background image

05

06

The RTS cable may be pulled through conduit along with the power wires. Tighten the connector screws 
with 5 in-lb (0.56 Nm) torque.

NOTE:

 The RTS is optional package. Please check local dealer for the details.

3.7 Battery Voltage Sense

CAUTION:

 The controller will not activate temperature compensate charging function

 

if the RTS is not used.

CAUTION: Equipment Damage

Never place the temperature sensor inside a battery cell. Both the RTS and the battery will be damaged.

NOTE:

 The RTS cable may be shortened if the full length is not needed.

The voltage at the battery connection on the controller may differ slightly from the voltage directly at the battery 
bank terminals due to connection and cable resistance. The Battery Voltage Sense connection enables the 
controller to measure the battery terminal voltage precisely with small gauge wires that carry very little current, 
and thus have no voltage drop. Both battery voltage sense wires are connected to the 2-pole terminal inside 
of wiring box (see figure as below). 

Be careful to connect the battery positive (+) terminal to the voltage sense positive (+) terminal and battery 
negative (-) terminal to the voltage sense negative terminal (-). No damage will occur if the polarity is reversed, 
but the controller cannot read a reversed sense voltage.

A battery voltage sense connection is not essential required to operate your controller,

 

but it is recommended 

for best performance. The battery voltage sense will ensure

 

that the voltage display in LCD is very accurate.

The voltage sense wires should be cut to length as required to connect the battery to

 

the voltage sense terminal. 

The wire size can range from 16 to 24 AWG (1.0 to 0.25mm2). A twisted pair cable is recommended but not 
required. Use UL rated 300 Volt

 

conductors. The voltage sense wires may be pulled through conduit with the 

power

 

conductors. Tighten the connector screws with 5 in-lb (0.56 Nm) torque.The maximum length allowed 

for each battery voltage sense wire is 98 ft (30 m).

Connect terminals by following below steps (Refer to diagram above):

1. Make sure that the system input and output disconnect switches are both turned

 

off before connecting 

    power wires to the charger. There are no disconnecting switches inside the charger.

2. Make 4 power wires first. Remove insulation sleeve 10.5mm and the conductor should be plated Tin. 

    Refer to the chart below.

3. Pull all wires into the wiring box.  The Remote Temperature Sensor and Battery Sense wires can be

     inside the conduit with the power conductors. It is easier to pull RTS and Sense wires before the power 

     cables.

10.5mm

Tin Plating

WARNING: Risk of Damage

Be sure that the battery connection is made with correct polarity. Turn on the battery breaker/disconnect 
and measure the voltage on the open battery wires BEFORE connecting to the controller. Disconnect the 
battery breaker/disconnect before wiring to the controller.

4. Connect positive terminal (+) of battery to the battery positive terminal (+) on the controller.
5. Connect negative terminal (-) of battery to one of the Common Negative terminals (-) on the controller.

WARNING: Risk of Damage

Be sure that solar connection is made with correct polarity. Turn on the solar breaker/disconnect and measure 
the voltage on the open wires BEFORE connecting to the controller. Disconnect solar breaker/disconnect 
before wiring to the controller.
6. Connect positive wire (+) of solar module to the solar positive terminal (+) on the controller.
7. Connect negative wire (-) of solar module to one of the Common Negative terminals
(-) on the controller.
8. Screw four (4) power terminals tightly with 50 in-lbs torque. (5.65 Nm)

3.5 Grounding and Ground Fault Interruption

Use a copper wire to connect the grounding terminal in the wiring box to earth ground.The grounding terminal 
is identified by the ground symbol shown below that is

 

stamped into the wiring box just below the terminal:

The minimum size of the copper grounding wire is 8 AWG (10 mm2).

WARNING: Risk of Fire

DO NOT bond system electrical negative to earth ground at the controller.

The included Remote Temperature Sensor (RTS) is recommended for effective temperature compensated 
charging. Connect the RTS to the 2-pole terminal (see figure as below). The RTS is supplied with 33 ft (10 m) 
of 22 AWG (0.34 mm2) cable. There is no polarity, so either wire (+ or -) can be connected to either 
screw terminal.

3.6 Remote Temperature Sensor

MPPT solar charge controller

MPPT solar charge controller

Summary of Contents for MPPT

Page 1: ...USER GUIDE MPPT solar charge controller MPPT solar charge controller Make life full of hope 358 010003 04 ...

Page 2: ... 6 4 OPERATION 7 4 1 Power Up 7 4 2 Operation and Display Panel 7 4 3 LCD Display Icons 8 4 4 LCD setting 9 12 4 5 Reference Code 12 5 CHARGING LOGIC 13 5 1 3 stage Charging 13 5 2 Equalize Stage 14 5 3 Setting Parameter and Default Value 15 6 TROUBLE SHOOTING 16 7 SPECIFICATIONS 17 18 8 MPPT charger controller match to the Inverter 19 8 1 Match the inveter to the MPPT controller 19 8 2 Matching M...

Page 3: ...rt circuit batteries or other electrical parts and could cause an explosion 8 Please strictly follow installation procedure when you want to disconnect PV or battery terminals Please refer to Installation section of this manual for the details 9 GROUNDING INSTRUCTIONS This charger should be connected to a permanent grounded wiring system Be sure to comply with local requirements and regulation to ...

Page 4: ...below 3 1 Unpacking and Inspection Consider the following points before selecting where to install This solar charge controller is designed in IP31 for indoor applicationsonly Do not mount the unit on flammable construction materials Mount on a solid surface Install this charger at eye level in order to allow the LCD display to be read at all times For proper air circulation to dissipate heat allow...

Page 5: ...ct switches are both turned off before connecting power wires to the charger There are no disconnecting switches inside the charger 2 Make 4 power wires first Remove insulation sleeve 10 5mm and the conductor should be plated Tin Refer to the chart below 3 Pull all wires into the wiring box The Remote Temperature Sensor and Battery Sense wires can be inside the conduit with the power conductors It i...

Page 6: ... A battery must be connected to the controller before operating it The controller will not operate only with solar input Solar input can trigger the controller to start up when the battery is connected without pressing the button Turn on battery disconnect switch first And press operation button for a while Then it will indicate a successful start up in LCD display Turn on solar disconnect switch I...

Page 7: ...arameter 05 is set as one of 12V 24V 48V If you want to set Lib first set the 05 battery rated voltage MPPT 45A 12 24V can t set theAbsorption voltage to 48v LIb mode can t set the AUO then set 02 to LIb AGM Setting Programs 0 0 Program Description Options Exit setting mode Escape Maximum charging current 0 1 45A Default Setting range is from 30A 45A 60A 80A 100Aor 120A Increment of each short pres...

Page 8: ...each short press is 0 1V The value will jump back to 12 0V after 15 5V is achieved If this program is selected to modify the changeable figure will be shown as below 1 0 The maximum current of battery equalization 15A Default The setting range is from 30A 45A 60A 80A 100Aor 120A Increment of each short press is 1A The value will jump back to 30A 45A 60A 80A 100A or 120A is achieved 0 6 Battery C V ...

Page 9: ...arge stage charge current begins to flow typically at the maximum rate of the charge source The controller will supply solar power to charge battery as much as possible 2 Absorption stage When battery charging voltage is reached to Absorption voltage point the charging stage changes from bulk charge to Absorption Constant voltage regulation is used to maintain battery voltage at the Absorption stag...

Page 10: ...ill supply solar power to charge battery as much as possible until battery voltage raises to battery equalization voltage Then constant voltage regulation is applied to maintain battery voltage at the battery equalization voltage The battery will remain in the Equalize stage until setting battery equalized time is arrived Equalize charging time and timeout ABSORPT BULK FLOAT Equalize Voltage EQUAL...

Page 11: ...ns Maximum Solar Input Voltage 12VDC 24VDC 48VDC PV Array MPPT Voltage Range Maximum Input Power 12V 625W 12V 625W 12V 825W 12V 1100W 12V 1375W 12V 1650W 24V 1250W 24V 1250W 24V 1650W 24V 2200W 24V 2750W 24V 3300W 48V 2500W 48V 3300W 48V 4400W 48V 5500W 48V 6600W MODEL Maximum Battery Current Nominal System Voltage 30Amps 45Amps 45Amps 60Amps 80Amps 100Amps 120Amps 12V 24V 48V DC Auto detection 14...

Page 12: ...nverter it needs to disable the function matching MPPT first 2 Limited the charging current of the inverter The methods are as follows a When the MPPT charging current inverter setting charging current the maximum allowable charging current of the inverter equal to 0 b When the MPPT charging current inverter setting charging current themaximum allowable charging current of the inverter equal to inv...

Reviews: