background image

 

 

DEFROST

STOP

DISPLAY

SET

35

START

SET

DISPLAY

SET

DISPLAY

TIME

CLOCK

DEFROST

ON/OFF

ON/OFF

ON/OFF

HUMIDITY

LIGHTS

POWER

PM

A

B

C

D

E

F

G

H

I

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Market Deli Refrigerated Cases   

 

 

 

 

 

 

 

Page 8 

Summary of Contents for SQ3CD

Page 1: ... Models INSTALLATION OPERATION INSTRUCTIONS KEEP THIS MANUAL FOR FUTURE REFERENCE Engineering and technical data are subject to change without notice Federal Industries P O Box 290 Belleville WI 53508 Toll Free 1 800 356 4206 WI Phone 608 424 3331 Fax 608 424 3234 ...

Page 2: ...CONTROLS 7 8 HINGED FRONT GLASS 9 PERIODIC MAINTENANCE 9 CLEANING INSTRUCTIONS 10 DAILY CLEANING 10 WEEKLY CLEANING 10 INTERIOR CLEANING 11 EXTERIOR CLEANING 11 SERVICE INFORMATION 12 PRE SERVICE CHECKLIST 12 13 SPECIAL SERVICE SITUATIONS 14 SALE DISPOSAL 14 OWNER RESPONSIBILITY 14 REFRIGERATION ELECTRICAL DATA SELF CONTAINED 15 REFRIGERATION ELECTRICAL DATA REMOTE 16 REPLACEMENT PARTS 17 REPLACEM...

Page 3: ...ents contain technical instructions intended only for persons qualified to perform electrical work DANGER Improper or faulty hookup of electrical components in the case can result in severe injury or death All electrical wiring hookups must be done in accordance with all applicable local regional or national standards SERIAL NUMBER Record the model and serial numbers of the case for easy reference...

Page 4: ...ignore the message WARNING Severe injury or death can occur if you ignore the message CAUTION Minor injury or damage to your case can occur if you ignore the message NOTICE This is important installation operation or service information If you ignore the message you may damage your case The warning and safety labels shown throughout this manual are placed on your Federal Industries case at the fac...

Page 5: ...o your shipment Ask for an immediate inspection of your concealed damage item Crating material must be retained to show the inspector from the truck line INSTALLATION INSTRUCTIONS Locating The Display Case The case should be located where it is not subjected to the direct rays of the sun heating ducts grills radiator or ceiling fans nor should it be located near open doors or main door entrances A...

Page 6: ...on components Normally it is not necessary to remove the panel to install the case This panel must be in place for proper operation of the case There is one 1 removable panel on the back of the case The panel allows access to the condensing unit and the field wiring connection box Remove this panel to make field wiring connections Condensate Evaporator This case is furnished with an electric conde...

Page 7: ...must be grounded upon installation This unit is designed for permanent connection to a power source See the electrical data plate located next to electrical junction box for proper circuit size and wire ampacity The electrical field connection 2 x 4 box is accessible from the rear of the case and is located in the right leg as viewed from case rear A second 2 x 4 field connection box is also locat...

Page 8: ...emove bulb from top light assembly by rotating bulb 90 degrees and pulling outward This will allow bulb prongs to easily slide out of bulb receptacles located at each end of the bulb The bulbs are furnished with plastic safety light shields Make certain the light shields are always in place to safeguard against bulb breakage When replacing lights use direct equivalents to the original bulbs Placin...

Page 9: ...rature D Clock Display Set Press to display current time Adjust time with bottoms B Hours C Minutes Press again to return the temperature display E Defrost Start Display Set Press to display current defrost start time adjust same as clock F Defrost Stop Display Set Press to display current auto stop time adjust same as clock If start and stop time are the same auto start stop is off G Light Switch...

Page 10: ...DEFROST STOP DISPLAY SET 35 START SET DISPLAY SET DISPLAY TIME CLOCK DEFROST ON OFF ON OFF ON OFF HUMIDITY LIGHTS POWER PM A B C D E F G H I Market Deli Refrigerated Cases Page 8 ...

Page 11: ...nsult the factory if service is required NOTE Condensation will occur on the front and side glass if the room environment exceeds 75º ambient and or 55 relative humidity conditions Periodic Maintenance Cleaning Condenser Coil Disconnect power to unit Remove the rear grill and vacuum the front surface of the condenser coil This should be done every one to two months as necessary Market Deli Refrige...

Page 12: ...Wipe complete interior of case using a damp cloth 3 The glass can be cleaned with common window cleaners The remaining exterior surface should be wiped down using any ammoniated cleaners or soapy warm water Note Detergents are not recommended Weekly Cleaning This procedure is recommended on a weekly basis It may need to be performed more often if necessary to maintain a clean sanitary case The cas...

Page 13: ...low to dry Note Depending on the amount of usage and spillage of foreign material some fasteners may have to be removed and parts disassembled to allow proper cleaning of the unit 8 Clean all foreign material from door tracks using warm soapy water and a brush Apply a light film of lubricant such as PAM to make the doors operate smoother 9 Clean both sides of the doors and interior of the front gl...

Page 14: ...ll Free 800 356 4206 WI Phone 608 424 3331 geninfo federalind com Pre Service Checklist You may avoid the cost and inconvenience of an unnecessary service call by first reviewing this checklist of frequently encountered situations that can cause unsatisfactory case performance CAUTION Before servicing case turn off power at the main breaker of fuse box Market Deli Refrigerated Cases Page 12 Pre Se...

Page 15: ...or approximately one hour to defrost Excessive frost can buildup if the case is operated with the doors open for extended periods of time Glass Fogging Checkroom ambient Case is designed to operate in an environment not to exceed 75ºF and 55 relative humidity Check case temperature Case is designed to operate between 36ºF and 42ºF Check that the airflow is not being disturbed by a nearby fan or ai...

Page 16: ...al area of the case Any case malfunction or housekeeping problem that creates a slip fall hazard around or under a case should be corrected immediately SALE DISPOSAL Owner Responsibility If you sell or give away your Federal Industries case you must make sure that all safety labels and the Installation Service Manual are included with it If you need replacement labels or manuals Federal Industries...

Page 17: ...otor Evaporator Fan 0 4 ea 1 0 4 ea 1 0 4 ea 1 0 4 ea 2 0 4 ea 2 Lights 0 3 0 7 0 7 0 7 0 8 Condensate 4 8 4 8 4 8 4 8 4 8 Evaporator Refer to the rating plate data attached to the rear of the case for Maximum Fuse Size and Minimum Circuit Ampacity Each model is equipped with a general purpose receptacle which requires a separate electrical circuit of 120V 15 Amps This receptacle must be wired in ...

Page 18: ... Lights 0 3 0 7 0 7 0 7 0 8 Condensate 4 8 4 8 4 8 4 8 4 8 Evaporator Refer to the rating plate data attached to the rear of the case for Maximum Fuse Size and Minimum Circuit Ampacity Each model is equipped with a general purpose receptacle which requires a separate electrical circuit of 120V 15 Amps This receptacle must be wired in accordance with the National Electrical Code Market Deli Refrige...

Page 19: ... 42 11071 42 11070 Ribbon Cable 8 Pin 41 13767 41 13767 41 13767 41 13767 41 13767 Ribbon Cable 12 Pin 41 13766 41 13766 41 13766 41 13766 41 13766 Temperature Probe 41 13755 41 13755 41 13755 41 13755 41 13755 Logic Board 41 13744 41 13744 41 13744 41 13744 41 13744 Relay Board 41 13745 41 13745 41 13745 41 13745 41 13745 Misc Components Front Curved Glass 50 13028 50 13029 50 15753 50 12830 50 1...

Page 20: ...767 41 13767 41 13767 Ribbon Cable 12 Pin 41 13766 41 13766 41 13766 41 13766 41 13766 Temperature Probe 41 13755 41 13755 41 13755 41 13755 41 13755 Logic Board 41 13744 41 13744 41 13744 41 13744 41 13744 Relay Board 41 13745 41 13745 41 13745 41 13745 41 13745 Misc Components Front Curved Glass 50 13028 50 13029 50 15753 50 12830 50 13831 Side Glass 51 13124 51 13124 51 13124 51 13124 51 13124 ...

Page 21: ...ON G G B B BLK W R MEZANNINEOPTION BALLAST NOTE3 B SOLENOID HUMIDITYOPTION THERMOSTAT DIGITALTHERMOMETER W BLK RELAY B A CONDENSING UNIT G Y W W IN COMP FOR DETAILS SEE DIAGRAM SQ 5CD SQ 4CD SQ 3CD DIAGRAMFOR W TEMPERATUREPROBES RIBBONCABLE BLK W BLK W W BLK LAMP W W BLK BLK W BLK BLK BLK BLK RIBBED BLK RIBBED G Y Y W 120VOLTS FIELDWIRING 1PHASE 60 HERTZ 2X4BOX USEDON EXTRAFAN SQ 6CDONLY M FAN MOT...

Page 22: ... G B B Y G Y B MOTOR FAN LAMP LAMP MEZANNINE OPTION R B B Y W B B MEZANNINE OPTION R W BLK BALLAST THERMOSTAT DIGITAL THERMOMETER SOLENOID HUMIDITY OPTION W SQ 8CD DIAGRAM FOR W TEMPERATURE PROBES RIBBONCABLE BLK W BLK W W BLK W W BLK BLK W BLK BLK BLK BLK RIBBED BLK RIBBED G Y Y LAMP B B Y G Y Y LAMP B Y G B LAMP B Y G B Y LAMP Y Y G B B Y R B B Y Y Y Y BALLAST W BLK R 120 VOLTS FIELDWIRING 1 PHA...

Page 23: ...BLK W W BLK LAMP W W BLK BLK BLK W BLK BLK BLK RIBBED BLK RIBBED G BLK BLK W 120 VOLTS FIELD WIRING 1 PHASE 60 HERTZ 2 UNIT MUST BEGROUNDED 1 SEE DATA PLATE FOR WIRE AND FUSE SIZING 2X4 BOX 3 CUT AND INSULATE EXTRA LEAD IN TWO LAMP USEDON EXTRA FAN SQ 6CD ONLY M FAN MOTOR BLK PLUG BLK RECP PLUG M FAN MOTOR BLK BLK RECP BLK BLK G W FLOAT SWITCH EVAPORATOR CONDENSATE THERMOSTAT W R LAMP B B W R BALL...

Page 24: ...BLK BLK W Y LAMP B B Y G Y Y LAMP B Y G B LAMP B Y G B Y LAMP Y Y G B B Y R B B Y Y Y Y BALLAST W BLK R 120 VOLTS FIELDWIRING 1 PHASE 60 HERTZ FUSESIZING SEEDATA PLATEFORWIREAND 2X4 BOX UNITMUSTBE GROUNDED M FAN MOTOR BLK PLUG BLK RECP PLUG M FAN MOTOR BLK BLK RECP W G BLK FLOAT SWITCH EVAPORATOR CONDENSATE THERMOSTAT W E 161412 26 96 CCSSQ MARKETDELIREMOTE COLORCODE B BLUE Y YELLOW W WHITE R RED ...

Page 25: ...NG DIAGRAM RECEPTACLE WIRING PLUG RECEPTACLE E 1423 1 07 25 07 BJW GROUNDED UNIT MUSTBE 1 PHASE 60 HERTZ 120 VOLTS G LINE BLK W W BLK G 2X4 BOX 15 AMP GFCI RECEPTACLE Market Deli Refrigerated Cases Page 23 ...

Reviews:

Related manuals for SQ3CD