FEMA ELECTRÓNICA . Series M . M40-A
15
This instrument has been designed and verified conforming to the 61010-1
CE Security Regulation, for industrial applications.
Installation of this instrument must be performed by qualified personnel
only. This manual contains the appropriate information for the installation.
Using the instrument in ways not specified by the manufacturer may lead to
a reduction of the specified protection level. Disconnect the instrument from
power before starting any maintenance and / or installation action.
The instrument does not have a general switch and will start operation as
1.16 Precautions on installation
Risk of electrical shock. Instrument terminals can be connected
to dangerous voltage.
Instrument protected with double isolation. No earth connection
required.
Instrument conforms to CE rules and regulations.
1.17 Factory configuration
Manufacturer FEMA ELECtrÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 - Barberà del Vallès
BArCELONA - SPAIN
www.fema.es - info@fema.es
Products
M40-A
The manufacturer declares that the instruments indicated comply with the
directives and rules indicated below.
Directive of electromagnetic compatibility 2004/108/CEE
Directive of low voltage 73/23/CEE
Security rules 61010-1
Instrument
Fixed
Permanently connected
Pollution degree 1 and 2 (without condensation)
Isolation
Double
Category
CAT-III up to 300 Vac
CAt-II up to 600 Vac
Emission rules
61000-6-4
Generic rules of emission
Immunity rules
61000-6-2
Generic rules of immunity
61000-4-2
By contact ±4 KV - Criteria B
By air ±8 KV - Criteria B
61000-4-3
Criteria A
61000-4-4
On AC power lines : ±2 KV - Criteria B
On DC power lines : ±2 KV - Criteria B
On signal lines : ±1 KV - Criteria B
61000-4-5
Between AC lines ±1 KV - Criteria B
Between DC lines ±0.5 KV - Criteria B
61000-4-6
Criteria A
61000-4-8
30 A/m a 50 Hz - Criteria A
61000-4-11
0 % 1 cycle - Criteria A
40 % 10 cycles - Criteria A
70 % 25 cycles - Criteria B
0 % 250 cycles - Criteria B
Barberà del Vallès September 2011
Daniel Juncà - Quality Manager
1.18 Warranty
1.19 CE declaration of conformity
this instrument is warranted against all manufacturing defects for a
period of 24 MONTHS from the shipment date. This warranty does
not apply in case of misuse, accident or manipulation by non-autho-
rized personnel. In case of malfunction get in contact with your local
provider to arrange for repair. Within the warranty period and after
examination by the manufacturer, the unit will be repaired or substi-
tuted when found to be defective. The scope of this warranty is lim-
ited to the repair cost of the instrument, not being the manufacturer
eligible for responsibility on additional damages or costs.
Scale
0/600 Vac
Scaling and decimal point
0/600 Vac = 0/600.0
Alarms 1,2 and 3
Active
off (disabled)
Type
alarm as maximum
Setpoint
1000
Hysteresis
0 counts
Activation delay
0.0 seconds
Deactivation delay
0.0 seconds
Setpoint 2
off
Inverted relay
off
Locked alarms
off
Display
Fixed digits
off
Average
off
Steps
off
Left zeros
off
Dummy zero
off
Maximum memory
-9999
Minimum memory
9999
Peak&Hold
off
tools
‘Fast access’
off
‘On power-up’
Delay
0 seconds
Key LE
no function
Password
off
Brightness
3
soon as power is connected. The instrument does not have protection fuse,
the fuse must be added during installation.
The instrument is designed to be panel mounted. An appropriate ventilation
of the instrument must be assured. Do not expose the instrument to excess
of humidity. Maintain clean by using a humid rag and do NOT use abrasive
products such as alcohols, solvents, etc.
General recommendations for electrical installations apply, and for proper
functionality we recommend : if possible, install the instrument far from
electrical noise or magnetic field generators such as power relays, electrical
motors, speed variators, ... If possible, do not install along the same conduits
power cables (power, motor controllers, electrovalves, ...) together with sig-
nal and/or control cables.
Before proceeding to the power connection, verify that the voltage level
available matches the power levels indicated in the label on the instrument.
In case of fire, disconnect the instrument from the power line, fire alarm
according to local rules, disconnect the air conditioning, attack fire with car-
bonic snow, never with water.