33
9.2 SPARE PARTS
BY THE NATURE OF ITS APPLICATION AND ITS SWITCHING
CAPABILITY SPARE PARTS FOR THE CIRCUIT BREAKER SHOULD
NORMALLY NOT BE REQUIRED. IF THE UNIT IS GOING TO BE USED FOR
FREQUENT LOAD SWITCHING, THEN THE PARTS SHOWN ON THE
RECOMMENDED SPARE PARTS LIST SHOULD BE CARRIED IN STOCK.
WHEN ORDERING SPARE PARTS, THE COMPLETE NAMEPLATE DATA,
ESPECIALLY THE BREAKER SERIAL NUMBER, SHOULD, BE PROVIDED TO
ENSURE THAT THE CORRECT PARTS ARE SUPPLIED.
9.3 COIL DATA (FIG 3.3)
RATED OPERATING
MINMUM AMPERES
CONTROL
VOLTAGE
VOLTAGE
DC
OHMS
INRUSH SEALED
120 AC 60 13.0 1.4
240 AC 120 50.0 1.0
48 DC 40 13.0 2.0
125 DC 40 86.0 2.5
SHUNT
TRIP
250 DC 70 215.0 1.25
120 AC 90 30.0 2.45 0.34
240 AC 180 312.0 1.5 0.15
48 DC 40 6.0 8.0 0.2
125 DC 60 50.0 2.2 0.2
SHUNT
CLOSE
250 DC 150 312.0 0.8 0.1
120 AC 96 23.0 2.45 0.34
U/V
TRIP
240 AC 190 312.0 0.8 0.1
120 AC 85
4
240 AC 190
2.5
48 DC 40
7
125 DC 85
4
CHARGING
MOTOR
250 DC 190
2.5
SERVICE DEPARTMENTS
133 lLSLEY AVENUE
UNIT M
DARTMOUTH, NOVA SCOTIA
B3B 1S9
PHONE: 902-468-2621
FAX: 902-468-2499
9600 IGNACE STREET
UNIT A
BROSSARD, QUEBEC
J4Y 9Z7
PHONE: 514-444-0800
FAX: 514-659-2484
1060 STACEY COURT
UNIT 2
MISSISSAUGA, ONTARIO
L4W 2X8
PHONE: 416-629-3942
FAX: 416-629-4947
1257 CLARENCE AVENUE
WINNIPEG, MANITOBA
R3T IT4
PHONE: 204-453-6166
FAX: 204-477-6999
7131F-6TH STREET S.E.
CALGARY, ALBERTA
T2H 2M8
PHONE: 403-255-2266
FAX: 403-255-2243
13520 CRESTWOOD PIKE
UNIT 11
CRESTWOOD INDUSTRIAL PARK RICHMOND,
BRITISH COLUMBIA
V6V 2G3
PHONE: 604-273-3531
FAX: 604-273-2218
www.schneider-electric.ca