9
2.4
DC nanogrid connection
1.
Connect the DC nanogrid cable to the marked terminals.
2.
Make sure that all terminals are tightened to 2.5 Nm, use a
torque wrench.
3.
Place the front panel in position according to figure above.
4.
Place the warning label on the front door.
3
Maintenance
When a fuse trips replace it with a fuse with the following
specifications:
Characteristic: gPV
Dimensions: 10x38 mm
Current rating: 15 A
Voltage rating: 1000 VDC
Breaking capacity: 20 kA
•
Make sure that the DC nanogrid is connected
to correct terminals.
•
Check that
all
terminals and PE-connections
are tightened to 2.5 Nm (there is a risk that
the connections loosen during transportation
due to vibration).