background image

SKY F

13

EN

cod. 3540Z105  -  Rev. 01 - 01/2018

DHW power adjustment

To adjust the DHW power, switch the boiler to 

TEST

 mode (see sec. 4.1). Press the 

“+”

and 

“-”

 buttons (details 1 and 2 - fig. 1) to increase or decrease the power (min. = 00 -

max. = 100). Press the 

reset

 button within 5 seconds and the max. power will remain that

just set. Exit the 

TEST

 mode (see sec. 4.1).

4.2 Commissioning
Before lighting the water heater

Check the tightness of the gas system.

Fill the water system and make sure all air contained in the water heater and the sys-
tem has been vented.

Make sure there are no water leaks in the system or unit.

Check correct connection of the electrical system and efficiency of the earthing system.

Make sure the gas pressure value is that required.

Make sure there are no flammable liquids or materials in the immediate vicinity of
the water heater.

B

IF THE ABOVE INSTRUCTIONS ARE NOT OBSERVED THERE MAY BE
RISK OF SUFFOCATION OR POISONING DUE TO GAS OR FUMES ES-
CAPING; DANGER OF FIRE OR EXPLOSION. ALSO, THERE MAY BE A
RISK OF ELECTRIC SHOCK OR FLOODING THE ROOM.

Checks during operation

Turn the unit on.

Check the tightness of the fuel circuit and water systems.

Check the efficiency of the flue and air/fume ducts while the water heater is working.

Make sure the gas valve modulates properly.

Check correct lighting of the water heater, by turning it on and off several times.

Make sure the fuel consumption indicated on the meter matches that given in the
technical data table on cap. 5.

4.3 Maintenance instructions
IMPORTANT

B

ALL MAINTENANCE WORK AND REPLACEMENTS MUST BE CARRIED
OUT BY SKILLED QUALIFIED PERSONNEL.
Before carrying out any operation inside the boiler, disconnect the power
and close the gas cock upstream. Otherwise there may be a danger of ex-
plosion, electric shock, suffocation or poisoning.

Periodical inspection

To ensure proper operation of the unit over time, have qualified personnel carry out a
yearly inspection, providing for the following checks:

The control and safety devices (gas valve, flow switch, etc.) must function correctly.

The fume exhaust circuit must be perfectly efficient.

The air/fume terminal and ducts must be free of obstructions and leaks

The burner and exchanger must be clean and free of deposits. For possible clean-
ing, do not use chemical products or wire brushes.

The electrode must be properly positioned and free of deposits.

fig. 12 - Electrode positioning

The gas and water systems must be tight.

The gas flow and pressure must match that given in the respective tables.

4.4 Troubleshooting
Diagnostics

The water heater has an advanced self-diagnosis system. In case of a fault in the unit,
the display will flash together with the fault symbol indicating the fault code.
There are faults that cause permanent shutdown (marked with the letter "

A

"): to restore

operation press the RESET button (detail 6 - fig. 1) for 1 second. If the water heater fails
to restart, it is necessary to eliminate the fault.
Other faults (marked with the letter "

F

") cause temporary shutdowns that are automati-

cally reset as soon as the value returns within the water heater's normal working range.

List of faults

Table. 6

fig. 10 - Gas valve

A

 - Upstream pressure point

B

 - Downstream pressure point

I

 - Gas valve electrical connection

R

 - Gas outlet

S

 - Gas inlet

fig. 11 - Gas valve connection

TYPE SGV100
Pi max 65 mbar
24 Vdc - class B+A

R

B

I

A

S

~ 65

W

~ 24

W

1  2  3  4

±

 0,5

=

=

Fault
code

Fault

Possible cause

Cure

A01

No burner ignition

No gas

Check the regular gas flow to the 
water heater and that the air has been 
eliminated from the pipes

Ignition/detection  electrode fault

Check the wiring of the electrode and 
that it is correctly positioned and free 
of any deposits

Faulty gas valve

Check gas valve and replace it if nec-
essary

Gas valve wiring disconnected

Check the wiring

Ignition power too low

Adjust the ignition  power

A02

Flame present signal with 
burner off

Electrode fault

Check the ionisation electrode wiring

Card fault

Check the card

A03

Overtemperature protec-
tion activation

DHW sensor damaged

Check the correct positioning and 
operation of the DHW sensor

No water circulation

Check the flowswitch

F04

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

F05

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

Fan fault

Wiring disconnected

Check the wiring

Faulty fan

Check the fan

Card fault

Check the card

A06

No flame after the ignition 
phase

Low pressure in the gas system

Check the gas pressure

Burner minimum pressure setting Check the pressures

F07

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

A09

Gas valve fault

Wiring disconnected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

F10

DHW sensor 1 fault

Sensor damaged

Check the wiring or replace the sen-
sor

Wiring shorted
Wiring disconnected

F14

DHW sensor 2 fault

Sensor damaged

Check the wiring or replace the sen-
sor

Wiring shorted
Wiring disconnected

A16

Gas valve fault

Wiring disconnected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

F20

Combustion control fault

Fan fault

Check the fan and fan wiring

Wrong baffle

Check the baffle and replace it if nec-
essary

Flue obstructed or not correctly 
sized

Check the flue

A21

Poor combustion fault

Fault F20 generated 6 times in the 
last 10 minutes

See fault F20

F34

Supply voltage under 180V. Electric mains trouble

Check the electrical system

F35

Faulty mains frequency

Electric mains trouble

Check the electrical system

A41

Sensor positioning

DHW sensor disconnected from 
pipe

Check the correct positioning and 
operation of the sensor

F42

DHW sensor fault

Sensor damaged

Replace the sensor

F50

Gas valve fault

Modulating Operator wiring dis-
connected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

A51

Poor combustion fault

Inlet/exhaust flue obstruction

Check the flue

Summary of Contents for SKY 11 F

Page 1: ... 2018 SKY F 595 E A 11 F 14 F 17 F A mm 295 335 375 C D B E mm 210 250 290 Modello 195 200 118 C B D 40 50 50 27 IT ISTRUZIONI PER L USO L INSTALLAZIONE E LA MANUTENZIONE EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...

Page 2: ...a funzione anomalia combustione 10 Connessione Service Tool Indicazione durante il funzionamento Durante la richiesta sanitario generata dal prelievo d acqua calda sanitaria il display part 5 fig 1 visualizza l attuale temperatura d uscita dell acqua calda sanitaria Anomalia In caso di anomalia vedi cap 4 4 il display part 5 fig 1 visualizza il codice di guasto e durante i tempi di attesa di sicur...

Page 3: ...NE LEGGERE LE ISTRUZIONI DI INSTALLAZIONE E DI MANUTENZIONE PRI MA DI INSTALLARE L APPARECCHIO RISPETTARE ANCHE LE INTRUZIONI DI PROGETTAZIONE Avvertenze L apparecchio è di tipo C a camera stagna e tiraggio forzato l ingresso aria e l uscita fumi devono essere collegati ad uno dei sistemi di evacuazione aspirazione indicati di seguito L apparecchio è omologato per il funzionamento con tutte le con...

Page 4: ...attivare la modalità TEST Lo scaldabagno si accende al massimo della potenza sanitario imposta ta come al paragrafo successivo Sul display verrà visualizzata la potenza sanitario fig 9 Modalità TEST potenza sanitario 100 Premere i tasti part 1 e 2 fig 1 per aumentare o diminuire la potenza Minima 0 Massima 100 Per disattivare la modalità TEST premere contemporaneamente i tasti part 1 e 2 fig 1 per...

Page 5: ... causano blocchi temporanei contraddistinte con la lettera F che ven gono ripristinati automaticamente non appena il valore rientra nel campo di funziona mento normale dello scaldabagno Lista anomalie Tabella 6 fig 10 Valvola gas A Presa di pressione a monte B Presa di pressione a valle I Connessione elettrica Valvola gas R Uscita gas S Entrata gas fig 11 Connessione valvola gas TYPE SGV100 Pi max...

Page 6: ...ORIA GAS G20 II2H3B P CATEGORIA GAS G31 II2H3 Portata termica max kW 21 7 26 9 32 9 Q Portata termica min kW 8 3 10 3 12 6 Q Potenza Termica max kW 19 2 23 9 29 2 Potenza Termica min kW 7 1 8 8 10 7 Rendimento Pmax 88 5 88 7 88 9 Ugelli bruciatore G20 n x Ø 10 x 1 25 12 x 1 25 14 x 1 25 Pressione gas alimentazione G20 mbar 20 0 20 0 20 0 Pressione gas max al bruciatore mbar 13 0 14 0 15 0 Pression...

Page 7: ...Ž Ěŝ ĞŶĞƌŐŝĂ ĞůĞƚƚƌŝĐĂ ŽŶƐƵŵŽ ĂŶŶƵŽ Ěŝ ĞŶĞƌŐŝĂ ĞůĞƚƚƌŝĐĂ ĨĨŝĐŝĞŶnjĂ ĞŶĞƌŐĞƚŝĐĂ Ěŝ ƌŝƐĐĂůĚĂŵĞŶƚŽ ĚĞůů ĂĐƋƵĂ ŽŶƐƵŵŽ ŐŝŽƌŶĂůŝĞƌŽ Ěŝ ĐŽŵďƵƐƚŝďŝůĞ ŽŶƐƵŵŽ ĂŶŶƵŽ Ěŝ ĐŽŵďƵƐƚŝďŝůĞ ŵƉŽƐƚĂnjŝŽŶŝ Ěŝ ƚĞŵƉĞƌĂƚƵƌĂ ƚĞƌŵŽƐƚĂƚŽ ƋƵĂůĞ ĐŽŵŵĞƌĐŝĂůŝnjnjĂƚŽ ŝǀĞůůŽ ĚĞůůĂ ƉŽƚĞŶnjĂ ƐŽŶŽƌĂ Ăůů ŝŶƚĞƌŶŽ ŵŝƐƐŝŽŶŝ Ěŝ ŽƐƐŝĚŝ Ě ĂnjŽƚŽ DĂƌĐŚŝŽ ZZK dŝƉŽ Ěŝ ƉƌŽĚŽƚƚŽ ĐĂůĚĂĐƋƵĂ ĐŽŶǀĞŶnjŝŽŶĂůĞ ŝŵďŽůŽ hŶŝƚă sĂůŽƌĞ YĞůĞĐ EtŚ YĨƵĞů t EKdž ŬtŚ ŬtŚ...

Page 8: ...SKY F 8 IT cod 3540Z105 Rev 01 01 2018 5 4 Schema elettrico fig 15 Circuito elettrico 81 1kW L N 230V 50 Hz 16 N L ABM02 73 R1 R2 R3 R4 288 T T 344 4 3 2 1 44 38 ...

Page 9: ...ƐƐĂ ƐĐůƵƐŝŽŶŝ ŽŶŽ ĞƐĐůƵƐŝ ĚĂůůĂ ƉƌĞƐĞŶƚĞ ŐĂƌĂŶnjŝĂ ŝ ĚŝĨĞƫ Ěŝ ĐŽŶĨŽƌŵŝƚă ĐĂƵƐĂƟ ĚĂ ͻ ƚƌĂƐƉŽƌƚŽ ŶŽŶ ĞīĞƩƵĂƚŽ Ă ĐƵƌĂ ĚĞůů ĂnjŝĞŶĚĂ ƉƌŽĚƵƩƌŝĐĞ ͻ ĂŶŽƌŵĂůŝƚă Ž ĂŶŽŵĂůŝĞ Ěŝ ƋƵĂůƐŝĂƐŝ ŐĞŶĞƌĞ ŶĞůů ĂůŝŵĞŶƚĂnjŝŽŶĞ ĚĞŐůŝ ŝŵƉŝĂŶƟ ŝĚƌĂƵůŝĐŝ ĞůĞƩƌŝĐŝ Ěŝ ĞƌŽŐĂnjŝŽŶĞ ĚĞů ĐŽŵďƵƐƟďŝůĞ Ěŝ ĐĂŵŝŶŝ Ğ Ž ƐĐĂƌŝĐŚŝ ͻ ĐĂůĐĂƌĞ ŝŶĂĚĞŐƵĂƟ ƚƌĂƩĂŵĞŶƟ ĚĞůů ĂĐƋƵĂ Ğ Ž ƚƌĂƩĂŵĞŶƟ ĚŝƐŝŶĐƌŽƐƚĂŶƟ ĞƌƌŽŶĞĂŵĞŶƚĞ ĞīĞƩƵĂƟ ͻ ĐŽƌƌŽƐŝŽŶŝ ĐĂƵƐĂƚĞ ĚĂ...

Page 10: ...on During a DHW demand generated by drawing domestic hot water the display detail 5 fig 1 shows the actual DHW outlet temperature Fault In case of a fault see cap 4 4 the display detail 5 fig 1 shows the fault code and during safety standby times the messages d3 and d4 2 3 Lighting and shutdown ATTENTION WHEN THE UNIT IS WORKING THE CASING MAY BE VERY HOT AVOID CON TACT RISK OF BURNS Connection to...

Page 11: ...ION OR INTOXICATION READ THE INSTALLATION AND MAINTENANCE INSTRUCTIONS BE FORE INSTALLING THE UNIT ALSO FOLLOW THE DESIGN INSTRUCTIONS Important The unit is a C type with sealed chamber and forced draught the air inlet and fume out let must be connected to one of the following extraction suction systems The unit is ap proved for operation with all the Cny flue configurations given on the dataplate...

Page 12: ... at the maximum DHW power set as described in the following section The DHW power will be shown on the display fig 9 TEST mode DHW power 100 Press the buttons details 1 and 2 fig 1 to increase or decrease the power Min 0 Max 100 To deactivate the TEST mode press the buttons details 1 and 2 fig 1 together for 5 seconds The TEST mode is automatically disabled in any case after 15 minutes or on stopp...

Page 13: ...art it is necessary to eliminate the fault Other faults marked with the letter F cause temporary shutdowns that are automati cally reset as soon as the value returns within the water heater s normal working range List of faults Table 6 fig 10 Gas valve A Upstream pressure point B Downstream pressure point I Gas valve electrical connection R Gas outlet S Gas inlet fig 11 Gas valve connection TYPE S...

Page 14: ...EGORY G20 II2H3B P GAS CATEGORY G31 II2H3 Max heating capacity kW 21 7 26 9 32 9 Q Min heating capacity kW 8 3 10 3 12 6 Q Max heat output kW 19 2 23 9 29 2 Min heat output kW 7 1 8 8 10 7 Pmax efficiency 88 5 88 7 88 9 Burner nozzles G20 no x Ø 10 x 1 25 12 x 1 25 14 x 1 25 Gas supply pressure G20 mbar 20 0 20 0 20 0 Max gas pressure at burner mbar 13 0 14 0 15 0 Min gas pressure at burner mbar 2...

Page 15: ...н ƚŽ Ϳ ĂŝůLJ ĞůĞĐƚƌŝĐŝƚLJ ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĞůĞĐƚƌŝĐŝƚLJ ĐŽŶƐƵŵƉƚŝŽŶ tĂƚĞƌ ŚĞĂƚŝŶŐ ĞŶĞƌŐLJ ĞĨĨŝĐŝĞŶĐLJ ĂŝůLJ ĨƵĞů ĐŽŶƐƵŵƉƚŝŽŶ ŶŶƵĂů ĨƵĞů ĐŽŶƐƵŵƉƚŝŽŶ dŚĞƌŵŽƐƚĂƚ ƚĞŵƉĞƌĂƚƵƌĞ ƐĞƚƚŝŶŐƐ ŽĨ ƚŚĞ ǁĂƚĞƌ ŚĞĂƚĞƌ ĂƐ ƉůĂĐĞĚ ŽŶ ƚŚĞ ŵĂƌŬĞƚ ŽƵŶĚ ƉŽǁĞƌ ůĞǀĞů ŵŝƐƐŝŽŶƐ ŽĨ ŶŝƚƌŽŐĞŶ ŽdžŝĚĞƐ dƌĂĚĞŵĂƌŬ ZZK dLJƉĞ ŽŶǀĞŶƚŝŽŶĂů ǁĂƚĞƌ ŚĞĂƚĞƌ LJŵďŽů hŶŝƚ sĂůƵĞ YĞůĞĐ EtŚ YĨƵĞů t EKdž ŬtŚ ŬtŚ й ŬtŚ Ě ŵŐ ŬtŚ DK z ϭϳ y Ϭ Ϭϯϯ ϴϭ Ϯϰ ϵϮϳ D y ...

Page 16: ...SKY F 16 EN cod 3540Z105 Rev 01 01 2018 5 4 Wiring diagram fig 15 Electrical circuit 81 1kW L N 230V 50 Hz 16 N L ABM02 73 R1 R2 R3 R4 288 T T 344 4 3 2 1 44 38 ...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ... DEEULFDWR LQ WDOLD 0DGH LQ WDO 552 6 S Via 5LWRQGD D 6DQ RQLIDFLR 9HURQD 7 ZZZ IHUUROL FRP ...

Reviews: