background image

FEMA ELECTRÓNICA - Page 7

User¨s Manual - Series MAG983-X

Manufacturer.-

FEMA ELECTRÓNICA, S.A.

Address      .- Pol. Ind. Santiga - Altimira 14 (T14 - N2)

E-08210 Barberà - BARCELONA
ESPAÑA - SPAIN

Conforming products
Model    .-

MAG983-1, MAG983-2, MAG983-3, MAG983-4

We hereby declare that the above products conform to the
essential protection requirements of Directives and
Harmonised Standards stated below

.

Signed  .-

D. Juncà

Position.-

Quality Manager

Place   .-

Barberà,  2005

DIRECTIVES

EUROPEAN DIRECTIVE FOR LOW VOLTAGE D73/23/CEE AMENDED BY D93/
68/CEE

. Equipments powered from 50 to 1000 Vac. and / or from 75 to 1500 Vdc.

ELECTROTECHNICAL REGULATION FOR LOW VOLTAGE (RBT) ITC21,
ITC29, ITC35. 

Equipments with power supply lower than 50 Vac and/or 75 Vdc.

EUROPEAN DIRECTIVE FOR ELECTROMAGNETIC COMPATIBILITY D89/
336/CEE AMENDED BY D93/68/CEE

STANDARDS

IMMUNITY

UNE EN 50082-1 (1998)

EMISSIONS

UNE EN 50081-1 (1994)

ELECTRICAL SAFETY

UNE EN 61010-1 (1996)
UNE EN 60204-1 (1997)

DECLARATION OF CONFORMITY

14.- Security Prescriptions ____________________________________________________

15.- Declaration of Conformity__________________________________________________

INSTALLATION PRECAUTIONS

.- The installation

and use of this unit must be done by qualified
operators. The unit has not power switch, and 

the

unit has not internal protection fuse

, and will start operation as

soon as power is connected. The installation must incorporate an
external main switch with a protection fuse of :

fuse 50 mA (at 230 Vac power)

Also the necessary devices to protect the operator and the process
when using the unit to control a machine or process where injury to
personnel or damage to equipment or process, may occur as a result
of failure of the unit.

SAFETY PRESCRIPTIONS

.- The unit has been designed and

tested under UNE 20553 rules and is delivered in good
condition. This manual contains information for electrical
connections. Do not make wiring signal changes or connec-

tions when power is applied to the unit. Make signal connections
before power is applied and, is reconnection is required, disconnect
the AC (mains) power before such wiring is attempted. Install the unit
in  places with a good ventilation to avoid the excessive heating. And
far from electrical noise source or magnetic field generators such as
power relays, electrical motors, speed controls etc... The unit cannot
be installed in open places. Do not use until the installation is finished.

POWER SUPPLY

.- The power supply must be connected to the

adequate terminals  (see the connection instructions). The charac-
teristics of the power supply are written on the attached label. Please
make sure that the unit is correctly connected to a power supply of
the correct voltage and frequency. Do not use other power supply
otherwise permanent damage may be caused to the unit. Do not
connect the unit to power sources heavily loaded or to circuits which
power loads in cycle ON-OFF or circuits with power inductive loads.

SIGNAL WIRING

.- Certain considerations must be given when install

the signal input and control wires.  Long wires can act like antennas
and introduce electrical noise to the unit, therefore :

A.- Do not install the signal input or control wires in the same

conduit with power lines, heaters, solenoids, SCR controls etc....and
always far from these elements.

B.- When shielded wires are used, connect the shield to the

common terminal and leave unconnected the other end of the shield
and do not connect to the machine ground.

EXCITATION VOLTAGE

.- The unit supplies exci-

tation voltage for sensors, at terminals 3 and 4. Do
not connect these terminals to external power
supply, permanent damages may result to the unit.

SAFETY CONSIDERATIONS

 .- Before starting any operation of

adjustment,  replacement,  maintenance or repair, the unit must be
disconnected from the power supply. Keep the unit clean , to assure
good functioning  and performance. To prevent electrical or fire
hazard, do not expose the unit to excessive moisture.  Do not operate
the unit in the presence of flammable gases or fumes, such as
environment constitutes a definite safety hazard. The unit is de-
signed to be mounted in a metal panel.

If the unit shows signs of damage, or is not able to show the expected
measures, or has been stored in a bad conditions or a protection
failure can occur, then do not attempt to operate and keep the unit
out of service.

IN CASE OF FIRE

1.- Disconnect the unit from the power supply.
2.- Give the alarm according to the local rules.
3.- Switch off all the air conditioning devices.
4.- Attack the fire with carbonic snow, do not use water in any case.

WARNING : In closed areas do not use sys-
tems with vaporized liquids.

CONNECTIONS

All wiring connections are made using push-in cable connectors.
There is a separate connector block for power supply, input signals
and each relay output. Please make sure that each connector block
is connected on the adequate place.

PANEL MOUNTING

.- The instrument size case is 1/8 DIN. The

internal electronic circuit can be inserted or removed by the front part
and is held on to the case by the two lateral lugs, which must be put
in their corresponding holes placed on each case side. Verify that
the panel cut-out is correctly according to the dimensions indicated
with a minimum depth of 135 mm. (5.31"). Install the fixation clips of
blue colour in the lateral guides of the unit by its rear part and then
slide and press them firmly against the panel, until the unit is totally
hold on.

Summary of Contents for MAG983 Series

Page 1: ...NICA COUNTERS for IMPULSES USER S MANUAL HT0695 r050705 Series MAG983 X IDEAL SOLUTION for impulse counting applications where the operator has no access to the configuration of the unit Instruments w...

Page 2: ...ions on section 8 for self configuration 0 Ordering Reference ____________________________________________________ 1 Technical Data________________________________________________________ DISPLAYS Led...

Page 3: ...Connections for POWER SUPPLY Connections for RESET RESET Common The rear side of the instrument shows the terminals for connecting signals power of the instrument and contact for RESET and the jumper...

Page 4: ...rminals 6 Vexc 4 Signal 7 4 Sensor Type PICKUP Select Jumpers AE INPUT1 terminals 5 Signal y 3 Common INPUT2 terminals 6 Signal y 3 Common Note Input2 will be Mechanical Contact It can not be configur...

Page 5: ...oseoneaftertheother contacts 6 5 2 and E Contact 6 Number 6 appears on display 6 Contact 5 Number 5 appears on display 65 1 Together with code 65 appears also the number 1 indicating that code 65 alre...

Page 6: ...half 12 Decimal Point Position_________________________________________________ 46 1E 0 Note The same codes but with negative allow 46 2E 0 0 visualization of zeroes to the left For example 46 3E 0 0...

Page 7: ...s correctly connected to a power supply of the correct voltage and frequency Do not use other power supply otherwise permanent damage may be caused to the unit Do not connect the unit to power sources...

Page 8: ...CELONA ESPA A SPAIN Tel 34 93 729 6004 www fema es Fax 34 93 729 6003 info fema es more products ELECTRONIC INSTRUMENTATION FOR INDUSTRY www fema es Large Displays for TIME Miniature Panel Meters Stan...

Reviews: