29
Programming
Signaling Standalone Manual
Federal Signal
www.fedsig.com
Fields
Description
Priority
The Priority assigned to the digital input. For Momentary mode,
an input of equal or higher priority interrupts an active Continuous
mode input and stops and overrides currently active Momentary
mode input. When multiple Continuous mode inputs area active with
different priorities, the lower priority inputs are skipped until the higher
priority inputs become inactive. The highest priority is 1, and the
lowest is 4.
Digital Voice
List of digital voice messages to play when the input becomes active.
This field must be a comma-delimited list of 1–19 digital voices
indices (for example, 1,2,3,4).
Relay 1
Turns on Relay 1 when the input is active.
Relay 2
Turns on Relay 2 when the input is active.
The relays will remain on while the DV messages are playing in
Momentary mode. The relays will remain on as long as the input is
active in Continuous mode.
Apply
Saves your settings. You must reboot for changes to take effect.
2.
Enter the RTU Number.
3.
Enter a description of the RTU.
4.
In the Power Attenuation box, type or select a the default volume level.
5.
In the Ambient Attenuation box, type or select the ambient attenuation threshold.
6.
Click Enable SmartMsg to enable the SmartMsg interface.
7.
Click Enable Modbus to enable the Modbus
®
interface.
8.
Click Enable SIP to enable SIP.
9.
Enter the fields for the Digital Inputs #1 through #4 to assign that Digital Input to play
digital voice messages. Inputs that have been programmed from Commander
®
for
local activation cannot be configured from the webpage and will be unavailable.
10.
Click Apply.
11.
Reboot the device for the IP address change to take effect.