background image

5

1.   ARC CHUTE ASSEMBLY

2.    INTERPHASE BARRIER

3.    R.H. END BARRIER

4.    L.H. END BARRIER

5.    FRONT FLASH SHIELD

6.    CLOSED-OPEN LINK

7.    CRANK ASSEMBLY

8.    CRANK BOX

9.    CRANK Box BEARINGS

10.    HOLDING PAWL

11.    RACHET WHEEL

12.    OSCILLATING LEVER

13.    CLUTCH

14.    CHARGED-DISCHARGED LINK

15.    CLOSED-OPEN INDICATOR

16.    CHARGED-DISCHARGED INDICATOR

17.    FRONT PLATE

18.    INDICATOR PLATE

19.    FACEPLATE Box ASSEMBLY

20.    FLOATING TRIM

21.    FACEPLATE ASSEMBLY

22.    HANDLE ASSEMBLY

23.    CLOSING LATCH

48.    WAFER CONTACT SPRING

49.    SPRING HOLDER

50.    MOVING ARCING CONTACT

51.    STATIONARY ARCING CONTACT

52.    LOAD TERMINAL

53.    ANTI-BOUNCE PLATE

54.    BASE MOULDING

55.    TRIP FLIPPER

56.    TRIP COIL ASSEMBLY

57.    LOWER CHANNEL

58.    FINGER SPACER

59.    DRAWOUT CONTACT ASSEMBLY

60.    SLS CAM

61.    GROUND CONTACT

62.    LOWER FLASH SHIELD

63.    SECONDARY DRAWOUT CONTACT (MOVING)

24.    CLOSE LEVER

25

.

 

TRIP ROD ASSEMBLY

26

.

 

SPRING GUIDE PIN

27.    CLOSING CASTING

28.    TOGGLE PIN

29.    TIE ROD ASSEMBLY

30.    CLOSING SHAFT

31.    MA

IN

 SPRING

32.    GUIDE BUSHINGS

33.    CLAMP ASSEMBLY

34.    BREAKER FRAME

35.    TRIP SHAFT

36.    TRIP LATCH

37.    LATCH BEARING

38.    LOWER MOULDING

39.    SENSOR MOUNTING BRACKET

40.    BARRIER

41.    SENSOR

42

.

 

JUMPER

43

.

 

CENTER STATIONARY MAIN CONTACT

44

.

 

MAIN MOVING CONTACT (WAFER ASSY)

45

.

 

UPPER MOVING MAIN CONTACT

46

.

 

CLOSING LINK ASSEMBLY

47

.

 

BRAID

3.

 BREAKER COMPONENTS AND CONTROLS

3.1

BREAKER SECTIONAL VIEW

Courtesy of NationalSwitchgear.com

Summary of Contents for H-3

Page 1: ...INSTRUCTIONS FOR THE CARE AND MAINTENANCE OF H 3 AND HL 3 CIRCUIT BREAKERS C 3 222 1 April 2000 FEDERAL PIONEER Courtesy of NationalSwitchgear com...

Page 2: ...IPMENT REFERENCE TO THIS MANUAL AND ADHERENCE ITS RECOMMENDATIONS WILL ENHANCE THE PERFORMANCE OF THESE BREAKERS UNDER ALL CONDITIONS THIS MANUAL DOES NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS OF...

Page 3: ...ONAL VIEW 3 3 BREAKER FACEPLATE AND CONTROLS 4 BREAKER OPERATION 4 1 DRAWOUT MECHANISM BREAKER INSERTION AND REMOVAL 4 2 GROUNDING CONTACT 4 3 SECONDARY CONTROL CONTACTS 4 4 BREAKER CLOSING 4 5 CLOSIN...

Page 4: ...KER AN EXAMINATION SHOULD BE MADE FOR DAMAGE SUSTAINED IN TRANSIT IF DAMAGE HAS OCCURRED OR THERE IS EVIDENCE OF ROUGH HANDLING A CLAIM SHOULD BE FILED IMMEDIATELY WITH THE TRANSPORTATION COMPANY AND...

Page 5: ...CUITS CONTROL CIRCUIT WIRING WHERE APPLICABLE SHOULD BE MADE IN STRICT ACCORDANCE WITH DETAILED WIRING DIAGRAMS FIXED MOUNTED BREAKERS ARE PROVIDED WITH TERMINAL BLOCKS FOR CONNECTIONS TO REMOTELY LOC...

Page 6: ...2 LOAD TERMINAL 53 ANTI BOUNCE PLATE 54 BASE MOULDING 55 TRIP FLIPPER 56 TRIP COIL ASSEMBLY 57 LOWER CHANNEL 58 FINGER SPACER 59 DRAWOUT CONTACT ASSEMBLY 60 SLS CAM 61 GROUND CONTACT 62 LOWER FLASH SH...

Page 7: ...D RESET TYPE HL 3 UNITS ONLY 8 MANUAL CLOSE M O UNITS ONLY 17 ELECTRICAL CLOSE E O UNITS ONLY 9 APERTURE FOR EMERGENCY MANUAL CLOSE E O UNITS ONLY 18 ELECTRICAL TRIP E O UNITS ONLY 10 FACEPLATE KEY IN...

Page 8: ...N THE CRADLE BREAKER DRAWOUT MECHANISM IS DISENGAGED ALL CONTACTS ARE DISENGAGED 4 1 DRAWOUT MECHANISM BREAKER INSERTION AND REMOVAL THE THREE POSITIONS OF A DRAWOUT MOUNTED BREAKER ARE SHOWN BELOW FI...

Page 9: ...OWN IN FIG 4 1 2 OR IN THE OPERATING POSITION AS SHOWN IN FIG 4 1 3 AND REMOVE THE CRANK WHEN CRANKING THE BREAKER INTO THE OPERATING POSITION CONTINUE CRANKING UNTIL THE MECHANISM COMES TO A FIRM STO...

Page 10: ...6 OSCILLATING LEVER 7 DRIVING PAWL 8 CLOSE COIL 9 SPRING CHARGING MOTOR 10 SPRING LIMIT SWITCH 11 SPRING LIMIT SWITCH LEVER 12 MAIN SPRING 13 AUXILIARY SWITCH 14 CLOSE COIL LIMIT SWITCH FIG 4 4 1 MAN...

Page 11: ...NG MANUALLY OPERATED BREAKER TO CHARGE THE MAIN SPRING ROTATE THE CHARGING HANDLE COUNTER CLOCKWISE TO THE UPRIGHT POSITION AND PUSH IN TO ENGAGE THE HANDLE WITH THE RATCHET WHEEL CLUTCH ON FRAME SIZE...

Page 12: ...ATTACHED TO THE SHAFT IS ROTATED TOWARD THE REAR OF THE BREAKER FREEING THE TRIP LATCH BEARING THIS ALLOWS THE UPPER PORTION OF THE CLOSING MECHANISM LINKAGE TO COLLAPSE AND THE ENERGY STORED IN THE M...

Page 13: ...ING ELECTRICAL OR MECHANICAL TRIP BUTTONS ON FACEPLATE DO NOT USE THE DRAWOUT MECHANISM GATE IF THE MAIN SPRING IS CHARGED RECLOSE THEN TRIP BREAKER FIG 4 1 1 OVERCURRENT PROTECTION I USD RELAY 2 CURR...

Page 14: ...KED FOR CONTINUITY WHILE IN THE BREAKER THE CONTROL FUSES IN THE ANTI SINGLE PHASE CIRCUIT MUST BE REMOVED OTHERWISE A BLOWN POWER FUSE WOULD STILL INDICATE CONTINUITY THROUGH THE SOLENOID NOTE THIS D...

Page 15: ...IL TO BE OPERATIVE THE FOLLOWING CONDITIONS MUST BE MET A BREAKER OPEN B CLOSING SPRING FULLY CHARGED SPRING LIMIT SWITCH CLOSED C TRIP LATCH AND LATCH ROLLER ENGAGED LATCH CHECKING SWITCH CLOSED REFE...

Page 16: ...E CIRCUIT HAS BEEN DE ENERGIZED SPRING RECHARGING FUNCTION AND CONSEQUENTLY BREAKER CLOSING IS BLOCKED THE CLOSING COIL SWITCH CONTACTS ARE IDENTIFIED ON THE WIRING DIAGRAM BY THE SYMBOL CC 4 18 SPRIN...

Page 17: ...THE CLOSING COIL IS ENERGIZED BOTH CC SWITCHES ARE OPERATED A CLOSING CONTACT OF ONE CC SWITCH NOW ENERGIZES THE A P R COIL ONE OF THE CLOSING A P R CONTACTS PARALLELS THE CC SWITCH CONTACT PROVIDING...

Page 18: ...E PREVENTS RECLOSING OF THE BREAKER EITHER MANUALLY OR ELECTRICALLY AFTER THE BREAKER HAS BEEN TRIPPED BY THE OVERLOAD RELAY UNTIL THIS DEVICE IS MANUALLY RESET FIG 5 6 OVERLOAD LOCKOUT SHOWN IN OPERA...

Page 19: ...T Of ONE BREAKER TO THE TRIP SHAFT OF A SECOND BREAKER AND VICE VERSA DRAWOUT BREAKERS ARE INTERLOCKED BY CABLE CONNECTIONS BETWEEN THE TWO CRADLES THERE ARE NO PERMANENT CONNECTIONS BETWEEN THE BREAK...

Page 20: ...CHARACTERISTICS 6 5 OPERATE BREAKER SEVERAL TIMES MANUALLY TO ENSURE CORRECT OPERATION NOTE THAT IF AN UNDERVOLTAGE TRIP DEVICE IS INSTALLED ITS MECHANISM MUST BE PHYSICALLY BLOCKED IN THE OPERATED PO...

Page 21: ...EMOTE CONTROL PROTECTION MONITORING AND ANNUNCIATING CIRCUITS REQUIRED TO BE OPERATIONAL IN TEST POSITION ARE FUNCTIONING CLOSE BREAKER COMPARTMENT DOOR CRANK BREAKER TO OPERATING POSITION OPERATE BRE...

Page 22: ...F WHICH ARE AVAILABLE FROM SCHNEIDER ELECTRIC SEE SECTION 9 1 IF THE MECHANISM IS VERY DIRTY A CLEANING SOLVENT MAY BE REQUIRED FOR LUBRICATION USE CAT NO PJC 8311 HIGH TEMPERATURE LUBRICATING GREASE...

Page 23: ...RUPTED THEY NEED ONLY BE REPLACED IF THEY SHOW SEVERE PITTING OR MATERIAL LOSS BECAUSE OF THEIR WIPING ACTION THE ARCING CONTACTS DO NOT REQUIRE CLEANING 7 INSPECT BRAIDS CHECK THE BRAIDS ATTACHED TO...

Page 24: ...CHANISM ROTATE THE TRIP SHAFT BACK AND RELEASE IT IT SHOULD ROTATE FREELY AND SPRING BACK TO POSITION CHECK THE CLOSING MECHANISM BY PARTIALLY CHARGING THEMAIN SPRING JUST TO THE POINT WHERE THE TRIP...

Page 25: ...12 2 TOP VIEW LUBRICATION FIG 7 3 12 4 MANUALLY OPERATED BREAKER LUBRICATION FIG 7 3 12 3 DRAWOUT MECHANISM LUBRICATION FIG 7 3 12 5 ELECTRICALLY OPERATED BREAKER LUBRICATION Courtesy of NationalSwit...

Page 26: ...E WAFER CONTACT IS TERMED THE CONTACT DEFLECTION THIS OVERTRAVEL ALLOWS THE WAFER CONTACTS TO BE FREE FLOATING AND SELF ALIGNING HELD AGAINST THE STATIONARY MAIN CONTACTS BY ONLY THE FORCE OF THE WAFE...

Page 27: ...Y THE TWO LOWER LOCATORS ON THE GAUGE REST IN THE HOLE IN THE SIDE OF THE CONTACT FRAME SIDEPLATE THE UPPER ONE ON THE TOP OF THE SIDEPLATE NOW RELEASE THE INDICATOR AND OBSERVE THE READING REPEAT FOR...

Page 28: ...MOULDINGS OF THE MAIN POWER STABS REMOVE GREASE FROM THE MAIN STAB SECONDARY DRAWOUT CONTACTS AND GROUND STAB 19 INSPECT CRADLE CHECK ALL MOLDINGS FOR DAMAGE AND THE MAIN STABS FOR EXCESSIVE WEAR SCO...

Page 29: ...OF THE OPERATING MECHANISM THIS ECCENTRIC ALTERS THE LENGTH OF THE LOWER CLOSING MECHANISM LINKAGE THEREBY CHANGING THE POSITION OF THE CLOSING CASTING ITEM 7 AND TOGGLE PIN WHEN THE MAIN SPRING IS I...

Page 30: ...IDE PLATE CONTROLS THE ENGAGEMENT OF THE TRIP LATCH ROLLER IF THIS ENGAGEMENT IS INSUFFICIENT THE ROLLER MAY RELEASE DURING THE CLOSING STROKE RESULTING IN FAILURE TO CLOSE THE MAIN CONTACTS MAY MOVE...

Page 31: ...DJUSTMENT IS MADE THE FOLLOWING MUST BE CHECKED IF PRESENT ON THE BREAKER 1 DRAWOUT GATE INTERLOCK LEVER ECCENTRIC ADJUSTMENT ON DRAWOUT BREAKERS SECTION 8 4 2 SHUNT TRIP ADJUSTMENT SECTION 8 5 3 UNDE...

Page 32: ...N THE CIRCUIT THIS IS NECESSARY TO ISOLATE THE TRIP COIL FROM THE POWER FUSE THE COIL SHOULD OPERATE AT APPROXIMATELY 50 VOLTS IN THIS TEST IT SHOULD BE NOTED THAT THESE COILS ARE SHORT TIME RATED IN...

Page 33: ...HEEL BE SURE TO CHECK ALL FACEPLATE INDICATORS AND OPERATING BUTTONS ETC FOR FREEDOM OF MOVEMENT AFTER REINSTALLNG THE FACEPLATE 9 MAINTENANCE ACCESSORIES AND SPARE PART 9 1 MAINTENANCE ACCESSORIES LI...

Page 34: ...240 AC 180 312 0 1 5 0 15 48 DC 40 6 0 8 0 0 2 125 DC 60 50 0 2 2 0 2 SHUNT CLOSE 250 DC 150 312 0 0 8 0 1 120 AC 96 23 0 2 45 0 34 U V TRIP 240 AC 190 312 0 0 8 0 1 120 AC 85 4 240 AC 190 2 5 48 DC 4...

Page 35: ...Front Flash Shield Right Hand Side 1 182A 40A 1 182A 40A 1 182A 40A 1 182A 618 2 Interphase Barrier 2 13A 578C 13A 578C 13A 578C 13A 634 635 3 End Barrier 2 13A 172A 1 13A 172A 2 13A 172A 2 13A 632 6...

Reviews: