When using the generator with a pure inductive load, the pure inductive load cannot exceed the rated power of the generator.
The power can only run 40% to 75% of rated power on pure inductive load.
Model
FG1600i-A
Rated Power (W)
1000
Frequency
(
Hz
)
50
Power Factor
(
cosΦ
)
1.0
AC
Resistive Load 100%
0-1000W
Inductive Load 40%~75%
0-400W~750W
DC
60W(12V\5A)
Rated Power Output Conditions of the Generator
Altitude: 0 meter; Ambient temperature: 25
℃
; Relative humidity:30%
Only in the specified cooling and ambient temperature, the generator can be loaded to the rated power. If the operating
conditions do not meet the requirements of the standard, or the generator or engine cooling is poor (in a limited area),
then the generator power should be reduced.
Ambient temperature coefficient:
℃
(
Relative humidity 30%
)
Altitude (m)
Ambient temperature (
℃
)
25
30
35
40
45
0
1
0.98
0.96
0.93
0.90
500
0.93
0.88
0.83
0.78
0.73
1000
0.87
0.82
0.77
0.72
0.67
2000
0.75
0.70
0.65
0.60
0.55
3000
0.64
0.59
0.54
0.49
0.44
4000
0.54
0.49
0.44
0.39
0.34
Note:
When the relative humidity is 60%, the ambient temperature improvement factor is C-0.01
When the relative humidity is 80%, the ambient temperature improvement factor is C-0.02
When the relative humidity is 90%, the ambient temperature improvement factor is C-0.03
When the relative humidity is 100%, the ambient temperature improvement factor is C-0.04
For example
:
When the rated power of the generator is PN
=
1.0 KW, the altitude is 1000m, the ambient temperature is 35
℃
, the relative
humidity is 80%. Under these circumstances, the rated output of the generator is P=PN×(C-0.02) =1.0×(0.77-0.02)=0.75KW
Use of DC Power
DC socket only supplies for 12V automatic battery charging.
NOTICE
When using a DC socket to charge the battery, the person must be present to monitor the
battery voltage. If the battery voltage exceeds 16V, the charge must be stopped immediately,
otherwise the battery burns or explodes.