Smart DCM/SN 

ELECTRONIC PRESSURE SWITCHES AND TRANSMITTERS 

 

OPERATING INSTRUCTIONS 

GENERAL 

Honeywell FEMA's Smart DCM Electronic Pressure Switches 
and Smart SN Electronic Pressure Transmitters are micro-
processor-controlled pressure measurement devices for 
relative pressure measurements (-1…+1 bar / 0…40 bar). 
With their high-performance stainless steel sensor material, 
they are suitable for a wide range of liquid media or gases in 
industrial applications. They are screwed (G1/2”) directly into 
the line / vessel to be monitored. 
 

 BEFORE PROCEEDING! 

VALIDITY 

These Operating Instructions pertain to measuring systems 
containing Smart SN Pressure Transmitters / DCM Pressure 
Switches. Device software must be version 1.30 or higher. 
 

QUALIFIED PERSONNEL AND USAGE 

Use only these Operating Instructions (and the corresponding 
Mounting Instructions) to set up and operate the device. Only 
qualified personnel are permitted to install, commission, 
operate, and maintain the device. This device may be used 
only in applications and under operating conditions described 
in these Operating Instructions. 
 

TECHNICAL DATA 

Materials 

Parts contacting medium 

Stainless steel (1.4571) 

Chemical resistance 

4C4 as per EN 60721-3-4 

HMI PA66 

GF25 

Total weight 

300 g without, 350 g with HMI 

 

Ambient (operating) temperature and humidity 

Versions (non-HMI) 

-20...+80 °C 

Versions (HMI) 

-20...+70 °C 

Humidity 

0...95% r.h., non-condensing 

Temperature of medium 

-30...+100 °C (

 16 bar models) 

-40...+100 °C (> 16 bar models) 

 

Storage temperature 

Versions (non-HMI) 

-40...+80 °C (

 16 bar) 

-40...+100 °C (> 16 bar) 

Versions (HMI) 

-30...+80 °C 

 

Climate class 

Indoors 

4K4H as per EN 60721-3-4 

Outdoors 

3K8H as per EN 60721-3-3 

 

Mechanical stability 

Vibration 

20 g as per IEC 68-2-6 (up to 
2000 Hz) 

Mechanical shock 

100 g as per IEC 68-2-27 

Device resistance / accuracy (combined non-linearity, 
hysteresis, and repeatability at 20 °C) 

 

 16 bar 

P > 16 bar 

overpressure safety 

2x P

nominal

 2x 

P

nominal

 

burst pressure 

4x P

nominal

 10x 

P

nominal

 

sensor type 

piezo 

thin-film 

accuracy 

max. ±0.8% FS 
±0.5% FS (typ.) 

max. ±1% FS 
±0.6% FS (typ.) 

 

Pressure meas. range

 

0…40 bar (rel.), -1…1 bar (vac.) 

Cycle time

 100 

ms 

 
EMC 

according to EN 61326 

Protection class 

2 as per EN 61010 

Protection rating (non-HMI)  IP67 as per EN 60529-2 
Protection rating (HMI) 

IP65 as per EN 60529-2 

Process connection 

G1/2" external thread 

Electrical connection 

4-prong A-coded M12x1 plug 

 

Switch 

Output, high level 

V

SUPPLY

 minus 2 V (min.) 

Output, low level 

GND plus 0.5 V (max.) 

Reaction time 

max. 300 ms 

 

WARN output voltage

 passive: 

V

SUPPLY

 - 2 V 

 active: 

 0.5 V 

 

Transmitter (analog) output 

Current (2-wire) 

4…20 mA 

Voltage / current (3-wire) 

0/2...10 V, 0/4...20 mA 

V

SUPPLY

 (2-wire) 

18…35 Vdc 

V

SUPPLY

 (3-wire) 

18…35 Vdc, 24 Vac +10%/-20%, 
max. 50 mA 

Current output (max. load)  (V

SUPPLY

 - 16 V) / 22 mA 

(max. error ±0.25% FS) 

Voltage output (min. load)  15 k

 (max. error ±0.25% FS) 

Transient response 

approx. 200 ms 

 

Span, offset, and long-term drift (within temperature 
compensation range of 0…80 °C) 

 

max. 

typical 

temp. effect on span 

±0.3% FS / 10 K  ±0.2% FS / 10 K 

temp. effect on offset 

±0.3% FS / 10 K  ±0.2% FS / 10 K 

long-term drift* 

±0.3% FS / year  ±0.2% FS / year 

 

Summary of Contents for Smart DCM

Page 1: ...0 95 r h non condensing Temperature of medium 30 100 C 16 bar models 40 100 C 16 bar models Storage temperature Versions non HMI 40 80 C 16 bar 40 100 C 16 bar Versions HMI 30 80 C Climate class Indo...

Page 2: ...here the device will check the plausibility of your values and if necessary redirect you back to the PARAMETRIZATION LEVEL and The CONFIRMATION LEVEL where you can review your edited values before per...

Page 3: ...to local ambient atmospheric pressure and to compensate for drift To use this function properly the device must be mounted in the application and the pressure sensor exposed to local ambient atmosphe...

Page 4: ...e simulation mode is started No The device remains in its normal operating mode The default setting is No WARNING After you have completed testing in the simulation mode do not forget to return to thi...

Page 5: ...250 mA the load is disconnected and the WARN output is set to 0 5 V in a loop Table 2 DCM Switch functions and definitions definition function equa tion active inactive max monitor N O 1 closed open m...

Page 6: ...ausibility of your values and if necessary redirect you back to the PARAMETRIZATION LEVEL and The CONFIRMATION LEVEL where you can review your edited values before permanently storing them START SCREE...

Page 7: ...2 Wire Trans mitter is 4 20 mA However it can be inverted to 20 4 mA see section Function below FUNCTION Here you can invert the device s function see also Fig 15 Non invert the mode current range or...

Page 8: ...e contrast is increased to its maximum value The default setting is Mean EXTRAS SIMUL SIMULATION MODE The simulation mode allows the user to test the device within the application without actually app...

Page 9: ...passive 0 mA 3 Wire 0 10 V passive 0 V The output limits of the device s outputs at overpressure and underpressure are as follows Table 4 SN Transmitter output limits at over underpressure device out...

Page 10: ...er The Y axis displays the generated output in the range according to the output definition see Fig 15 on page 7 and Table 5 on page 9 DCM SWITCH Measuring pressures is the safety function of the dire...

Page 11: ...output pin 2 If due to miswiring or electronic failure the signal output cannot reach the desired high failure state it will auto matically go to the low failure state Table 6 SN Transmitter error rep...

Page 12: ...ontact FEMA 6 Device memory check failure R U Hardware reset as described above Contact FEMA 7 Device program flow failure R U If unrecoverable Contact FEMA 8 Environment too hot or electronics failur...

Page 13: ...sionen mit HMI 20 70 C Rel Luftfeuchtigkeit 0 95 nicht kondensierend Mediumtemperatur 30 100 C 16 bar Modelle 40 100 C 16 bar Modelle Lagertemperatur Versionen ohne HMI 40 80 C 16 bar 40 100 C 16 bar...

Page 14: ...ener Einstellwerte PR FBEREICH berpr fung auf korrekte Eingabe und ggfls Zur ckstufung in den PARAMETRISIERUNGS BEREICH und BEST TIGUNGSBEREICH Nochmalige Best tigung der Einstellwerte bevor sie dauer...

Page 15: ...st N O AUTO ZERO Die auto zero Funktion erm glicht es dem Anwender das Ger t entsprechend den lokalen atmosph rischen Druck verh ltnissen einzustellen sowie die Drift auszugleichen Um diese Funktion r...

Page 16: ...das Ger t wieder in Sicherheitsanwendungen eingesetzt werden Yes Der Simulationsmodus wird aufgerufen No Das Ger t bleibt in seiner normalen Betriebsart Die Werkseinstellung ist No VORSICHT Nach Absc...

Page 17: ...annungsversorgung gestellt Falls der Strom immer noch h her als 250 mA ist wird die Last getrennt und der WARN Ausgang auf 0 5 V in eine Schleife gestellt Tabelle 2 DCM Funktionen und Definitionen Def...

Page 18: ...ung auf korrekte Eingabe und ggfls Zur ckstufung in den PARAMETRISIERUNGS BEREICH und BEST TIGUNGSBEREICH Nochmalige Best tigung der Einstellwerte bevor sie dauerhaft gespeichert werden STARTANZEIGE B...

Page 19: ...tiert werden siehe Abschnitt Function Funktion unten FUNCTION FUNKTION Hier k nnen Sie die Ger tefunktion invertieren siehe auch Abb 15 Non invert der Modus Strom bzw Spannungsbereich wird auf 0 4 20...

Page 20: ...Simulationsmodus erm glicht es dem Anwender die reibungslose Funktion des Ger ts zu pr fen ohne das System unter Druck zu setzen Nach Aufrufen des Simulationsmodus sind die Diagnostik funktionen nicht...

Page 21: ...V passiv 0 V Die Ausgangsgrenzen der Ger teausg nge bei ber und Unterdruck sind wie folgt Tabelle 4 SN Transmitter Ausgangsgrenzen bei ber und Unterdruck Ger t Ausgangs signal bereich min Ausgangs gre...

Page 22: ...te besteht darin Dr cke zu messen Je nach dem wie das Ger t eingestellt ist l t es sich mit einer Genauigkeit von 5 als Max Min oder Window W chter Schalter ausgang und WARN Ausgang betreiben Wenn di...

Page 23: ...er automatisch in den niedrigen Fehlerzustand fallen Tabelle 6 SN Transmitter Fehlermeldung Fehlermeldung Modell Aus gangs signal Bereich prim rer hoher Fehler zustand sekund rer niedriger Fehler zust...

Page 24: ...ntaktieren 6 Speicherpr fung fehlgeschlagen B NB Wie oben beschrieben Hardware Reset durchf hren FEMA kontaktieren 7 Programmlauffehler B NB Falls nichtbehebbar FEMA kontaktieren 8 Umgebung zu hei ode...

Reviews: