background image

MIKRO P7 - P12

21

EN

cod. 3540T988  -  Rev. 01  -  01/2014

3.3 Electrical connections

The burner is equipped with a multi-pole terminal block for the electrical connections; re-
fer to the wiring diagram in section “

4 Technical data and characteristics

" for the con-

nections. The connections to be made by the installer are:

Supply line

Request contact

Auger motor connection

Temperature probe connection

Boiler safety thermostat connection

The length of the connection cables must allow the burner and, if necessary, the boiler
door to be opened. If the burner power cable is damaged, it must only be replaced by
qualified personnel.

The burner must be connected to a single-phase 230 Volt-50 Hz electric line.

B

Have the efficiency and suitability of the earthing system checked by profes-
sionally qualified personnel; the Manufacturer declines any liability for damage
caused by failure to earth the system. Also make sure the electrical system is
adequate for the maximum power absorbed by the unit, as specified on the boil-
er data plate.

Make sure to respect the polarities (LINE: brown wire / NEUTRAL: blue wire /
EARTH: yellow-green wire) in the connections to the electric line.

3.4 Fuel supply

General Instructions

The burner must be fed with the type of fuel for which it is arranged, as specified on the
unit's dataplate and in the technical data table on sec. 5.3 of this manual.

The user is advised to use good quality pellets, since low quality pellets result in low heat
outputs, high ash content with subsequent need of frequent cleaning, possible early wear
of burner parts exposed to the fire, clogging of the auger and burner due to excess loose
sawdust, and operation shutdowns due to sedimentation of unburnt materials inside the
burner.

To identify quality pellets it is advisable to proceed as follows:

They must be cylinders of constant diameter and have a smooth and bright surface.

Check that the labels give the details of the quality certifications

Check that the packs are intact so that the pellets do not absorb humidity.

Load pellets

Pellet  loading  can  be  activated  within  40  minutes  after  switching  on  the  power  to  the
burner.

Within this time, the system makes available three 5-minute attempts, during which only
the auger is activated.

The burner cannot be lit during pellet loading.

Sequence:

1.

Switch on the power to the burner.

2.

Wait for the pre-ventilation stage to end.

3.

Remove the burner lighting request: open the request contact (Method A, default
setting) or set the manual OFF mode (Method B and C).

4.

Press and hold down the Override button “x->” (detail 3 - fig. 1) for 3 seconds.
- The message "PELt", identifying the imminent start of the PELLET loading proce-
dure, will be displayed.
- After two seconds, the auger will be electrically powered and continuously for a
maximum time of 5 minutes.
- PELLET loading can be terminated at any time by pressing and holding down the
Override button “x->” (detail 3 - fig. 1) for 3 seconds.

5.

If the maximum pellet loading time (5 minutes) is reached, the power to the auger is
switched off.

6.

Press and hold down the Override button “x->” (detail 3 - fig. 1) for 3 seconds.
- The message "PELt" will disappear and the display returns to normal operation.

7.

If the first attempt was not sufficient, repeat the previous sequence from point 4 to
start the second attempt

8.

If the second attempt was not sufficient, repeat the previous sequence from point 4
to start the third and last attempt

9.

In order to do another 3 attempts, switch the power to the unit off and then on again

10. After  pellet  loading,  reinstate  the  burner  lighting  request:  close  the  request  contact

(Method A, default setting) or set the Automatic or manual ON mode (Method B and C)

4. SERVICE AND MAINTENANCE

All adjustment, commissioning and maintenance operations must be carried out by Qual-
ified Personnel in compliance with the current regulations. The personnel of our sales or-
ganisation  and  the  Local  After-Sales  Technical  Service  are  at  your  disposal  for  any
further information.

FER

 declines any liability for damage and/or injury caused by unqualified and unauthor-

ised persons tampering with the unit.

4.1 Burner operation methodology

Three methods of burner ignition management are foreseen:

A - Burner management (default setting)

The request for burner lighting is activated only on closing of the contact on terminals 7-
8 (see fig. 14).

A

The clock and the set weekly programme are bypassed: the exact time does
not have to be set.

B - Burner management (with internal Clock or Contact)

The request for burner lighting can be activated by the Clock (during Automatic Heating
Mode in ON Band or in Manual On Heating Mode) or with closing of the contact on ter-
minals 7-8 (see fig. 14).

A

It is necessary to set the Clock and possibly modify the weekly programme de-
fault setting.

C - Burner management (with internal Clock and Contact)

The request for burner lighting is activated by the Clock (during Automatic Heating Mode
in  ON  Band  or  with  Manual  On  Heating  Mode)  and  if  the  contact  on  terminals  7-8  is
closed (see fig. 14).

A

It is necessary to set the Clock and possibly modify the weekly programme de-
fault setting.

The selection of A, B or C occurs from the Clock user menu.

Press the operation mode selection button "M" (detail 2 - fig. 1) for 5 seconds.

Press the Programming button "P" (detail 5 - fig. 1) twice.

Parameter no. 3, identified by the message SET 03, is displayed.

Set to 00 for mode A, 01 for mode B, or 02 for mode C with the + and - buttons (details
4 and 6 - fig. 1).

After  selecting  the  method, it is  necessary  to wait 3  seconds:  the data  flashes and is
stored. Press the operation mode selection "M" button (detail 2 - fig. 1) for 5 seconds to
exit the menu.

4.2 Commissioning

Checks to be made at first lighting, and after all maintenance operations involving dis-
connection from the systems or any operation on safety devices or parts of the burner:

Before lighting the burner

Make sure the burner is correctly fixed in the boiler with the preliminary settings in-
dicated above.

Make sure the boiler and system are filled with water or diathermic oil, the water cir-
cuit valves are open and that the flue is free and correctly sized.

Check closing of the boiler door, so that the flame is only generated inside the com-
bustion chamber.

Check the correct positioning of the auger and the burner connection flexible tube.

Fill the hopper with pellets.

Check the correct positioning and connection of the temperature probe.

A

Make sure the grille (detail 1 fig. 9) is clean.

fig. 9 - Burner grille

1

Summary of Contents for MIKRO P7

Page 1: ...IKRO P7 P12 IT ISTRUZIONE PER L USO L INSTALLAZIONE E LA MANUTENZIONE ES INSTRUCCIONES DE USO INSTALACI N Y MANTENIMIENTO EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE BG GR SL NAVODILA ZA UPOR...

Page 2: ...otto In questa rappresentazione possono esserci lievi e non significative differenze con il prodotto fornito 2 ISTRUZIONI D USO 2 1 Presentazione Gentile Cliente La ringraziamo di aver scelto MIKRO P7...

Page 3: ...rt 4 e 6 fig 1 per modificare l inizio della 2st fascia oraria di ON esempio 12 30Premere il pulsante Programmazione P part 5 fig 1 7 12 00 e Radiatore lampeggianti 4 Utilizzare i tasti e part 4 e 6 f...

Page 4: ...ne deve essere privo di oggetti o materiali infiammabili gas corrosivi polveri o sostanze volatili che richiamate dal ventilatore possano ostruire i condotti in terni del bruciatore o la testa di comb...

Page 5: ...on sia stato sufficiente ripetere la sequenza pre cedente dal punto 4 per avviare il secondo tentativo 8 Nel caso in cui il secondo tentativo non sia stato sufficiente ripetere la sequenza precedente...

Page 6: ...e il dado C e scollegare il corpo svitare le viti di fissaggio D ed estrarre il boccaglio E fig 10 Verifiche su parti e componenti Ventilatore Verificare che all interno del ventilatore e sulle pale d...

Page 7: ...erale e componenti principali fig 13 Legenda 1 Trasduttore di pressione 2 Centralina 3 Corpo bruciatore 4 Morsettiera 5 Interfaccia utente 6 Resistenza 7 Fotoresistenza 8 Termostato 85 9 Tubo per cari...

Page 8: ...one blocco E Sblocco bruciatore Dati Unit MIKRO P7 MIKRO P12 Portata Termica max kW 34 1 55 0 Q Portata Termica min kW 13 7 30 0 Q Portata Combustibile max kg h 7 2 11 6 Portata Combustibile min kg h...

Page 9: ...i S W n n AA F i n X W in n i i ni n i F i n i i i m n i i i i X W in i n in n i i ni i in i n C i F i n i i i m n i i in i n X W in n i n m i i i ni i i m n i i n iC in i n iA i m n n i n i i X W n...

Page 10: ...Estimado cliente Muchas gracias por elegir MIKRO P7 P12 un quemador FER de dise o avanzado tec nolog a de vanguardia elevada fiabilidad y calidad constructiva MIKRO P7 P12 es un quemador de pellets c...

Page 11: ...0 Pulsar la tecla de programaci n P 5 fig 1 7 12 00 y Radiador parpadeantes 4 Utilizar las teclas y 4 y 6 fig 1 para modificar el inicio de la segunda franja horaria de apagado por ejemplo 14 00 Pulsa...

Page 12: ...tilador puedan obstruir los conductos internos del quemador o el cabezal de combusti n El lugar tiene que ser seco y estar reparado de lluvia nieve y heladas Fijar el quemador a la puerta Efectuar las...

Page 13: ...imer intento no es suficiente repetir la secuencia desde el punto 4 para ini ciar el segundo 8 Si el segundo intento tampoco da resultado repetir la secuencia desde el punto 4 para iniciar el tercero...

Page 14: ...aer la tobera E fig 10 Controles de partes y componentes Ventilador Controlar que la parte interna del ventilador y las palas del rotor no est n sucias de pol vo el polvo reduce el caudal de aire y au...

Page 15: ...y componentes principales fig 13 Leyenda 1 Transductor de presi n 2 Centralita 3 Cuerpo del quemador 4 Regleta de conexiones 5 Interfaz de usuario 6 Resistencia 7 Fotorresistencia 8 Termostato 85 C 9...

Page 16: ...eo del quemador Datos Unidad MIKRO P7 MIKRO P12 Capacidad t rmica m xima kW 34 1 55 Q Capacidad t rmica m nima kW 13 7 30 Q Caudal m ximo de combustible kg h 7 2 11 6 Caudal m nimo de combustible kg h...

Page 17: ...TERMOCLUB Pol Ind Gaserans Calle B esquina calle D 17451 ST FELIU DE BUIXALLEU Girona tel 972 86 57 0 fax 972 86 54 44...

Page 18: ...t supplied 2 OPERATING INSTRUCTIONS 2 1 Introduction Dear Customer Thank you for choosing MIKRO P7 P12 a FER burner featuring advanced design cut ting edge technology high reliability and quality cons...

Page 19: ...5 fig 1 7 12 00 and Radiator flashing 4 Use the and buttons details 4 and 6 fig 1 to modify the start of the 2nd OFF time band e g 14 00Press the Programming button P detail 5 fig 1 8 16 30 and Radia...

Page 20: ...dusts or volatile substances which drawn by the fan can obstruct the pipes inside the burner or the combustion head The room must be dry and not exposed to rain snow or frost Fix the burner to the do...

Page 21: ...d the display returns to normal operation 7 If the first attempt was not sufficient repeat the previous sequence from point 4 to start the second attempt 8 If the second attempt was not sufficient rep...

Page 22: ...he nut C and disconnect the body undo the fixing screws D and remove the nozzle E fig 10 Checks on parts and components Fan Make sure no dust has accumulated inside the fan and on the blades it reduce...

Page 23: ...P12 5 2 General view and main components fig 13 Key 1 Pressure transducer 2 Controller 3 Burner body 4 Terminal block 5 User interface 6 Heating element 7 Photoresistance 8 Thermostat 85 9 Burner load...

Page 24: ...al E Burner reset Data Unit MIKRO P7 MIKRO P12 Max heating capacity kW 34 1 55 0 Q Min heating capacity kW 13 7 30 0 Q Max fuel delivery kg h 7 2 11 6 Min fuel delivery kg h 2 9 6 3 Electrical protect...

Page 25: ...14 BG 1 2 2 1 MIKRO P7 P12 FER MIKRO P7 P12 CO NOx 2 2 3 A B C 1 7 8 14 10 1 2 3 10 4 nOCU 5 8 9 16 17 18 19 10 11 12 13 14 15 1 2 3 4 5 6 7 1 A B C 1 2 3 Override 4 5 6 7 8 9 10 11 12 13 Override 14...

Page 26: ...5 0 Q kW 13 7 30 0 Q 7 2 11 6 2 9 6 3 IP X0D X0D V hz 230 50 230 50 W 100 100 W 300 300 11 13 5 195 323 140 226 6 35 6 35 0 2 0 2 OUT 15V GND DBM13 L N 4 5 6 7 8 9 10 11 12 A B E C D 13 14 X2 X1 X3 21...

Reviews: