Switch off the VF control before connecting the open and close command cables. Do not 

mix the voltages from the lift controller with the internal ones in the VF control (9: 12 V 

and 11: 0 V).

B   Put the potentiometers to the minimum.

 

- Close Speed (52).

 

- Open Speed (53).

 

- Safety (54).

C  Test the door. 

 

- Check from the landing door side. 

 

- Press the «TEST» button and establish the potentiometers (open speed, close speed and the    

safety force) in order to get the required adjustment. 

 Information: 

The VF parameters could be adjusted with the Fermator programming tool.

Remove the photocell wiring from any place where there are “electric noises” such as motors, 

supplies wiring, etc.

A

  Verify that there is an emitter and a receiver (E mark and R mark on the capsules) connected to the 

correct cable (emitter to the yellow cable and receiver to the green one).

B

  Connect the photocell (on the operator).

Even if you will not install the photocell, make the learning of the photocell to avoid that 

the photocell relay is active by no reason. Once the photocell is verified, it is possible to 

disconnect it and the VF control will detect that is not connected anymore.

C

  Put the capsules face to face at a minimum distance of 50 cm, make the autoadjusment process 

without hitting the capsules, once done, make a open and a close movement, and then block the 

photocell with the hand during the close movement to check that the Photocell relay is active every 

time the hand is in the middle of the infrared beam.

NORMAL REGULATION WITH THE LIFT CONTROLLER

TEST OF THE PHOTOCELL

12

11

10

9

8

EXTERNAL VOLTAGE INPUTS

Open

Close

Voltage

 

12 V DC...60 V DC,

100 V AC... 230 V AC.

OPEN

Voltage

 

12 V DC...60 V DC,

100 V AC... 230 V AC.

CLOSE

12

11

10

9

8

INTERNAL VOLTAGE INPUTS

Open

Close

OPEN

CLOSE

Summary of Contents for VCI-VF5A.CD0 Series

Page 1: ...ENG Assembly manual Automatic horizontal sliding car door Component VF5 Electronic Module AUTOMATIC DOORS FOR LIFTS MAN MMCAENGV5TC 10 2017...

Page 2: ...lose 100 230V AC DC PM ASYNC 13 Derecha Right QCI VF5A CD0EE ENCODER 12 V COM CERRAR LENTO SLOW CLOSE REABRIR RE OPEN SE AL DE PISO FLOOR LEVEL ENTRADAS PRIORITARIAS PRIORITY INPUTS FOTOC LULA PHOTOCE...

Page 3: ...s to open In the absence of a signal the doors will remain static If both inputs are applied then the open signal has priority 2 Automatic Semiautomatic ON Automatic Operators with skate automatic lan...

Page 4: ...from the supply It is important that the Door Operator Module has a GOOD EARTH CONNECTION The circuit can work with external voltage inputs or internal voltage input voltage free contact 8 Close signa...

Page 5: ...trol is the optional incorporation of the Fermator photocell It is composed by a emitter and receptor infrared 21 Re open This signal is used for installing the cabin door switch or an external barrie...

Page 6: ...0 41 Obstruction Led indicator and relay activated when an obstacle is detected that stops the doors from closing The signal will reset when the doors reach the opened or closed position Note In USA m...

Page 7: ...rocessor will calculate the acceleration and deceleration ramps and the braking torque required to give the optimum control of the doors 52 Close speed The door closing speed can be independently adju...

Page 8: ...te of the photocell Priorities 1 21 23 Reopening 2 Obstacle 3 25 23 Slow Closing 4 17 20 Photocell 5 8 Close SLAVE 2 INPUTS Configuration 1 ON 2 Inputs 2 Depends on type of door 3 Depends on type of d...

Page 9: ...with this configuration then there is a mechanical problem or electric motor or controller not supplied 6 Place the door in a middle position in order to see the starting movement 7 Switch on the VF...

Page 10: ...the encoder if nothing solves it The door opens instead of close Verify the DIP switch 3 position Reverse 2 phases of the motor connection 56 The door makes the learning phase correctly but the skate...

Page 11: ...e correct cable emitter to the yellow cable and receiver to the green one B Connect the photocell on the operator Even if you will not install the photocell make the learning of the photocell to avoid...

Page 12: ...is the clear entrance of any controller that has never been adjusted Therefore an autoadjustment is required check the autoadjustment process The door opens but doesn t close Check if the photocell L...

Page 13: ...of the motor and consequently the encoder is sending a wrong information Adjust the belt tension and make the autoadjustment again The system gets power but doesn t work and the led ON is off Check i...

Page 14: ...oltage supply 230 V Power 250 W Nominal torque 1 5 N m Nominal speed 900 RPM Thermic class F 155 C MOTOR PM Synchronous permanent magnet 10 pole Voltage supply 88 V Power 63 W Nominal torque 1 N m Nom...

Page 15: ...ioned below conform with the following E U council directives European Directive 2014 30 EU on Eelectromagnetic Compatibility EMC in accordance with the Product family standard for lifts escalators an...

Page 16: ...ge produced in the equipment described in this manual and associated installation if the instructions given have not been followed TECNOLAMA reserves the rights to modify the products specifications o...

Reviews: