1.12 Configuration menu (cont.)
The ‘UP’ (
5
) key at the front of the instrument gives access to a list
of functions configurable by the operator. See section
for an ex-
planation on how to operate the ‘
fast access
’ menu.
the ‘
Key UP (Fast access)
’ (‘
K.uP
’) menu allows to select which func-
tions will be accessible through the ‘fast access’ menu. Select ‘
on
’ to
activate each function.
• the ‘
Setpoint
1
’ (‘
ALr1
’) function allows to visualize and modify the
alarm
1 setpoint through the ‘fast access’ menu.
• the ‘
Setpoint
2
’ (‘
ALr2
’) function allows to visualize and modify the
alarm
2 setpoint through the ‘fast access’ menu.
• the ‘
Setpoint
3
’ (‘
ALr3
’) function allows to visualize and modify the
alarm
3 setpoint through the ‘fast access’ menu.
• the ‘
Memory of maximum
’ (‘
MAX
’)
or
‘
Memory of minimum
’
(‘
MIn
’) functions allow to visualize the maximum or minimum read-
ing value stored in memory. To reset this value, visualize the memory
value at the ‘fast access’ menu with key UP (
5
) and when message
‘
rSt
’ is displayed, press (
<
) to reset.
• the ‘
Measure
’ (‘
MEAS
’) function allows to visualize the actual sig-
nal at input terminals, without scaling. Example : with an instrument
with input 0/10
Vac, and with reading scaled to 0/750.0, the ‘
mea-
sure
’ function will show the direct value in Vac, without the scaling.
1.12.5 Fast access
If only a single function is selected for the ‘fast access’ menu, press-
ing the the ‘UP’ (
5
) key will shortly display the function name and
then automatically jump to the function value.
1.12.6 Super fast access
On power-up
Delay
Seconds
the ‘
On Power Up
’ (‘
on.Pu
’) menu configures functions to apply at
start-up. It applies only to instrument restart after power loss. It does
not apply to instrument restart due to change in configuration.
• parameter ‘
Delay
’ (‘
dLAy
’) assigns a waiting time in seconds. The
instrument waits the configured time before starting normal func-
tion. During this waiting time, the display shows all decimal points
on in flash mode, all alarms are in ‘oFF’ state, there is no signal acqui-
sition and there is no communications or control being performed.
After the configured time is over, the instrument starts in normal
function. Delay value between 0 and 200 seconds.
Application - the start-up process for an automation system implies
that different parts of the system (engines, actuators, controllers, ...)
have different start-up times. The ‘Delay’ function gives time to the
instrument to wait until the slowest part of the system is fully func
-
tional before executing actions on the system (signal reading, relay
activation, ...)
1.12.7 Menu ‘On Power Up’