Control Display
The control display is located in the unit base. It is programmed to display the current set point
associated with the control sensor located inside the air duct at the top of the case.
Minimum Run Timer Feature
The unit controller is programmed to have the condensing unit run a minimum of 5 minutes,
regardless of the control temp being satisfied. If the temperature control reaches the cut out set point
before 5 minutes, the minimum run time setting in the control will keep the unit in a run cycle mode
until the timer reaches 5 minutes. The refrigeration cycle will be off until the temperature control cut in
temperature is reached.
This timer typically comes into effect in low ambient conditions where the unit may cycle too
frequently to maintain proper product temperature.
Maximum Run Timer Feature
The unit controller is programmed to have the condensing unit run a maximum of 60 minutes.
If the unit has not reached cut out temperature setting in 60 minutes, the unit goes into on off cycle.
This typically comes into effect in high ambient temperature and relative humidity conditions.
REFRIGERATION OPERATION
Self Contained Models
Refrigeration R404A Charge Prior To 01/01/2020
See Refrigeration
And Electrical Data
Pages
Refrigeration R449a Charge After 01/01/2020
See Refrigeration
And Electrical Data
Pages
The self-contained models are shipped from the factory with a completely operational refrigeration system and
require no modifications or adjustments upon installation. Case must be installed as per the installation section
of this manual to provide proper condensing air cooling.
Self Contained Refrigeration Operation
The unit temperature is controlled by the Electronic control outlined in the control section of this manual.
Note: The condenser fan is factory wired to run continuously.
Refrigerated Self-Serve Merchandiser (High Profile)
Page 16