background image

5

Installing and Maintaining the Model PS1000

Installing the Model PS1000 requires mounting the enclosure and wiring the PS1000. To calculate battery 

capacity, alarm duration, and other variables, use “Table 3 Battery-size calculation worksheet” on page 8.

 For access control applications, standby batteries are optional. When standby batteries are not used, a loss of 

AC results in the loss of output voltage. When standby batteries are used, they must be lead-acid or gel.

Mounting the Model PS1000 Enclosure

For the enclosure dimensions, see Figure 1 on page 4.

  

Select a mounting location for the Model PS1000. 

 

Mark and drill holes in the wall to line up with the top two keyholes in the enclosure. 

 

Install two upper fasteners and screws in the wall with the screw heads protruding. 

 

Place the upper keyholes of  the enclosure over the two upper screws. 

 

Level and the enclosure and tighten the two upper screws. 

 

Mark the position of the lower two holes and remove the enclosure. 

 

Drill the lower holes and install the three fasteners. 

 

Place the upper keyholes of the enclosure over the two upper screws. Install the two lower screws and 

make sure to tighten all screws. 

 

Secure the enclosure to earth ground.

Wiring the Model PS1000

For an illustration of the enclosure wiring, see Figure 2 on page 5. Keep the power limited wiring at least 0.25" 

away from non-power limited wiring, such as the AC input wires and battery wires.

SHORT CIRCUIT—Do not expose the Model PS1000 to rain or moisture. Failure to 

heed this warning may cause electrical shock or equipment damage.

EQUIPMENT DAMAGE—To avoid equipment damage, do not exceed a total output 

rating of 10 A for each Model PS1000 installed.

To wire the Model PS1000: 

 

To avoid damage to the equipment, measure the output voltage before connecting the Model PS1000. 

Ensure that the enclosure is connected to earth ground. 

 

Use 22 AWG to 18 AWG wiring to connect AC power to the terminals marked 

L

,

 

G

N

 

Use 14 AWG or thicker for all power connections (battery, DC output, AC input). 

NOTE:

 Keep the power limited wiring separate from non-power limited wiring (AC input, battery 

wires). Minimum 0.25" spacing must be provided. 

Summary of Contents for PS1000

Page 1: ...2562563A REV A 1212 Printed in U S A Installation and Maintenance Manual Model PS1000 Power Supply Charger...

Page 2: ...nd controllers manufactured by Federal Warning Systems are warranteed for two years on parts and one year on labor No agent employee representative or distributor of Seller has any authority to bind t...

Page 3: ...uct Specifications 3 Installing and Maintaining the Model PS1000 5 Mounting the Model PS1000 Enclosure 5 Wiring the Model PS1000 5 Maintaining the Model PS1000 9 Obtaining Service Parts and Support 10...

Page 4: ...70 NFPA 72 ANSI and with all local codes and authorities having jurisdiction Read and understand all instructions before installing or operating this equipment Consult the authority having jurisdicti...

Page 5: ...sealed lead acid or gel batteries Automatic switchover to stand by battery when AC fails 3 6 A maximum charge current Zero voltage drop when switched over to battery backup Supervision AC fail superv...

Page 6: ...A Alarm 10 A Standby 200 mA Alarm 10 A Standby 100 mA Alarm 10 A 24 Vdc 65 Ah Battery NA Standby 8 A Alarm 10 A Standby 1 5 A Alarm 10 A Standby 500 mA Alarm 10 A 1 285 ENCLOSURE DIMENSIONS 15 5 H x 1...

Page 7: ...rill the lower holes and install the three fasteners Place the upper keyholes of the enclosure over the two upper screws Install the two lower screws and make sure to tighten all screws Secure the enc...

Page 8: ...onnected to an annunciator alarm panel The relays are normally energized when AC power is present The contact rating is 1 A at 28 Vdc AC or brownout fail is reported within 1 minute of event To delay...

Page 9: ...ISTRIBUTION MODULE S 115 Vac POWER MAINS NON POWER LIMITED CLASS I BATTERY AND AC SUPERVISION CIRCUIT POWER LIMITED NON POWER LIMITED KEEP POWER LIMITED WIRING SEPARATED FROM NON POWER LIMITED USE 0 2...

Page 10: ...alarm A G Alarm duration hours 15 min 0 2 hour alarm H H Battery capacity required for alarm E F G Ah I Total calculated battery capacity D H Ah J Battery capacity required I 1 8 safety factor Ah Note...

Page 11: ...Under normal load conditions the DC output voltage should be checked for proper voltage level Battery Test Under normal load conditions check that the battery is fully charged check the specified vol...

Page 12: ...eturn authorization from your local distributor prior to returning the product to Federal Signal Please contact your distributor for assistance A product is qualified to be returned for credit when th...

Reviews: