3
VF5
AUTOMATIC DOORS FOR LIFTS
1
O
N
2 3 4
O
F
F
PROGRAMMING
The VF may be programmed using the DIP switches on the front of the unit. If any
change is made to any of the above switch selections, the main supply of the VF 5
unit MUST be switched OFF and ON again to read the new programming.
The switches functions are:
1
1 & 2 Inputs.
ON:
1 Input.
The door control unit will be controlled by a single input. Any voltage between 12 V DC to
60 V DC or door remains opened. When it activates the door close. Open input is not used.
OFF:
2 Inputs.
The door control module will be controlled by two independent inputs. Any voltage bet-
ween 12 V DC to 60 V DC or 100 V AC to 230 V AC applied between terminals 8 & 10 will
cause the doors to close. And between terminals 10 & 12 will cause the doors to open.
In the absence of a signal, the doors will remain static. If both inputs are applied then the
open signal has priority.
2
Automatic/ Semiautomatic.
ON:
Automatic.
Operators with skate (automatic landing). In this case a special movement is made for
locking and unlocking the skate.
OFF:
Semiautomatic.
Operators without skate (Semiautomatic landing door)
3
Rotation sense.
ON:
Lock at the picture:
-Skate fixed on the top side of the belt
and the motor on the right side.
-Skate fixed on the bottom side of the
belt and the motor on the left side.
OFF:
Lock at the picture:
-Skate fixed on the bottom side of the
belt and the motor on the right side.
-Skate fixed on the top side of the belt
and the motor on the left side.
Com
0 V
12 V
8
9
10
11
12
1 INPUTS
Close
Open
Without Voltage
0 V
OPEN
With Voltage
12 V DC...250 V DC,
100 V AC..230 V AC
CLOSE
Com
0 V
12 V
8
9
10
11
12
2 INPUTS
Close
Open
Voltage
12 V DC...60 V DC,
100 V AC...230 V AC
CLOSE
Voltage
12 V DC...250 V DC,
100 V AC...230 V AC
OPEN