AUTOMATIC DOORS FOR LIFTS

4

ECC 230 V

5 / 6 / 7 

POWER INPUTS 230 VOLTS SINGLE PHASE AC.

 

The circuit has been designed to operate on a mains supply of 230 V AC (+10%,-15%, 50 

or 60 Hz).

 

 

CONTROLS INPUTS

 

The circuit can work with external voltage inputs or by means a volt free contact input.

Open signal.

 

This signal orders the door to open. The tension to apply could be from 24 V DC to 60 

V DC or 100 V AC to 230 V AC, with an external supply between this input and common 

(10).

0 V.

 

Opposite pole to 12 V, in the case of using internal VOLTAGE, it should be connected to 

the common input.

10 

Common.

 

This input is the reference used for the open and close inputs.

11 

12 V.

 

 

            Isolated 12 V output available to control the door via a voltage free contact. Features are: 

 

 

    

 

a) This supply must only be used for this purpose.

 

 

 

 

b) This contact must be isolated from any other power supply.

12 

Close signal.

 

This signal is used for ordering to close the door.

13 / 14

 

Floor level.

 

This input activates the open movement in emergency rescue mode in case of power 

failure, through a 12 V battery to rescue the passengers from the lift. The door only will 

open if this signal is bridged (Normally Open).

PROGRAMING

 INPUTS

Open

Close

Voltage

 

OPEN

Voltage

 

CLOSE

Open

Close

OPEN

CLOSE

EXTERNAL VOLTAGE INPUT

VOLT FREE CONTACT INPUT

8

9

10

11

12

8

9

10

11

12

24...230 V

24...230 V

Open

Close

Without Voltage

OPEN

With Voltage

CLOSE

Open

Close

Voltage

OPEN

Voltage

CLOSE

1 INPUT

2 INPUTS

Com

12 V

0 V

8

9

10

11

12

Com

12 V

0 V

8

9

10

11

12

24...230 V

24...230 V

24...230 V

24...230 V

Summary of Contents for ECC 230 V

Page 1: ...MAN MUEC00000ENGTC 05 2016 ENG Assembly manual Automatic horizontal sliding car door Component ECC 230 V Electronic Module AUTOMATIC DOORS FOR LIFTS...

Page 2: ...PEN THE COVER FUERZA SAFETY OPEN SPEED VELOCIDAD ABRIR VELOCIDAD CERRAR CLOSE SPEED PULSAR PARA VERIFICAR PUSH TO CHECK THE DOOR SPECIAL ESPECIAL STANDARD EST NDAR MOTOR ENCODER FINAL CARRERA LIMIT SW...

Page 3: ...ra torque to be able to move heavy doors OFF Standard door Standard control is applied to perform the door movement 4 Floor level Inputs 12 V battery ON 2 Inputs 1 Input OFF Note With DIP switch No 4...

Page 4: ...ed 12 V output available to control the door via a voltage free contact Features are a This supply must only be used for this purpose b This contact must be isolated from any other power supply 12 Clo...

Page 5: ...approximately 5 Hz on for approximately 100 ms followed by off for approximately 100 ms LED single flash one short flash approximately 100 ms followed by a long off phase approximately 2 250 ms 21 22...

Page 6: ...tion of the Test pushbutton will cause a door open or close cycle 39 Safety La velocit di apertura della porta pu essere regolata da 100 mm s fino a 300 mm s 40 Close speed The door closing speed can...

Page 7: ...ximum 5 A Voltage 240 V PERFORMANCE Open Speed 100 300 mm s Close speed 100 300 mm s Safety force 40 150 N adjustable REFERENCE DATA DECLARATION OF CONFORMITY Herewith declares that the products menti...