background image

1. If the furnace and air conditioner are on separate

thermostats, turn the furnace thermostat off during the
cooling season to prevent simultaneous operation of the
heating and cooling systems. Reverse the procedure during
the heating season. 

Adjust thermostat temperature and fan settings according
to the thermostat manufacturer’s recommendations. It is not
recommended to vary the temperature settings more than 5
degrees. Varying the temperature more than 5 degrees or
turning the thermostat off for periods less than 12 hours can
actually cost you more in energy consumption than keeping
the temperature constant. Consider indoor plants and pets
when varying the temperature from the normal comfort
level.

2. IMPORTANT:  Wait at least 3 minutes after turning the air

conditioner off before trying to restart. If an attempt is
made to start the compressor before the refrigerant
pressures are equalized, the compressor motor may trip on
its overload. An additional waiting period will be required
before restarting.

OPERATION INSTRUCTIONS

1. Keep the condenser (outdoor coil) clean. Wash it down with

a garden hose if necessary.

For continuing high performance and to minimize possible
equipment failure, periodic maintenance must be performed on
this equipment. Frequency of maintenance may vary depending
upon geographic areas, such as costal applications.

MAINTENANCE INSTRUCTIONS

WARNING

BE SURE THE UNIT DISCONNECT IS IN THE “OFF”
POSITION AND THAT ALL ELECTRICAL POWER TO THE
UNIT IS TURNED “OFF” BEFORE CLEANING THE SYSTEM.

2.  Remove any loose grass, leaves, papers, etc., from the area

around the condenser coil. These could reduce the air supply
through the coil and reduce the amount of cooling. 

3. Always install and keep system filters clean. Consult your

licensed Contractor for filter replacement schedules and
instructions.

WARNING

SERIOUS PERSONAL INJURY OR DEATH MAY RESULT IF
WATER SPRAY IS DIRECTED TOWARD LIVE ELECTRICAL
CONNECTIONS OR POWER SOURCES. 

Model

5

SUB-COOLING CHARGING 

Coils with TXVs should be charged 10-12 degrees (+ or – one
degree) of sub-cooling. For proper sub-cooling readings, a
standard high side gauge is required for pressure readings.

Use the chart below to determine the required sub-cooling value.

INSTRUCTIONS

1. Measure the outdoor air temperature. (T1)
2. Measure the liquid line pressure at the outdoor unit and

determine condenser refrigerant temperature by the scale on
the high side pressure gauge. (T2)

3. Measure the liquid line temperature on the liquid line at the

outdoor unit. (T3)

4. Subtract T3 from T2. (T2 – T3) This is the subcooling value.

Compare this value and the outdoor temperature (T1), to the
charts below. If the value is below the line, add refrigerant. If
the value is above the line, remove refrigerant charge.

NOTE: For the majority of installations no adjustment to the

TXV setting is required. However, if the measured superheat
at the evaporator is less than 4° or greater than 8° an
adjustment is required. The adjustment stem is at the base of
the valve under the flare nut. To increase superheat tighten
the stem clockwise and to decrease superheat back-out the
stem counter-clockwise. Use a 1/4” refrigeration service
wrench for this function.

NOTE: When removing refrigerant, always use standard reclaim
procedures.

FINAL CHECKS FOR INSTALLER

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub-through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers.

3. Tighten service valve stem caps to 1/12 turn past finger tight.
4. Leave Owner’s Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

°F

°F

°F

°F

°F

°F

SUB-COOLING CHART FOR UNITS WITH TXV

Summary of Contents for Split System Air Conditioner

Page 1: ...Braze Joints 3 Evacuation 3 Opening the Service Valve Step Valve 3 CONNECT REFRIGERANT PIPING 4 Precautions 4 Liquid Line Sizes 4 Suction Line Sizes 4 SUBCOOLING CHARGING 5 OPERATION INSTRUCTIONS 5 MAINTENANCE INSTRUCTIONS 5 CONDENSING UNIT NOMENCLATURE 6 LIMITED WARRANTY 7 NOTE THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATIO...

Page 2: ... representations contained in the limited warranty CODES The installer SHALL comply with all local state and federal codes and or regulations pertaining to this type of equipment and its installation Such codes and or regulations should take precedence over any recommendations contained herein in lieu of local codes Installations SHALL be made in accordance with the National Electrical Code local ...

Page 3: ...denser as close as possible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop and will make the system less susceptible to liquid migrations due to less refrigerant charge 1 The installer shall check available power to make certain it matches the unit rating plate located inside control box cover and that constant voltage can be maintained to ...

Page 4: ...d wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG wire to avoid excessive voltage drop 3 All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power Note Use of available 24 volt accessories may exceed the minimum power requir...

Page 5: ... with tubing When necessary use hanger straps which are 1 in wide and conform to shape of tubing insulation Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation Condensing units are available with pre charged sweat type copper connecting fittings Units are factory charged for 15 of line set tubing Adjust charge 0 65 oz per foot of variation from chart...

Page 6: ...icensed Contractor for filter replacement schedules and instructions WARNING SERIOUS PERSONAL INJURY OR DEATH MAY RESULT IF WATER SPRAY IS DIRECTED TOWARD LIVE ELECTRICAL CONNECTIONS OR POWER SOURCES Model 5 SUB COOLING CHARGING Coils with TXVs should be charged 10 12 degrees or one degree of sub cooling For proper sub cooling readings a standard high side gauge is required for pressure readings U...

Page 7: ... Hz 2 230 Volts 1 Phase 50 Hz 3 208 230 Volts 3 Phase 60 Hz 4 460 Volts 3 Phase 60 Hz 5 230 Volts 3 Phase 50 Hz 6 380 Volts 3 Phase 50 Hz C Air Conditoner CH Heat Pump A F Fedders Poduct Type Brand V Sweat Fitting Type D R 22 Refrigerant Z R 410A Refrigerant Variations Electrical Designation B 21 1 2 W x 21 1 2 D x H C 29 1 2 W x 29 1 2 D x H Chassis Size Nominal Capacity Series CONDENSING UNIT NO...

Page 8: ...pment nor for refrigerant used For warranty purposes the purchase date is established by a proof of purchase If a proof of purchase can not be verified then warranty period will be measured from the date of manufacture plus 6 months Cost of repair or replacement of consumable parts is not covered under the terms of this warranty Replacement parts are warranted only for the balance of the original ...

Reviews: