- 31 -
CONTROL PARAMETERS IMSS120 SELF-CONTAINED
Table 3 - Control Parameters
Parameter Description
Control Setpoint
1
2
3
4
5
6
7
8
9
Compressor Cut out [°F]
32.0 30.5 29.0 27.5 26.0 24.5 23.0 21.5 20.0
Compressor Cut in [°F]
39.0°
Compressor Min On Time
5 min
Compressor Min Off Time
2 min
Compressor Max Run Time
75 min
Defrost Termination Temp [°F]
43.0
Time to first defrost
8 hr.
Time to subsequent defrost
8 hr.
Maximum Defrost duration
30 min
Defrost on demand differential [°F]
15.0
Delay for defrost on demand
5 min
Time delay to the next defrost on demand
30 min
\Table 4 - Temperature Probe Common Resistance Chart
Probe Temp
Maximum
Resistance [Ω]
Normal Resistance [Ω]
Minimum Resistance [Ω]
32°F (0°C)
27.83
27.28
26.74
77°F (25°C)
10.1
10
9.9
212°F (100°C)
1
0.97
0.94