background image

 

2.5. Filling and putting into operation  

Filling must be carried out by soft water. Before starting filling every valve must be opened and the 
outlet valves must be closed. Air discharging valves are to be opened and ensure that the caps of 
automatic ones' are opened to 1-2 turns. 
Filling must be done slowly. Keep an eye on lower situated purging points and purging valves of 
radiators and close them after the appearance of water. Automatic purgers' caps must not be closed! 
Purging of pump can be done by unbolting the screw on the front of it. Purging of boiler can be done 
during slow filling by air discharging valve situated on heat exchanger.  
Technicalness is very important from the point of long operation life. Frequent charging or discharging 
of the system or certain parts of it and other water losses (leakages) cause consequential refill. This 
means letting corrosion causing oxygen into the system. If water quality is not suitable than scaling 
occurs. 
It is recommended to carry out first heating-up slowly (approx. in 5 hours) in the interest of scaling 
reduction and perfect purging. 

First month purge the system in warm status during continuous refill to let aggregated air out 
of the pipes. 
 

2.6. Electric description 

(This chapter describes information only about the electric part of boiler. It does not contain hydraulic, 
gas technical and installation tasks connecting to the operation of electric unit!) 
 

Preparations for installation 

For operation of the appliance the supply voltage is 230V 50Hz. The boiler has a 2m long connection 
cable. The user has to provide a two-pole earthed wall-socket placed beside the appliance-or in case 
of a bathroom in zone 3-and connect it to the electric network of the house. Max. current drain of the 
boiler is not bigger than 1Amper. 
 
 

Attention! 

The user has to arrange mounting, connecting, shock-hazard protection and fire prevention inspection 
of the wall plug. 
The user also has to provide a room thermostat and its mounting to the suitable place from heating 
technical and control engineering point of view as well as a connection cable pulled out from the boiler 
to the room thermostat. For a connection cable the most appropriate one is a three-conductor cable 
with a nominal voltage of min. 0,4 kV and with a cross-section of 1mm² for each wire. Pull this cable to 
the room thermostat without interruption. 
 
The controlling electronics located behind the boiler casing are mounted in a sealed plastic box. Their 
protection ratio is IP 44. In case of boilers where the casing cannot be opened (but the case can be 
taken off) the protection ratio of the (whole) appliance is IP 45, so if it mounted in a bathroom it can be 
placed to zone 1. (According to Hungarian Standard). 
After removing boiler casing and cover of controlling box the wiring points can be reached. 
 
 

Attention!

 

After removing the cover of control box the points conducting mains voltage (230 V) can be touched! 
Therefore: 
(1) Removal of cover and connecting (e.g.: the room thermostat) from the box is allowed only in no-
voltage state: the mains plug must be pulled out of the wall-socket. 
(2) Adjusting in a voltage state of trimmer potentiometer located in electronic panel must be done by 
an insulated screwdriver. 
(3) Steps described in points (1) and (2) can be carried out by an electrician! 
 
 
 
Items in the control box wired up by factory (see Fig. 5.): 

-pump 
-gas magnetic valve 
-DWT potentiometer 

Summary of Contents for C 24 H

Page 1: ...USER S MANUAL Wall mounted boiler for central heating C 24 H F t stechnikai K sz l kgy rt Ltd Hungary 6900 Mak Aradi street 136...

Page 2: ...4 FLUE GAS PIPING 7 2 5 FILLING AND PUTTING INTO OPERATION 8 2 6 ELECTRIC DESCRIPTION 8 2 7 CONNECTING OF ROOM THERMOSTAT 9 2 8 INSTALLATION 10 2 9 FROST PROTECTION 11 2 10 FIRST INSTALLATION 12 2 11...

Page 3: ...electric appliance do not move any electric wall plug do not employ an open fire In case of further gas leakage turn off the main gas valve under the gas meter The gas leakage must be reported to the...

Page 4: ...Pilot flame holder Flue gas backflow sensor Limiter thermostat Pump Electric control box Purging screw Thermocouple Gas inlet pipe 19 20 Thermistor Display A G B Delivery water Gas connection Returni...

Page 5: ...s inlet 3 Thermocouple 4 Burner 5 Heat exchanger 6 Delivery temperature sensor NTC 7 8 Flue gas backflow sensor Limiter thermostat 9 Deflector 10 Purging screw 11 11 Pilot flame pipe 12 12 Magnetic va...

Page 6: ...temperature controller 5 30 C Weight kg 22 At 15 C and 1013 mbar Table 1 2 General instructions for installation 2 1 Placement of the appliance Make sure that the wall is suitable for mounting the app...

Page 7: ...nt Gas connections The cross section of the connecting pipe must be at least the same or bigger than of the gas pipe in the boiler A closing fitting must be mounted before the appliance The furnace ca...

Page 8: ...if the boiler is placed into a cabinet then it is to be built from floor to ceiling its walls and door must be made of non burnable material If possible its door should be gridded 2 4 Flue gas piping...

Page 9: ...hed wall socket placed beside the appliance or in case of a bathroom in zone 3 and connect it to the electric network of the house Max current drain of the boiler is not bigger than 1Amper Attention T...

Page 10: ...rent input e g Floor heating module electronic temperature controller etc mains input can be connected from points 5 and 6 which inputs stop when the mains plug of boiler is disconnected Table 1 Sign...

Page 11: ...a request for heating on the part of room thermostat Turn potentiometer located on electronic panel and marked P1 by a screwdriver while checkig the display As a result of adjustment display changes f...

Page 12: ...in burner Cause of failure can be Minimum required quantity of water is not provided Temporary lack of water in the leaking heating system Notes Above 91 C the electronics consider thermistor dead sho...

Page 13: ...ce is to be modified for operation by the supplied gas SEE CHAPTER ADJUSTMENT FOR ANOTHER TYPE OF GAS gas valve must be opened leakages are to be terminated Mains 230V IN 1 2 3 4 7 8 9 10 11 12 13 141...

Page 14: ...n order to adjust the combined gas valve correctly follow the next steps Connect a pressure gauge to stub C after loosening of closing screw Pressure of connecting gas can be measured on stub E in cas...

Page 15: ...r 10 and the label on back panel 11 Adjustment from LPG to natural gas After loosening the screw M 4x8 remove the flame trap 3 altogether with the pilot flame pipe 4 After loosening of other fixing sc...

Page 16: ...er is PROHIBITED Maintenance is not an action of guarantee 3 Instructions for use and maintenance for users First installation of the appliance may only be made by an expert of the service network of...

Page 17: ...rotective heating operates until 25 C DWT Reaching this value the boiler stops after 1 minute of post circulation Notes frost protection starts to operate only when the gas supply of boiler is ensured...

Page 18: ...pliance every five years ATTENTION The boiler has got a flue gas backflow sensor When it starts operation the boiler stops automatically Restart can only be made by manual ignition of pilot flame Disa...

Reviews: