INSTRUCTION GUIDE INSTALLATION OPERATION AND MAINTENANCE MANUAL Model Serial Number Date of Purchase For future reference write down the model serial number and date of purchase Use thes...

Page 2: ...ng Piping Length 18 Pipe Using A Concentric Venting Kit 19 Exhaust Vent 20 Exhaust Vent 21 Non Direct Vent Furnace Installations 22 Direct Vent Piping Termination 17 CONDENSATE DRAINS 25 Drain Hose In...

Page 3: ...he furnace Furnace for heating the home located in the attached garage for example 8 A gas fired furnace for installation in a residential garage must be installed so that the burners and ignitor are...

Page 4: ...ING BIRTH DEFECTS AND OTHER REPRODUCTIVE HARM UL AND CUL RECOGNIZED CO DETECTORS ARE RECOMMENDED FOR ALL BUILDINGS EQUIPPED WITH FOSSIL FUEL BURNING APPLIANCES ALL CO DETECTORS SHOULD BE INSTALLED IN...

Page 5: ...wall horizontal vented gas fueled equipment It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon mo...

Page 6: ...be required 4 Existing ductwork should be assessed for its air handling capabilities For residential applications the recommended air velocity of a supply air trunk duct is 700 feet per minute fpm an...

Page 7: ...pounds Polyurethane and similar derivatives fumes Printer s inks paint removers furniture strippers varnishes varsol toluene etc Water softener salts and chemicals LOCATION of UNIT General 1 The furna...

Page 8: ...ER COMBUSTIBLE MATERIAL EXCEPT WOOD INSTALLATION ON COMBUSTIBLE MATERIAL CAN RESULT IN FIRE CAUSING PROPERTY DAMAGE PERSONAL INJURY OR DEATH DANGER COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINS...

Page 9: ...revent entraining combustion gases from an adjacent fuel burning appliance or entraining combustion air for this furnace 5 Ensure that there is adequate space and accessibility for the air filter 6 If...

Page 10: ...ce cabinet to prevent twisting or sagging General Considerations When choosing an installation position the installer must consider the following connections Combustion air intake Exhaust vent Gas pip...

Page 11: ...pling bands 12 Tighten the vent clamp and secure in place using the screws provided FIGURE A RIGHT INDUCER POSITION FIGURE B LEFT INDUCER POSITION SUGGESTED METHOD FOR SUSPENDING HORIZONTAL FURNACE AL...

Page 12: ...ducer drain connector will angle toward the front of cabinet with the second nested inside directed towards the top panel The 108 000 BTUH will require an extension between the inducer and the first e...

Page 13: ...of the cabinet WARNING WHEN INSTALLED IN THE DOWNFLOW POSITION ON A COMBUSTIBLE FLOOR SUBBASE KIT 30476 IS REQUIRED FAILURE TO INSTALL SUBBASE KIT COULD RESULT IN FIRE DEATH OR SERIOUS INJURY The open...

Page 14: ...w that is not provided If exhaust vent exits the left side panel the pipe can be routed straight outside the cabinet The pipe exiting the cabinet in any installation should be long enough to install t...

Page 15: ...area from which the combustion and ventilation air will be drawn negative pressure could be a problem if natural infiltration from the outdoors does not match the rate at which air is exhausted IMPOR...

Page 16: ...ng salons Antistatic fabric softeners used in clothes dryers Carbon tetrachloride Chlorinated cleaners and waxes Chlorine and bromine based swimming pool chemicals Deicing salts or chemicals e g rock...

Page 17: ...ED TO THE FURNACE WITH SHEET METAL SCREWS TAPE THE SHEET METAL SEAMS IN THE VICINITY OF THE FURNACE WITH DUCT TAPE OR SIMILAR MATERIAL WHEN THE FURNACE IS MOUNTED ON A PLATFORM WITH RETURN AIR THROUGH...

Page 18: ...OLLOW ALL VENTING GUIDELINES MAY RESULT IN ERRATIC FURNACE OPERATION FREEZE UP OF THE VENTILATION AIR PIPING OR SOOTING OF THE FURNACE DANGER SOLVENT CEMENTS AND PRIMERS ARE HIGHLY FLAM MABLE PROVIDE...

Page 19: ...r location or installa tion can cause structural or exterior finish damage to the building Caulk all cracks seams or joints within a 6 foot radius of the termination Direct Vent Piping Termination Gen...

Page 20: ...overhangs is a minimum of 1 foot vertically for each foot horizontally up to 6 feet As a protection against freezing do not expose a 3 x 2 reducing coupling to outdoor ambient temperatures Any adjacen...

Page 21: ...ntric vent terminal there must be a minimum of 12 clearance to grade or antici pated snow level There are no means available to raise the terminal externally If planning to use this terminal kit see T...

Page 22: ...o use one the screen may actually encourage the formation of rime ice which could cause the intake to become blocked in certain weather conditions Horizontal Exhaust Vent Termination Horizontal vents...

Page 23: ...quired if venting vertically through a roof The end of the exhaust pipe must be 12 higher than the entrance of the combustion air intake terminal The exhaust pipe extending through the roof must exten...

Page 24: ...NT IN CANADA In addition to the general guidelines in Canada the non direct vent exhaust shall not terminate Directly above a paved sidewalk or paved driveway which is located between two single famil...

Page 25: ...appliances 10 000 Btuh 4 ft 121 cm below or to side of supply inlet to building or the 3 kW 12 in 30 cm for appliances opening 1 ft 30 cm above combustion air inlet to any other 10 000 Btuh 3 kW and...

Page 26: ...air 6 in 15 cm for appliances 10 000 Btuh 6 in 15 cm for appliances 10 000 Btuh supply inlet to building or the 3 kW 12 in 30 cm for appliances 3 kW 9 in 23 cm for appliances combustion air inlet to...

Page 27: ...clamp to approximately 1 8 from the end of the hose 5 Fasten each drain hose to its inlet by tightening the hose clamps 6 Cut each drain hose near the blower division panel at the point where kinking...

Page 28: ...HORIZONTAL FLOW RIGHT CONDENSATE TRAP CONDENSATE TRAP HORIZONTAL FLOW LEFT UPFLOW DOWNFLOW CONDENSATE CONDENSATE TRAP TRAP FIGURE 11 FIGURE 12 FIGURE 13 FIGURE 14 26...

Page 29: ...Secure the condensate drain trap to the side of the fur nace using the mounting holes that were just drilled 5 Install one rubber grommet provided into each of the drain holes and then insert the 90 d...

Page 30: ...VALVE AND GAS VALVE DURING ANY PRESSURE TESTING THAT EXCEEDS 1 2 P S I G 3 45 KPA w c 12 inches w c is recommended These pressures must be maintained while all other gas fired appliances are operatin...

Page 31: ...o the furnace if applicable 1 Shut off electrical power to the furnace if applicable 2 Remove the upper front door to expose the gas train and burner assembly 3 Unfasten the ground joint union between...

Page 32: ...600 1 95mm 1 20mm 2000 3000 79200 75240 51480 48906 1 90mm 1 15mm 90 000 3000 4000 75600 71820 49140 46683 1 90mm 1 10mm 5 4000 5000 72000 68400 46800 44460 1 85mm 1 10mm 5000 6000 68400 64980 44460 4...

Page 33: ...manifold first examine the gas piping system to ensure that it is correctly sized Pipe sizing is specified in ANSI Z223 1 NFPA 54 in the U S or the B148 Natural Gas and Propane Installation Code in Ca...

Page 34: ...are rated 120 VAC 60 Hz 1 phase The amperage rating is indicated on the furnace rating plate Each furnace requires a dedicated overcurrent device either a circuit breaker or a Type D time delay fuse...

Page 35: ...the main burners directly See the lighting instructions on the furnace To Start The Furnace 1 Remove the burner compartment access door 2 Shut off the electrical power to the furnace and set the room...

Page 36: ...rops causing the room thermostat heating contacts to close 2 If pressure switch contacts are closed and have failed to open since the last cycle all subsequent steps will fail to occur 3 The induced b...

Page 37: ...e determine the air temperature rise of the furnace Insert a duct thermometer in the supply air duct The ther mometer should be placed as close as practical to the fur nace but out of the line of sigh...

Page 38: ...ded that the heating airflow be set for the Nominal Plus setting when the furnace is matched for this cooling capacity Furnace is set at the factory for maximum cooling capacity and DIP switches must...

Page 39: ...ommended that the Plus temperature rise is between 35 and 65 degrees F Heating Make adjustments to the controller with the electrical power off WARNING front blower shroud from furnace How To Remove T...

Page 40: ...OR LOSS OF LIFE MAINTENANCE This is a critical connection Small amounts of corrosion can significantly increase the internal resistance of the connection A relatively small increase in resistance can...

Page 41: ...ION WARNING heat and make a retrial for high every 5 or 10 minutes switch does not pull in the controller will continue in low finished and during the trial for ignition the high pressure If there is...

Page 42: ......

Page 43: ...t trips 1 hour lockout Too many low pressure switch trips after ignition 1 hour lockout 1 hour lockout Reset by cycling power or thermostat CHECK and REPAIR 1 Replace Integrated Furnace Control 2 Roll...

Page 44: ...ignition period If main flame is not sensed during trial for ignition system will shut off HSI element and main gas flow then go through another purge period and initiate another ignition trial A tota...

Page 45: ...5 7 0 187 67 1 21752 8720 7 67 57 7 7 5 0 187 6 2 217 18286 2 7 23 5 7 21 7 7 5 0 187 6 2 217 18286 2 7 23 5 7 21 25 0 187 67 1 25 6 1 67 7 50267 7 803 5 1 6 72 6 7 72 0 187 725 8 7 6 77 1 8720 7 67...

Page 46: ...E DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING LEAVE THE BUILDING IMMEDIATELY IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A PHONE OUTSIDE THE BUILDING FOLLOW THE GAS SUPPLIER S...

Page 47: ...must be in place during normal furnace operation Attempting to operate the furnace with missing doors or panels could lead to the creation of carbon monoxide gas 4 If the furnace is installed in a con...

Page 48: ...valve Ensure that the Gas Valve Control is in the ON position see Figure 3 at right 9 Replace the burner access door ensuring that it is properly in place 10 Restore the electric power to the furnace...

Page 49: ...2 Pull the filter out the front 3 Replace with a fresh filter and reconnect power to the furnace The filter will have an arrow indicating proper airflow direction DO NOT OPERATE YOUR FURNACE OR AIR C...

Page 50: ...nored The furnace achieves its mid efficiency in two general areas First there is no wasteful standing pilot The furnace consumes no gas in between cycles Secondly the furnace is designed to allow ver...

Reviews: