2.4

 

DC nanogrid connection 

1.

 

Connect the DC nanogrid cable to the marked terminals. 

2.

 

Make sure that all terminals are tightened to 2.5 Nm, use a 
torque wrench. 

 

 

 

3.

 

Place the front panel in position according to figure above. 

 

4.

 

Place the warning label on the front door.  

 

3

 

Maintenance 

When a fuse trips replace it with a fuse with the following 
specifications: 

 

Characteristic: gPV 

Dimensions: 10x38 mm 

Current rating: 15 A 

Voltage rating: 1000 VDC 

Breaking capacity: 20 kA 

 

 

Make sure that the DC nanogrid is connected 
to correct terminals. 

Check that 

all

 terminals and PE-connections 

are tightened to 2.5 Nm (there is a risk that 

the connections loosen during transportation 
due to vibration). 

 

Summary of Contents for Power Distribution 8

Page 1: ...Installation manual Swe En Power Distribution 8 Rev A01 Rev B01...

Page 2: ......

Page 3: ...troduction 6 1 1 Included items 6 1 2 Warnings and recommendations 6 1 3 Explanation of safety notices 6 1 4 Dimensions 6 1 5 Components 7 1 6 Connections 7 1 7 Inlets and cable glands 7 2 Installatio...

Page 4: ...ta enheter till liksp nningsn tet n r det r sp nningssatt VARNING Risk f r elektrisk st t och ljusb ge om produkten inte hanteras i enlighet med manualens instruktioner VARNING Anv nd inte produkten o...

Page 5: ...eller v rdsl s installation NOTERA Ferroamp rekommenderar att ndhylsor anv nds f r samtliga anslutningar med m ngtr diga ledare 2 1 N dv ndiga verktyg Skruvmejslar o Sp r 1x5 mm o Kryss TBD Hylsnyckla...

Page 6: ...8 NOTERA F r att ber kna korrekt kabeldimension anv nd Ferroamps kabelkalkylator som finns tillg nglig p www ferroamp se under supportfliken 1 Skruva loss t ckpl ten enligt bilden ovan T ckpl ten r ko...

Page 7: ...alen p kopplingssk pets front 3 Underh ll Vid byte av utl st s kring skall en s kring med f ljande specifikation anv ndas Driftklass gPV Dimensioner 10x38 mm Max str m 15 A M rksp nning 1000 VDC Brytf...

Page 8: ...lowed to connect units to the DC nanogrid when it is energized WARNING Risk of electrical shock arc if the product is not used according to the instructions in the manual WARNING Do not use the produc...

Page 9: ...NOTE We recommend that you use end terminals for all connection points that have multi threaded conductors 2 1 Required tools Screwdrivers o Slot drive 1x5 mm o Philips TBD Socket wrench o No 1 27 mm...

Page 10: ...calculate correct cable dimensions you can use Ferroamp s online cable calculator available at www ferroamp com under the support section 1 Unscrew the front plate as shown above The front plate is at...

Page 11: ...ng label on the front door 3 Maintenance When a fuse trips replace it with a fuse with the following specifications Characteristic gPV Dimensions 10x38 mm Current rating 15 A Voltage rating 1000 VDC B...

Page 12: ...Electricity Reinvented...

Reviews: